12.10.101 Fault 42 - Brake resistor overtemperature, Subcode S3 - Brake resistance too low (BCU)

Cause

Brake resistor overtemperature protection has detected too heavy braking.

Troubleshooting

Reset unit.
Set the deceleration time longer.
Dimensioning of the brake chopper is not correct.
Use external brake resistor.

12.10.102 Fault 42 - Brake resistor overtemperature, Subcode S4 - Brake resistance not detected

(BCU)

Cause

Brake resistor overtemperature protection has detected too heavy braking.

Troubleshooting

Reset unit.
Set the deceleration time longer.
Dimensioning of the brake chopper is not correct.
Use external brake resistor.

12.10.103 Fault 42 - Brake resistor overtemperature, Subcode S5 - Brake resistance leakage (earth

fault) (BCU)

Cause

Brake resistor overtemperature protection has detected too heavy braking.

Troubleshooting

Reset unit.
Set the deceleration time longer.
Dimensioning of the brake chopper is not correct.
Use external brake resistor.

12.10.104 Fault 43 - Encoder fault, Subcode S1 - Encoder 1 channel A is missing

Cause

Problem detected in encoder signals.
Encoder channel A is missing.

Troubleshooting

Do a check of the encoder connections.
Do a check of the option board.
Measure the encoder pulses.

If the pulses are correct, the option board is faulty.
If the pulses are not correct, the encoder/cabling is faulty.

12.10.105 Fault 43 - Encoder fault, Subcode S2 - Encoder 1 channel B is missing

Cause

Problem detected in encoder signals.
Encoder channel B is missing.

AQ275638903263en-000601 / DPD00910

188 | Danfoss A/S © 2022.12

Specifications

VACON® NXS/NXP Air-cooled

Operating Guide

Содержание VACON NXS Air-cooled

Страница 1: ...Operating Guide VACON NXS NXP Air cooled Wall mounted and Standalone drives danfoss com...

Страница 2: ......

Страница 3: ...16 Description of the Type Code 17 Enclosure Sizes 19 Available Protection Ratings 22 Available EMC Classes 22 Control Panel 24 Introduction to Control Panel 24 Keypad 24 Display 26 Basic Menu Structu...

Страница 4: ...r Cables 40 EMC compliant Installation 40 Installation in a Corner grounded Network 41 Grounding 41 Get Access and Locate the Terminals 43 Get Access and Locate the Terminals for FR4 FI4 43 Get Access...

Страница 5: ...rds 93 Galvanic Isolation Barriers 94 Using the Control Panel 95 Navigating on the Control Panel 95 Using the Monitoring Menu M1 95 Monitored Values 95 Using the Parameter Menu M2 97 Finding the Param...

Страница 6: ...9 Activating or Deactivating the Automatic Parameter Back up P6 3 4 109 Comparing the Parameters 110 Security 110 Finding the Security Menu 110 Passwords 111 Setting a Password 111 Entering a Password...

Страница 7: ...ug Menu S6 8 7 118 Using the Expander Board Menu 118 Expander Board Menu 118 Examining the Connected Option Boards 118 Finding the Option Board Parameters 119 Further Control Panel Functions 119 Commi...

Страница 8: ...0 FR11 Standalone 143 Cable and Fuse Sizes 146 List of Cable and Fuse Size Information 146 Cable and Fuse Sizes for 208 240 V and 380 500 V FR4 to FR9 146 Cable and Fuse Sizes for 208 240 V and 380 50...

Страница 9: ...Voltage 525 690 V UL Rating 600 V North America 162 VACON NXP Technical Data 163 Brake Chopper Ratings 167 Brake Chopper Ratings 167 Brake Chopper Ratings for Mains Voltage 208 240 V 168 Brake Choppe...

Страница 10: ...anuals are available from Danfoss NOTE Download the English and French product manuals with applicable safety warning and caution information from https www danfoss com en service and support REMARQUE...

Страница 11: ...bles Find information on the control connections in 7 3 2 Control Terminals on OPTA1 If the start up wizard is active select the language of the control panel and the application Accept the selections...

