background image

Control card, digital/frequency output
Number of programmable digital/pulse outputs

1 pcs.

Terminal number

46

Voltage level at digital/frequency output

0-24 V DC (O.C PNP)

Max. output current at digital/frequency output

25 mA.

Max. load at digital/frequency output

1 kΩ

Max. capacity at frequency output

10 nF

Minimum output frequency at frequency output

16 Hz

Maximum output frequency at frequency output

10 kHz

Accuracy on frequency output

Max. error: 0.2% of full scale

Resolution on frequency output

10 bit

The digital output is galvanically isolated from the supply voltage (PELV) and other high-voltage terminals. See section Galvanic
Isolation in the Design Guide.

Control card, analog output
Number of programmable analog outputs

1

Terminal number

42

Current range at analog output

0/4-20 mA

Max. load to common at analog output

500 Ω

Accuracy on analog output

Max. error: 1.5% of full scale

Resolution on analog output

10 bit

The analog output is galvanically isolated from the supply voltage (PELV) and other high-voltage terminals. See section Galvanic
Isolation in the Design Guide.

Control card, 24 V DC output
Terminal number

12

Max. load

130 mA

The 24 V DC supply is galvanically isolated from the supply voltage (PELV) , but has the same potential as the analogue and
digital inputs and outputs. See section Galvanic Isolation in the Design Guide.

Control card, 10 V DC output
Terminal number

50

Output voltage

10.5 V 

±

0.5 V

Max. load

15 mA

The 10 V DC supply is galvanically isolated from the supply voltage (PELV) and other high-voltage terminals. See section
Galvanic Isolation in the Design Guide.

Control card, RS 485 serial communication
Terminal number

68 (TX+, RX+), 69 (TX-, RX-)

Terminal number 67

+ 5 V

Terminal number 70

Common for terminals 67, 68 and 69

Full galvanic isolation. See section Galvanic Isolation in the Design Guide.
For DeviceNet units, see VLT 2800 DeviceNet manual.

Relay outputs

1)

Number of programmable relay outputs

1

Terminal number, control card (resisitvie and inductive load)

1-3 (break), 1-2 (make)

Max. terminal load (AC1) on 1-3, 1-2, control card

250 V AC, 2 A, 500 VA

Max. terminal load (DC1 (IEC 947)) on 1-3, 1-2, control card

25 V DC, 2 A/50 V DC, 1A, 50 W

Min. terminal load (AC/DC) on 1-3, 1-2, control card

24 V DC 10 mA, 24 V AC 100 mA

1) The relay contact is separated from the rest of the circuit by strengthened isolation.

NOTICE

Rated values resistive load - cos

Φ

 >0.8 for up to 300,000 operations.

Inductive loads at cos

Φ

 0.25 approximately 50% load or 50% life time.

Specifications

Quick Guide

30

Danfoss A/S © Rev. 2014-03-18 All rights reserved.

MG28M202

7

7

Содержание VLT 2800

Страница 1: ...MAKING MODERN LIVING POSSIBLE Quick Guide VLT 2800 www danfoss com drives...

Страница 2: ......

Страница 3: ...ables 9 4 Electrical Installation 10 4 1 Electrical Installation in General 10 4 2 Power Cables 10 4 3 Mains Connection 12 4 4 Motor Connection 12 4 5 Parallel Connection of Motors 12 4 6 Motor Cables...

Страница 4: ...27 7 1 1 Mains Supply 200 240 V 27 7 1 2 Mains Supply 380 480 V 27 7 2 General Specifications 28 7 3 Special Conditions 32 7 3 1 Aggressive Environments 32 7 3 2 Derating for Ambient Temperature 32 7...

Страница 5: ...are available to understand advanced frequency converter functions and programming VLT 2800 Design Guide VLT 2800 Filter Instruction Brake Resistor Manual Profibus DP V1 Manual Profibus DP Manual VLT...

