6 Application Set Up Examples
6.1 Introduction
The examples in this section are intended as a quick
reference for common applications.
•
Parameter settings are the regional default values
unless otherwise indicated (selected in
0-03 Regional Settings
)
•
Parameters associated with the terminals and
their settings are shown next to the drawings
•
Where switch settings for analog terminals A53 or
A54 are required, these are also shown
6.2 Application Examples
Parameters
FC
4-20 mA
+24 V
+24 V
D IN
D IN
D IN
COM
D IN
D IN
D IN
D IN
+10 V
A IN
A IN
COM
A OUT
COM
12
13
18
19
20
27
29
32
33
37
50
53
54
55
42
39
A 54
U - I
+
-
130BB675.10
Function
Setting
6-22 Terminal 54 Low
Current
4mA*
6-23 Terminal 54 High
Current
20mA*
6-24 Terminal 54 Low
Ref./Feedb. Value
0*
6-25 Terminal 54 High
Ref./Feedb. Value
50*
* = Default Value
Notes/comments:
Table 6.1 Analog Current Feedback Transducer
Parameters
FC
+24 V
+24 V
D IN
D IN
D IN
COM
D IN
D IN
D IN
D IN
+10 V
A IN
A IN
COM
A OUT
COM
12
13
18
19
20
27
29
32
33
37
50
53
54
55
42
39
A54
U - I
0 - 10V
+
-
130BB676.10
Function
Setting
6-20 Terminal 54
Low Voltage
0.07V*
6-21 Terminal 54
High Voltage
10V*
6-24 Terminal 54
Low Ref./Feedb.
Value
0*
6-25 Terminal 54
High Ref./Feedb.
Value
50*
* = Default Value
Notes/comments:
Table 6.2 Analog Voltage Feedback Transducer (3-wire)
Parameters
FC
+24 V
+24 V
D IN
D IN
D IN
COM
D IN
D IN
D IN
D IN
+10 V
A IN
A IN
COM
A OUT
COM
12
13
18
19
20
27
29
32
33
37
50
53
54
55
42
39
A54
U - I
0 - 10V
+
-
130BB677.10
Function
Setting
6-20 Terminal 54
Low Voltage
0.07V*
6-21 Terminal 54
High Voltage
10V*
6-24 Terminal 54
Low Ref./Feedb.
Value
0*
6-25 Terminal 54
High Ref./Feedb.
Value
50*
* = Default Value
Notes/comments:
Table 6.3 Analog Voltage Feedback Transducer (4-wire)
Application Set Up Examples
VLT
®
AQUA Drive
Operating Instructions
46
MG.20.M8.02 - VLT
®
is a registered Danfoss trademark
6
6