Страница 12: ...als or the DC terminals are live when the drive is connected to mains also when the motor does not operate A contact with this voltage can lead to death or serious injury Do not touch the motor termin...

Страница 13: ...y can result in death or serious injury Ensure the correct grounding of the equipment by a certified electrical installer W A R N I N G SHOCK HAZARD FROM PE CONDUCTOR The drive can cause a DC current...

Страница 14: ...e Do not move the AC drive during operation Use a fixed installation to prevent damage to the drive N O T I C E DAMAGE TO THE AC DRIVE FROM INCORRECT EMC LEVEL The EMC level requirements for the AC dr...

Страница 15: ...voltage withstand tests can damage the drive Do not do voltage withstand tests on the AC drive The manufacturer has already done the tests AQ275638903263en 000601 DPD00910 15 Danfoss A S 2022 12 Safet...

Страница 16: ...ards N O T I C E In a residential environment this product can cause radio interference in which case supplementary mitigation measures can be required Foreseeable misuse Do not use the drive in appli...

Страница 17: ...r of VACON C The type code D The serial number E The mains voltage F The nominal output current G The protection rating H The firmware code I The order number of the customer 3 4 Description of the Ty...

Страница 18: ...fixed installations and nominal voltage less than 1000 V L complies with the category C3 of standard IEC EN 61800 3 A1 2nd environment and nominal voltage less than 1000 V T complies with the standard...

Страница 19: ...ption board abbreviations A basic I O board B expander I O board C fieldbus board D special board E fieldbus board For example E3 PROFIBUS DP DNOT The optional codes See full list of option codes in t...

Страница 20: ...5 0025 0031 0048 FR6 0061 0075 FR7 0088 0114 0140 FR8 0170 0205 0261 FR9 0300 5 380 500 V 0003 FR4 0004 0005 0007 0009 0012 0016 FR5 0022 0031 0038 FR6 0045 AQ275638903263en 000601 DPD00910 20 Danfoss...

Страница 21: ...0 FR8 0168 0205 0261 FR9 0300 0385 FR10 Standalone 0460 0520 0590 FR11 Standalone 0650 0730 6 500 690 V 0004 FR6 0005 0007 0010 0013 0018 0022 0027 0034 0041 FR7 0052 AQ275638903263en 000601 DPD00910...

Страница 22: ...Standalone x 525 690 V FR4 FR9 x x 525 690 V FR10 Standalone x x 525 690 V FR11 Standalone x 3 7 Available EMC Classes The product standard EMC immunity requirements IEC EN 61800 3 A1 has 5 categorie...

Страница 23: ...4 to FR9 C3 L Includes AC drives that have the nominal voltage of less than 1000 V These AC drives are used in the 2nd environment only IP21 UL Type 1 and IP54 UL Type 12 in 380 500 V FR10 and larger...

Страница 24: ...trol the speed of a motor and monitor the status of the AC drive Use it also to set the parameters of the AC drive The control panel can be removed from the AC drive The control panel is isolated from...

Страница 25: ...orward in the menu move the cursor right in the parameter menu and to go to the edit mode G The enter button Use it to accept a selection reset the fault history push for 2 3 s H The Browser button Do...

Страница 26: ...cursor left in the Parameter menu K The reset button Use it to reset a fault L The Browser button Up Use it to scroll the main menu and the pages of different submenus and to increase a value 3 8 3 Di...

Страница 27: ...Submenus See Application Manual Main menu M1 Monitor V1 1 Output frequency V1 2 Frequency ref V1 3 Motor speed V1 4 Motor current M3 Keypad control P3 1 Control place R3 2 Keypad reference P3 3 Direct...

Страница 28: ...contents of the accessories bag is different for different enclosure sizes and protection ratings FR4 FI4 FR4 FR6 4 1 1 Accessories for FR4 FI4 FR6 FI6 FR7 FI7 FR8 FI8 4 1 2 Accessories for FR7 FI7 F...

Страница 29: ...the product has to be stored before installing it follow these instructions Procedure If the AC drive must be stored before using it make sure that the ambient conditions agree to the following Storag...

