Illustration 11: Installation Space
A
The clearance around the drive (see also B and C)
B
The distance from a drive to a second drive, or the
distance to the cabinet wall
C
The free space above the drive
D
The free space below the drive
Table 6: Minimum Clearances around the AC Drive in mm (in inch)
Drive type
A
B
C
D
0003 2–0012 2
0003 5–0012 5
20
(0.79)
20
(0.79)
100
(3.94)
50
(1.97)
0017 2–0031 2
0016 5–0031 5
20
(0.79)
20
(0.79)
120
(4.72)
60
(2.36)
0048 2–0061 2
0038 5–0061 5
0004 6-0034 6
30
(1.18)
20
(0.79)
160
(6.30)
80
(3.15)
0075 2–0114 2
0072 5–0105 5
0041 6–0052 6
80
(3.15)
80
(3.15)
300
(11.81)
100
(3.94)
0140 2–0205 2
0140 5–0205 5
80
(3.15)
80
(3.15)
300
(11.81)
300
(11.81)