9.
Press [OK].
10.
Follow on-screen instructions.
11.
The test will run automatically and indicate when
it is complete.
3.5 Check Motor Rotation
Prior to running the frequency converter, check the motor
rotation. The motor will run briefly at 5Hz or the minimum
frequency set in
4-12 Motor Speed Low Limit [Hz]
.
1.
Press [Quick Menu].
2.
Scroll to
Q2 Quick Setup
.
3.
Press [OK].
4.
Scroll to
1-28 Motor Rotation Check
.
5.
Press [OK].
6.
Scroll to
Enable
.
The following text will appear:
Note! Motor may run in
wrong direction
.
7.
Press [OK].
8.
Follow the on-screen instructions.
To change the direction of rotation, remove power to the
frequency converter and wait for power to discharge.
Reverse the connection of any two of the three motor
cables on the motor or frequency converter side of the
connection.
3.6 Local-control Test
CAUTION
MOTOR START!
Ensure that the motor, system, and any attached
equipment is ready for start. It is the responsibility of the
user to ensure safe operation under any operational
condition. Failure to ensure that the motor, system, and
any attached equipment is ready for start could result in
personal injury or equipment damage.
NOTE
The hand on key on the LCP provides a local start
command to the frequency converter. The OFF key
provides the stop function.
When operating in local mode, the up and down arrows
on the LCP increase and decrease the speed output of the
frequency converter. The left and right arrow keys move
the display cursor in the numeric display.
1.
Press [Hand ON].
2.
Accelerate the frequency converter by pressing
[
▲
] to full speed. Moving the cursor left of the
decimal point provides quicker input changes.
3.
Note any acceleration problems.
4.
Press [OFF].
5.
Note any deceleration problems.
If acceleration problems were encountered
•
If warnings or alarms occur, see
•
Check that motor data is entered correctly
•
Increase the ramp-up time in
3-41 Ramp 1 Ramp
Up Time
•
Increase current limit in
4-18 Current Limit
•
Increase torque limit in
4-16 Torque Limit Motor
Mode
If deceleration problems were encountered
•
If warnings or alarms occur, see
•
Check that motor data is entered correctly
•
Increase the ramp-down time in
3-42 Ramp 1
Ramp Down Time
•
Enable overvoltage control in
2-17 Over-voltage
Control
See
8.4 Warning and Alarm Definitions
for resetting the
frequency converter after a trip.
NOTE
through
in this chapter
concludes the procedures for applying power to the
frequency converter, basic programming, set-up, and
functional testing.
3.7 System Start Up
The procedure in this section requires user-wiring and
application programming to be completed.
is intended to help with this task. Other
aids to application set-up are listed in
. The following procedure is recommended after
application set-up by the user is completed.
Start Up and Functional Tes...
VLT
®
AQUA Drive
Operating Instructions
MG.20.M8.02 - VLT
®
is a registered Danfoss trademark
27