Страница 30: ...ackage Procedure Check the weight of the AC drive see 12 1 Weights of the AC Drive To lift the AC drives larger than FR7 FI7 out of the package use a jib crane 60 60 e30bh767 10 After lifting the driv...

Страница 31: ...NXOPT Date IP54 upgrade Collar EMC level modified H L to T Drive modified in slot A B C D E Date Date Date Illustration 9 The Product Modified Label Procedure Attach the label on the side of the AC dr...

Страница 32: ...ure decreases When the air density decreases the thermal capacity decreases that is less air removes less heat and the resistance to electric field breakdown voltage distance decreases The full therma...

Страница 33: ...sufficiently free space around the drive Make sure that the temperature of the cooling air does not go above the maximum ambient operating temperature or below the minimum ambient operating temperatu...

Страница 34: ...AC Drive in mm in inch Drive type A B C D 0003 2 0012 2 0003 5 0012 5 20 0 79 20 0 79 100 3 94 50 1 97 0017 2 0031 2 0016 5 0031 5 20 0 79 20 0 79 120 4 72 60 2 36 0048 2 0061 2 0038 5 0061 5 0004 6 0...

Страница 35: ...r Drive type The quantity of cooling air m3 h The quantity of cooling air CFM 0003 2 0012 2 0003 5 0012 5 70 41 2 0017 2 0031 2 0016 5 0031 5 190 112 0048 2 0061 2 0038 5 0061 5 0004 6 0034 6 425 250...

Страница 36: ...rive type The quantity of cooling air m3 h The quantity of cooling air CFM 0385 5 0520 5 0261 6 0416 6 2000 900 0590 5 0730 5 0460 6 0590 6 3000 1765 For more information on the power losses in all op...

Страница 37: ...pace around the AC drive for cooling see 5 2 2 Cooling of FR4 to FR9 Some free space is also necessary for maintenance Attach the AC drive with the screws and other components in the delivery 5 3 2 In...

Страница 38: ...ing If the motor temperature protection of the drive see VACON All in One Application Manual is used as an overload protection select the cable to agree with the protection If 3 or more cables are use...

Страница 39: ...ables must comply with the requirements of the National Electric Code NEC and the Canadian Electric Code CEC The maximum ambient temperature is 86 F The maximum temperature of the cable surface is 158...

Страница 40: ...ct with a conducting compo nent If a multi conductor cable is used cut off all conductors that are not connected The enclosure sizes FR8 and larger have the DC connection as optional If it is necessar...

Страница 41: ...SC that is a minimum of 120 RSCE If necessary contact the mains operator 6 2 1 Installation in a Corner grounded Network Corner grounding can be used with the drive types FR4 to FR9 with a rating of 3...

Страница 42: ...this table The cross sectional area of each protective earthing conductor that is not a part of the mains cable or the cable enclosure must be a minimum of 2 5 mm2 if there is mechanical protection an...

Страница 43: ...pen the AC drive for installing the cables Procedure Open the cover of the AC drive e30bg082 10 Remove the screws of the cable cover Remove the cable cover Do not open the cover of the power unit e30b...

Страница 44: ...0 Illustration 16 FR4 FI4 Terminals A Mains terminals B Brake resistor terminals C Motor terminals D Grounding terminals AQ275638903263en 000601 DPD00910 44 Danfoss A S 2022 12 Electrical Installation...

Страница 45: ...nstalling the cables Procedure Open the cover of the AC drive e30bg083 10 Remove the screws of the cable cover Remove the cable cover Do not open the cover of the power unit e30bg084 10 AQ275638903263...

Страница 46: ...90 10 Illustration 17 FR5 Terminals A Mains terminals B Brake resistor terminals C Motor terminals D Grounding terminals AQ275638903263en 000601 DPD00910 46 Danfoss A S 2022 12 Electrical Installation...

Страница 47: ...installing the cables Procedure Open the cover of the AC drive e30bg083 10 Remove the screws of the cable cover Remove the cable cover Do not open the cover of the power unit e30bg084 10 AQ2756389032...

