No.
Text
2561
No communication from DSP to ATACD
2562
No communication from ATACD to DSP (state
running)
2816
Stack overflow control board module
2817
Scheduler slow tasks
2818
Fast tasks
2819
Parameter thread
2820
LCP stack overflow
2821
Serial port overflow
2822
USB port overflow
2836
cfListMempool too small
3072-5122 Parameter value is outside its limits
5123
Option in slot A: Hardware incompatible with
control board hardware
5124
Option in slot B: Hardware incompatible with
control board hardware.
5125
Option in slot C0: Hardware incompatible with
control board hardware.
5126
Option in slot C1: Hardware incompatible with
control board hardware.
5376-6231 Out of memory
Table 8.3
ALARM 39, Heatsink sensor
No feedback from the heatsink temperature sensor.
The signal from the IGBT thermal sensor is not available on
the power card. The problem could be on the power card,
on the gate drive card, or the ribbon cable between the
power card and gate drive card.
WARNING 40, Overload of digital output terminal 27
Check the load connected to terminal 27 or remove short-
circuit connection. Check
5-00 Digital I/O Mode
and
5-01 Terminal 27 Mode
.
WARNING 41, Overload of digital output terminal 29
Check the load connected to terminal 29 or remove short-
circuit connection. Check
5-00 Digital I/O Mode
and
5-02 Terminal 29 Mode
.
WARNING 42, Overload of digital output on X30/6 or
overload of digital output on X30/7
For X30/6, check the load connected to X30/6 or remove
the short-circuit connection. Check
5-32 Term X30/6 Digi
Out (MCB 101)
.
For X30/7, check the load connected to X30/7 or remove
the short-circuit connection. Check
5-33 Term X30/7 Digi
Out (MCB 101)
.
ALARM 46, Power card supply
The supply on the power card is out of range.
There are three power supplies generated by the switch
mode power supply (SMPS) on the power card: 24 V, 5 V,
±
18 V. When powered with 24 V DC with the MCB 107
option, only the 24 V and 5 V supplies are monitored.
When powered with three phase AC line voltage, all three
supplies are monitored.
WARNING 47, 24 V supply low
The 24 V DC is measured on the control card. The external
24 V DC backup power supply may be overloaded,
otherwise contact the Danfoss supplier.
WARNING 48, 1.8 V supply low
The 1.8 V DC supply used on the control card is outside of
allowable limits. The power supply is measured on the
control card. Check for a defective control card. If an
option card is present, check for an overvoltage condition.
WARNING 49, Speed limit
When the speed is not within the specified range in
4-11 Motor Speed Low Limit [RPM]
and
4-13 Motor Speed
High Limit [RPM]
, the adjustable frequency drive shows a
warning. When the speed is below the specified limit in
1-86 Trip Speed Low [RPM]
(except when starting or
stopping), the adjustable frequency drive will trip.
ALARM 50, AMA calibration failed
Contact your Danfoss supplier or Danfoss Service
Department.
ALARM 51, AMA check U
nom
and I
nom
The settings for motor voltage, motor current and motor
power are wrong. Check the settings in parameters 1-20 to
1-25.
ALARM 52, AMA low I
nom
The motor current is too low. Check the settings.
ALARM 53, AMA motor too big
The motor is too big for the AMA to operate.
ALARM 54, AMA motor too small
The motor is too small for the AMA to operate.
ALARM 55, AMA Parameter out of range
The parameter values of the motor are outside of the
acceptable range. AMA will not run.
ALARM 56, AMA interrupted by user
The user has interrupted the AMA.
ALARM 57, AMA internal fault
Try to restart AMA again a number of times until the AMA
is carried out. Note that repeated runs may heat the motor
to a level where the resistance Rs and Rr are increased. In
most cases, however, this is not critical.
ALARM 58, AMA internal fault
Contact your Danfoss supplier.
WARNING 59, Current limit
The current is higher than the value in
4-18 Current Limit
.
Ensure that Motor data in parameters 1-20 to 1-25 are set
correctly. Possibly increase the current limit. Be sure that
the system can operate safely at a higher limit.
Warnings and Alarms
VLT
®
Automation Drive D-Frame
Instruction Manual
MG34U222 - VLT
®
is a registered Danfoss trademark
8-9
8
8
Содержание VLT AutomationDrive FC 300
Страница 1: ...MAKING MODERN LIVING POSSIBLE Instruction Manual 90 kW 315 kW D frame VLT AutomationDrive FC 300...
Страница 2: ......
Страница 4: ...Safety VLT Automation Drive D Frame Instruction Manual MG34U222 VLT is a registered Danfoss trademark...
Страница 98: ...www danfoss com drives MG34U222 130R0291 MG34U222 Rev 2012 11 15...