Страница 6: ...nce must be performed by qualified personnel only WARNING UNINTENDED START When the frequency converter is connected to AC mains DC power supply or load sharing the motor may start at any time Uninten...

Страница 7: ...the procedures in this manual CAUTION INTERNAL FAILURE HAZARD An internal failure in the frequency converter can result in serious injury when the frequency converter is not properly closed Before app...

Страница 8: ...with enclosure IP20 must be integrated in cabinets and panels IP20 is not suitable for remote mounting In some countries for example in the USA units with enclosure NEMA 1 are approved for remote moun...

Страница 9: ...AC VLT 2805 2815 200 191 75 60 168 7 5 4 5 8 4 4 5 VLT 2822 2840 267 5 257 90 70 168 8 6 5 5 11 4 5 5 5 VLT 2855 2875 267 5 257 140 120 168 8 6 5 5 11 4 5 5 5 VLT 2880 2882 505 490 200 120 244 7 75 7...

Страница 10: ...IP21 Solution Type Code number A B C VLT 2803 2815 200 240 V VLT 2805 2815 380 480 V 195N2118 47 80 170 VLT 2822 200 240 V VLT 2822 2840 380 480 V 195N2119 47 95 170 VLT 2840 200 240 V VLT 2822 PD2 VL...

Страница 11: ...b J K L M N 75 45 6 190 60 16 24 12 192H4720 A B C a D E F G 20 273 20 5 5 8 303 25 313 H I b J K L M N 90 50 6 257 70 16 24 12 192H4893 A B C a D E F G 20 273 20 5 5 8 303 25 313 H I b J K L M N 140...

Страница 12: ...Nm Torque Control Cables Nm 2803 2875 Power mains brake 0 5 0 6 0 22 0 25 Ground 2 3 2880 2882 2840 PD2 Power mains brake 1 2 1 5 Ground 2 3 4 2 Power Cables NOTICE The power terminals can be removed...

Страница 13: ...5 VLT 2840 200 240 V PD2 VLT 2880 2882 380 480 V Illustration 4 6 Electrical Connections VLT 2880 2882 and 2840 PD2 Fit screened armoured cable from the motor to the motor terminals of the frequency...

Страница 14: ...n in the VLT 2800 Design Guide for further details 4 4 Motor Connection Connect the motor to terminals 96 97 98 Connect ground to terminal 99 See chapter 7 2 General Specifications for correct dimensi...

Страница 15: ...lator or motor relay the screen must be continued at the lowest possible HF impedance 4 7 Motor Thermal Protection The electronic thermal relay in the frequency converter has received the UL approval...

Страница 16: ...ket for the relay must cover the first row of control card terminals otherwise the galvanic isolation PELV cannot be maintained Max cable diameter 4 mm 4 9 Grounding Comply with the following at insta...

Страница 17: ...borne 150 kHz 30 MHz Radiated 30 MHz 1 GHz Cable borne 150 kHz 30 MHz Radiated 30 MHz 1GHz 3 x 480 V version with 1B RFI filter Yes 50 m Yes 50 m Yes 50 m No Table 4 6 EMC Emission Compliance 1 For VL...

Страница 18: ...ood electrical contact from the installation plate through the installation screws to the metal cabinet of the frequency converter Use starwashers and galvanically conductive installation plates Do no...

Страница 19: ...JDDZ RK1 JDDZ 2805 2820 KTS R20 JKS 20 JJS 20 FNQ R 20 KTK R 20 LP CC 20 5017906 0 20 KLS R20 ATM R25 A6K 20R 2855 2875 KTS R25 JKS 25 JJS 25 5017906 0 25 KLS R25 ATM R20 A6K 25R 2880 2882 KTS R50 JK...

Страница 20: ...3 digits To see the value press CHANGE DATA The CHANGE DATA key is also used for confirming a change of parameter settings are used for selecting parameters and for changing parameter values These ke...

