Illustration 2.23 Installation to Achieve a Stopping Category 0 (EN 60204-1) with Safety Cat. 3 (EN 954-1) / PL “d” (ISO 13849-1).
1
Safety device Cat. 3 (circuit interrupt device, possibly
with release input)
7
Inverter
2
Door contact
8
Motor
3
Contactor (Coast)
9
5V DC
4
Frequency converter
10
Safe channel
5
Mains
11
Short-circuit protected cable (if not inside installation cabinet)
6
Control board
Table 2.5
Safe Stop Commissioning Test
After installation and before first operation, perform a commissioning test of the installation making use of safe stop.
Moreover, perform the test after each modification of the installation.