FC 302 High/Normal Load*
N200
N250
N315
HO
NO
HO
NO
HO
NO
Typical Shaft output at 550 V [kW]
160
200
200
250
250
315
Typical Shaft output at 575 V [hp]
250
300
300
350
350
400
Typical Shaft output at 690 V [kW]
200
250
250
315
315
400
Enclosure IP21
D2h
D2h
D2h
Enclosure IP54
D2h
D2h
D2h
Enclosure IP20
D4h
D4h
D4h
Output current
Continuous (at 550 V) [A]
253
303
303
360
360
418
Intermittent (60 s overload) (at 550 V) [A]
380
333
455
396
540
460
Continuous (at 575/690 V) [A]
242
290
290
344
344
400
Intermittent (60 s overload) (at 575/690 V) [kVA]
363
319
435
378
516
440
Continuous kVA (at 550 V) [kVA]
241
289
289
343
343
398
Continuous kVA (at 575 V) [kVA]
241
289
289
343
343
398
Continuous kVA (at 690 V) [kVA]
289
347
347
411
411
478
Max. input current
Continuous (at 550 V) [A]
245
299
299
355
355
408
Continuous (at 575 V) [A]
234
286
286
339
339
390
Continuous (at 690 V)
240
296
296
352
352
400
Max. cable size: line power, motor, brake and load share
mm (AWG)
2x185 (2x350)
Max. external electrical fuses [A]
550
Estimated power loss at 575 V [W]
3012
3723
3642
4465
4146
5028
Estimated power loss at 690 V [W]
3123
3851
3771
4614
4258
5155
Weight, enclosure IP21, IP54 kg (lbs)
125 (275)
Weight, enclosure IP20 kg (lbs)
125 (275)
Efficiency
0.98
Output frequency
0–590 Hz
Heatsink overtemperature trip
230° F [110°C]
Control card ambient trip
167° F [75°C]
*High overload=150% current for 60 s, Normal overload=110% current for 60 s.
Table 10.3 Line Power Supply 3x525–690 V AC
The typical power loss is at nominal load conditions and expected to be within
±
15% (tolerance relates to variety
in voltage and cable conditions).
The losses are based on the default switching frequency. The losses increase significantly at higher switching
frequencies.
The options cabinet adds weight to the adjustable frequency drive. The maximum weight of the D5h–D8h frames
is shown in
Frame Size
Description
Maximum Weight [kg (lbs)]
D5h
D1h disconnect and/or brake chopper
166 (255)
D6h
D1h contactor and/or circuit breaker
129 (285)
D7h
D2h disconnect and/or brake chopper
200 (440)
D8h
D2h contactor and/or circuit breaker
225 (496)
Table 10.4 D5h–D8h Weights
Specifications
VLT
®
Automation Drive D-Frame
Instruction Manual
MG34U222 - VLT
®
is a registered Danfoss trademark
10-3
10
10
Содержание VLT AutomationDrive FC 300
Страница 1: ...MAKING MODERN LIVING POSSIBLE Instruction Manual 90 kW 315 kW D frame VLT AutomationDrive FC 300...
Страница 2: ......
Страница 4: ...Safety VLT Automation Drive D Frame Instruction Manual MG34U222 VLT is a registered Danfoss trademark...
Страница 98: ...www danfoss com drives MG34U222 130R0291 MG34U222 Rev 2012 11 15...