VLT
®
5000 FLUX
Installation
Please pay attention to the requirements
that apply to integration and field mounting
kit, see the below list. The information given
in the list must be observed to avoid serious damage
or injury, especially when installing large units.
The frequency converter
must
be installed vertically.
The frequency converter is cooled by means of air
circulation. For the unit to be able to release its cooling
air, the
minimum
distance over and below the unit
must be as shown in the illustration below.
To protect the unit from overheating, it must be ensured
that the ambient temperature
does not rise above the
max. temperature stated for the frequency converter
and that the 24-hour average temperature is not
exceeded
. The max. temperature and 24-hour average
can be seen from the General Technical section.
Derating of the frequency converter is required by
ambient temperature in the range of 45° C - 55° C.
See the section
Derating
in the Design Guide.
Service Life Time of the frequency converter will
be reduced if no derating is carried out in the
above ambient temperature range.
■
Enclosure type
IP 00
IP 20/Nema 1
IP 54
Bookstyle
-
OK
-
Compact
OK
OK
OK
■
Installation of VLT 5001-5302
All frequency converters must be installed in a
way that ensures proper cooling.
Cooling
All Bookstyle and Compact units require a minimum
space above and below the enclosure.
Side by side/flange by flange
All frequency converters can be mounted side
by side/flange by flange.
d [mm]
Comments
Bookstyle
VLT 5001-5006, 200-240 V
100
VLT 5001-5011, 380-500 V
100
Installation on a plane, vertical surface (no spacers)
Compact (all enclosure types)
VLT 5001-5006, 200-240 V
100
VLT 5001-5011, 380-500 V
100
Installation on a plane, vertical surface (no spacers)
VLT 5008-5027, 200-240 V
200
VLT 5016-5062, 380-500 V
200
VLT 5072-5102, 380-500 V
225
Installation on a plane, vertical surface (no spacers)
VLT 5032-5052, 200-240 V
225
VLT 5122-5302, 380-500 V
225
Installation on a plane, vertical surface (no spacers)
IP 54 filter mats must be changed when they are dirty.
MG.55.A6.02 - VLT is a registered Danfoss trademark
17