Страница 21: ...er is in Auto mode where the reference signal is given externally analog or digital via the control terminals However in Hand mode it is possible to give the reference signal locally via the control p...

Страница 22: ...rence 5 2 Motor Start Press START to start the motor Set the motor speed by adjusting parameter 003 Local Reference Check whether the direction of rotation of the motor shaft is clockwise If not excha...

Страница 23: ...eedback unit 013 Local Control 0 Local not active 1 Local control and open loop without slip compensation 2 Remote operated control and open loop without slip compensation 3 Local control as par 100 4...

Страница 24: ...0 000 Hz Par 100 1 3 Par 204 Ref MIN Par 415 Max Feedback 50 000 rpm par 416 206 Ramp Type 0 Linear 1 Sin shaped 2 Sin 2 207 Ramp up Time 1 0 02 3600 00 s 3 00 s VLT 2803 2875 10 00 2880 2882 208 Ramp...

Страница 25: ...min max 0 20 mA 2 External reference min max 4 20 mA 3 Feedback min max 0 20 mA 4 Feedback min max 4 20 mA 5 Output frequency 0 max 0 20 mA 6 Output frequency 0 max 4 20 mA 7 Output current 0 I INV 0...

Страница 26: ...428 F3 frequency par 104 427 U3 Voltage 0 0 999 0 V par 103 428 F3 Frequency Par 426 F2 frequency 1000 Hz par 104 437 Process PID Normal Inverse Control 0 Normal 1 Inverse 438 Process PID Anti Windup...

Страница 27: ...T X X Short circuit on the motor terminals or in the motor 17 Serial communication timeout STD BUS TIMEOUT X X No serial communication to the frequency converter 18 HPFB bus timeout HPFB TIMEOUT X X N...

Страница 28: ...in 3 ways 1 Via the operating key STOP RESET 2 Via a digital input 3 Via serial communication It is also possible to select an automatic reset in parameter 405 Reset function When a cross appears in b...

Страница 29: ...ency 95 95 95 95 95 95 95 95 95 Power loss at 100 load W 24 35 48 69 94 125 125 231 231 Weight kg 2 0 2 0 2 0 2 0 2 0 3 7 6 0 6 0 18 5 Enclosure type IP 20 IP 20 IP 20 IP 20 IP 20 IP 20 IP 20 IP 20 IP...

Страница 30: ...0 Supply voltage VLT 2805 2840 R5 380 400 V 10 Supply frequency 50 60 Hz 3 Hz Max imbalance on supply voltage 2 0 of rated supply voltage True Power Factor 0 90 nominal at rated load Displacement Powe...

Страница 31: ...ccuracy of analog inputs Max error 1 of full scale Scan interval 13 3 m The analog inputs are galvanically isolated from the supply voltage PELV and other high voltage terminals See section Galvanic I...

Страница 32: ...lly isolated from the supply voltage PELV but has the same potential as the analogue and digital inputs and outputs See section Galvanic Isolation in the Design Guide Control card 10 V DC output Termi...

Страница 33: ...speed Speed control range closed loop 1 120 of synchronous speed Speed accuracy open loop 150 3600 RPM Max error of 23 RPM Speed accuracy closed loop 30 3600 RPM Max error of 7 5 RPM All control char...

Страница 34: ...s on existing electrical installations 7 3 2 Derating for Ambient Temperature The ambient temperature measured over 24 hours should be at least 5 C lower than the max ambient temperature If the freque...

Страница 35: ...I IT mains 17 L Leakage current 5 M Mains connection 12 Mechanical installation 6 Menu mode 19 Motor cable 13 Motor coil 7 Motor connection 12 Motor thermal protection 13 Motors parallel connection 1...

Страница 36: ...to products already on order provided that such alterations can be made without subsequential changes being necessary in specifications already agreed All trademarks in this material are property of...

Отзывы: