VLT
Model
Bussman
PN
Littelfuse PN Littelfuse
PN
Bussmann
PN
Siba PN
Ferraz-Shawmut
PN
Ferraz-Shawmut PN
(Europe)
Ferraz-Shawmut PN
(North America)
N90K
170M2619 LA50QS300-4 L50S-300
FWH-300A 20 610
31.315
A50QS300-4
6.9URD31D08A0315
A070URD31KI0315
N110
170M2620 LA50QS350-4 L50S-350
FWH-350A 20 610
31.350
A50QS350-4
6.9URD31D08A0350
A070URD31KI0350
N132
170M2621 LA50QS400-4 L50S-400
FWH-400A 20 610
31.400
A50QS400-4
6.9URD31D08A0400
A070URD31KI0400
N160
170M4015 LA50QS500-4 L50S-500
FWH-500A 20 610
31.550
A50QS500-4
6.9URD31D08A0550
A070URD31KI0550
N200
170M4016 LA50QS600-4 L50S-600
FWH-600A 20 610
31.630
A50QS600-4
6.9URD31D08A0630
A070URD31KI0630
N250
170M4017 LA50QS800-4 L50S-800
FWH-800A 20 610
31.800
A50QS800-4
6.9URD32D08A0800
A070URD31KI0800
Table 10.6 Fuse Options for 380–500 V Adjustable Frequency Drives
VLT© Model
Bussmann PN
Siba PN
Ferraz-Shawmut European PN
Ferraz-Shawmut North American PN
N55k T7
170M2616
20 610 31.160
6.9URD30D08A0160
A070URD30KI0160
N75k T7
170M2619
20 610 31.315
6.9URD31D08A0315
A070URD31KI0315
N90k T7
170M2619
20 610 31.315
6.9URD31D08A0315
A070URD31KI0315
N110 T7
170M2619
20 610 31.315
6.9URD31D08A0315
A070URD31KI0315
N132 T7
170M2619
20 610 31.315
6.9URD31D08A0315
A070URD31KI0315
N160 T7
170M4015
20 620 31.550
6.9URD32D08A0550
A070URD32KI0550
N200 T7
170M4015
20 620 31.550
6.9URD32D08A0550
A070URD32KI0550
N250 T7
170M4015
20 620 31.550
6.9URD32D08A0550
A070URD32KI0550
N315 T7
170M4015
20 620 31.550
6.9URD32D08A0550
A070URD32KI0550
Table 10.7 Fuse Options for 525–690 V Adjustable Frequency Drives
For UL compliance, for units supplied without a contactor-
only option, the Bussmann 170M series fuses must be
used. See
for SCCR ratings and UL fuse criteria if
a contactor-only option is supplied with the adjustable
frequency drive.
10.3.3 Short Circuit Current Rating (SCCR)
If the adjustable frequency drive is not supplied with a line
power disconnect, contactor or circuit breaker, the Short
Circuit Current Rating (SCCR) of the adjustable frequency
drives is 100,000 amps at all voltages (380–690 V).
If the adjustable frequency drive is supplied with a line
power disconnect, the SCCR of the adjustable frequency
drive is 100,000 amps at all voltages (380–690 V).
If the adjustable frequency drive is supplied with a circuit
breaker, the SCCR depends on the voltage, see
:
415 V
480 V
600 V
690 V
D6h frame
120,000 A
100,000 A
65,000 A
70,000 A
D8h frame
100,000 A
100,000 A
42,000 A
30,000 A
Table 10.8 Adjustable Frequency Drive
Supplied with a Circuit Breaker
If the adjustable frequency drive is supplied with a
contactor-only option and is externally fused according to
, the SCCR of the adjustable frequency drive is as
follows:
415 V
IEC
1)
480 V
UL
2)
600 V
UL
2)
690 V
IEC
1)
D6h frame
100,000 A 100,000 A
100,000 A 100,000 A
D8h frame (not
including the
N250T5)
100,000 A 100,000 A
100,000 A 100,000 A
D8h frame
(N250T5 only)
100,000 A Consult
factory
Not applicable
Table 10.9 Adjustable Frequency Drive Supplied with a Contactor
1)
With a Bussmann type LPJ-SP or Gould Shawmut type AJT fuse.
450 A max fuse size for D6h and 900 A max fuse size for D8h.
Specifications
VLT
®
Automation Drive D-Frame
Instruction Manual
MG34U222 - VLT
®
is a registered Danfoss trademark
10-9
10
10
Содержание VLT AutomationDrive FC 300
Страница 1: ...MAKING MODERN LIVING POSSIBLE Instruction Manual 90 kW 315 kW D frame VLT AutomationDrive FC 300...
Страница 2: ......
Страница 4: ...Safety VLT Automation Drive D Frame Instruction Manual MG34U222 VLT is a registered Danfoss trademark...
Страница 98: ...www danfoss com drives MG34U222 130R0291 MG34U222 Rev 2012 11 15...