VLT® 5000 Crane
■
Fuses
UL compliance
380-500 V
Bussmann
SIBA
Littel fuse
Ferraz-Shawmut
5042
KTS-R100
2028220-125
KLS-R100
A6K-100R
5052
KTS-R125
2028220-125
KLS-R125
A6K-125R
5062
KTS-R150
2028220-160
KLS-R150
A6K-150R
5072
FWH-220
2028220-200
L50S-225
A50-P225
5102
FWH-250
2028220-250
L50S-250
A50-P250
5122
FWH-300
2028220-315
L50S-300
A50-P300
5152
FWH-350
2028220-315
L50S-350
A50-P350
5202
FWH-400
206xx32-400
L50S-400
A50-P400
KTS-fuses from Bussmann may substitute KTN for 240 V drives.
FWH-fuses from Bussmann may substitute FWX for 240 V drives.
KLSR fuses from LITTEL FUSE may substitute KLNR fuses for 240 V drives.
L50S fuses from LITTEL FUSE may substitute L50S fuses for 240 V drives.
A6KR fuses from FERRAZ SHAWMUT may substitute A2KR for 240 V drives.
A50X fuses from FERRAZ SHAWMUT may substitute A25X for 240 V drives.
Non UL compliance
If UL/cUL is not to be complied with, we recommend the above mentioned fuses or:
VLT 5001-5027
200-240 V
type gG
VLT 5001-5062
380-500 V
type gG
VLT 5032-5052
200-240 V
type gR
VLT 5072-5500
380-500 V
type gR
Not following the recommendation may result
in unnecessary damage of the drive in case of
malfunction. Fuses must be designed for protection in
a circuit capable of supplying a maximum of 100000
A
rms
(symmetrical), 500/600 V maximum.