VLT® 5000 Crane
■
General Warning before Installation
Before starting the installation, please
be aware of heavy weight and sharp
edges. Furthermore, make sure that
no mains are connected
■
Mechanical Installation
The frequency converter must be installed vertically.
The frequency converter is cooled by means of air
circulation. For the unit to be able to release its cooling
air, the
minimum
distance over and below the unit
must be as shown in the illustration below. To protect
the unit from overheating, it must be ensured that the
ambient temperature
does not rise above the max.
temperature stated for the frequency converter
and
that the 24-hour average temperature
is not exceeded
.
The max. temperature and 24-hour average can be
seen from the General Technical Data.
■
Enclosure Protection
Compact
VLT 5042 - 5102 400-500 V
IP 20
VLT 5152 - 5202 400-500 V
IP 00
■
Installation of VLT 5042–5062 400-500 V
Compact IP20/IP00
Cooling
All Compact units in the above-mentioned series
require a minimum space of 200 mm above and
below the enclosure and must be installed on a
plane, vertical surface (no spacers).
Side-by-side
Compact IP 00/IP20
All units in the above-mentioned series can be installed
side by side without any space between them, since
these units do not require cooling on the sides.
MG.50.N4.02 - VLT is a registered Danfoss trademark