The brake is functioning.
Ramp operation (REM. RAMPING):
Remote
has been selected in parameter 002 and
the output speed is changed in accordance
with the ramps set.
Ramp operation (LOCAL RAMPING):
Local
has been selected in parameter 002 and
the output speed is changed in accordance
with the ramps set.
Ramp operation (MIXED RAMPING):
Local
has been selected in parameter 002 and
the output speed is changed in accordance
with the ramps set.
Running, remote control (REM. RUN OK):
Remote control has been selected in parameter 002 and
a start command is given on either terminal 18 (START
or LATCHED START in parameter 302), terminal 19
(START REVERSE parameter 303) or via the serial bus.
Running, local control (LOCAL RUN OK):
Local control has been selected in parameter 002
and a LCP start command has been givin
Running, local control (MIXED RUN OK):
Local control has been selected in parameter
002 and a start command is given on terminal 19
(START REVERSE parameter 303).
VLT ready, remote control (REM. UNIT READY):
Remote control
has been selected in parameter
002 and
Coasting stop
inverse in parameter 304,
and there is 0 V on terminal 27.
VLT ready, local control (LOCAL UNIT READY):
Local
has been selected in parameter 002 and
Hardware coast on terminal 37 is 0 V.
VLT ready, local control (MIXED UNIT READY):
Local
has been selected in parameter 002
and
Coasting inverse
in parameter 304, and
there is 0 V on terminal 27.
Quick-stop, remote control (REM. QSTOP):
Remote control
has been selected in parameter
002 and the frequency converter has stopped via
a quick-stop signal on terminal 27 (or possibly
via the serial communication port).
Quick-stop, local (MIXED QSTOP):
Local
has been selected in parameter 002 and
the frequency converter has stopped via a
quick-stop signal on terminal 27.
DC stop, remote control (REM. DC STOP):
Remote control
has been selected in parameter
002 and the frequency converter has stopped via
a DC stop signal on a digital input (or possibly
via the serial communication port).
DC braking, local (MIXED DC STOP):
Local
has been selected in parameter 002 and
the frequency converter has stopped via a DC
braking signal on terminal 27.
Stop, remote controlled (REM. STOP):
Remote control
has been selected in parameter
002 and the frequency converter has stopped
via the control panel or a digital input (or possibly
via the serial communication port).
Stop, local (LOCAL STOP):
Local
has been selected in parameter 002 and the
frequency converter has stopped via the control panel.
Stop, local (MIXED STOP):
Local
has been selected in parameter 002 and
the frequency converter has stopped via the
control panel or the digital input (or possibly via
the serial communication port).
Stand by (REM. STAND BY):
Remote control has been selected in parameter
002. The frequency converter will start when
it receives a start signal via a digital input (or
the serial communication port).
Freeze output (REM. FREEZE OUTPUT):
Remote control
has been selected in parameter 002
together with
Freeze reference
in parameter 300,
301, 305, 306 or 307, and the terminal in question
(16, 17, 29, 32 or 33) has been activated (or possibly
via the serial communication port).
Jog operation, remote controlled
(REM.RUN JOG):
Remote control
has been selected in parameter 002
and
Jog
in parameter 300, 301, 305, 306 or 307, and
the terminal in question (16, 17, 29, 32 or 33) has been
activated (or possibly via the serial communication port).
Jog operation, local (LOCAL RUN JOG):
Local
has been selected in parameter 002 and
LCP Jog
enabled and activated.
Jog operation, local (MIXED RUN JOG):
Local
has been selected in parameter 002 and
LCP Jog
enabled and activated.
Overvoltage control (REM. OVER VOLTAGE
CONTROL):
MG.55.A6.02 - VLT is a registered Danfoss trademark
122