VLT
®
5000 FLUX
Appendix
Compact, Mains supply 3 x 380 - 500 V
According to international requirements
VLT type
5032
5042
5052
Normal overload torque (110 %):
Output current
I
VLT,N
[A] (380-440 V)
61
73
90
I
VLT, MAX
(60 s) [A] (380-440 V)
67.1
80.3
99
I
VLT,N
[A] (441-500 V)
54
65
78
I
VLT, MAX
(60 s) [A] (441-500 V)
59.4
71.5
85.8
Output
S
VLT,N
[kVA] (380-440 V)
46.5
55.6
68.6
S
VLT,N
[kVA] (441-500 V)
46.8
56.3
67.5
Typical shaft output
P
VLT,N
[kW]
30
37
45
Typical shaft output
P
VLT,N
[HP]
40
50
60
High overload torque (160 %):
Output current
I
VLT,N
[A] (380-440 V)
44
61
73
I
VLT, MAX
(60 s) [A] (380-440 V)
70.4
97.6
116.8
I
VLT,N
[A] (441-500 V)
41.4
54
65
I
VLT, MAX
(60 s) [A] (441-500 V)
66.2
86
104
Output
S
VLT,N
[kVA] (380-440 V)
33.5
46.5
55.6
S
VLT,N
[kVA] (441-500 V)
35.9
46.8
56.3
Typical shaft output
P
VLT,N
[kW]
22
30
37
Typical shaft output
P
VLT,N
[HP]
30
40
50
Max. cable cross-section to motor,
IP 54
35/2
35/2
50/0
brake and loadsharing [mm
2
]/[AWG]
2)5)
IP20
35/2
35/2
50/0
Min. cable cross-section to motor,
brake and loadsharing [mm
2
]/[AWG]
2)4)
10/8
10/8
16/6
Rated input current
I
L,N
[A] (380 V)
60
72
89
I
L,N
[A] (460 V)
53
64
77
Max. cable cross-section
IP 54
35/2
35/2
50/0
power[mm
2
]/[AWG]
2) 5)
IP 20
35/2
35/2
50/0
Max. pre-fuses
[-]/UL
1)
[A]
80/80
100/100
125/125
Efficiency
3)
0.96
0.96
0.96
Weight IP 20 EB
[kg]
28
41
42
Weight IP 54
[kg]
54
56
56
Power loss at max. load.
- high overload torque (160 %)
[W]
768
1065
1275
- normal overload torque (110 %)
[W]
1065
1275
1571
Enclosure
IP 20/
IP 54
IP 20/
IP 54
IP 20/
IP 54
1. For type of fuse see section
Fuses.
2. American Wire Gauge.
3. Measured using 30 m screened motor cables at rated load and rated frequency.
4. Min. cable cross-section is the smallest cable cross-section allowed to be fitted on the terminals to comply with IP 20. Always comply with national and
local regulations on min. cable cross-section.
5. Aluminium cables with cross-section above 35 mm
2
must be connected by use of a AI-Cu connector.
MG.55.A6.02 - VLT is a registered Danfoss trademark