Страница 48: ...91 10 Illustration 18 FR6 FI6 Terminals A Mains terminals B Brake resistor terminals C Motor terminals D Grounding clamp AQ275638903263en 000601 DPD00910 48 Danfoss A S 2022 12 Electrical Installation...

Страница 49: ...installing the cables Procedure Open the cover of the AC drive e30bg083 10 Remove the screws of the cable cover Remove the cable cover Do not open the cover of the power unit e30bg084 10 AQ2756389032...

Страница 50: ...10 Illustration 19 FR7 FI7 Terminals A Mains terminals B Brake resistor terminals C Motor terminals D Grounding terminals AQ275638903263en 000601 DPD00910 50 Danfoss A S 2022 12 Electrical Installati...

Страница 51: ...ng the cables Procedure Open the cover of the AC drive e30bg031 10 Open the power unit cover e30bg032 10 Find the DC terminals and Brake resistor terminals on top of the AC drive B B R R e30bg076 10 A...

Страница 52: ...0bg102 10 A B C Illustration 20 FR8 FI8 Terminals A Mains terminals B Motor terminals C Grounding terminals AQ275638903263en 000601 DPD00910 52 Danfoss A S 2022 12 Electrical Installation VACON NXS NX...

Страница 53: ...C drive for installing the cables Procedure Remove the cable cover e30bg075 10 Find the DC terminals and Brake resistor terminals on top of the AC drive B B R R e30bg076 10 AQ275638903263en 000601 DPD...

Страница 54: ...e30bg103 10 A B C Illustration 21 FR9 Terminals A Mains terminals B Motor terminals C Grounding terminals AQ275638903263en 000601 DPD00910 54 Danfoss A S 2022 12 Electrical Installation VACON NXS NXP...

Страница 55: ...Follow these instructions to open the AC drive for installing the cables Procedure Open the cabinet door Remove the protective covers e30bh771 10 AQ275638903263en 000601 DPD00910 55 Danfoss A S 2022 1...

Страница 56: ...tration 22 FR10 Standalone Terminals 1 Brake resistor and DC terminals 2 Control terminals 3 Motor terminals 4 Mains terminals 5 Grounding busbar AQ275638903263en 000601 DPD00910 56 Danfoss A S 2022 1...

Страница 57: ...Follow these instructions to open the AC drive for installing the cables Procedure Open the cabinet door Remove the protective covers e30bh772 10 AQ275638903263en 000601 DPD00910 57 Danfoss A S 2022 1...

Страница 58: ...Illustration 23 FR11 Standalone Terminals 1 Brake resistor and DC terminals 2 Control terminals 3 Motor terminals 4 Mains terminals 1 5 Grounding busbar 6 Mains terminals 2 AQ275638903263en 000601 DPD...

Страница 59: ...cedure Check the requirements related to lengths distances and positioning of the cables according to instructions in 6 5 1 Addi tional Instructions for Cable Installation Follow the installation inst...

Страница 60: ...hecks are necessary see 9 3 Measuring the Cable and Motor Insulation Table 11 Minimum Distances between Cables The distance between ca bles m The length of the shielded cable m The distance between ca...

Страница 61: ...and the optional brake cable in the openings of the cable entry plate Use the cable entry plate delivered in the accessories bag A B C e30bg085 10 Illustration 25 Cables through the Cable Entry Plate...

Страница 62: ...bag FR6 FI6 Attach the grounding conductor of each cable with a grounding clamp for grounding conductor Use the grounding clamps and the screws delivered in the accessories bag Make sure to connect th...

Страница 63: ...nnect an external brake resistor see VACON Brake Resistor Manual See also 8 7 8 2 Setting the Internal Brake Resistor Connection Make sure that the delivery contains all necessary components For the i...

Страница 64: ...vered in the accessories bag A B C e30bg085 10 Illustration 27 Cables through the Cable Entry Plate A The mains cable B The brake cable C The motor cable Put the cable entry plate with the cables into...

Страница 65: ...ch cable with a grounding clamp Make sure to connect the grounding conductor to the motor and the terminals that are identified with the grounding sym bol If a double grounding is necessary use the gr...

Страница 66: ...able accessories For information on how to comply with the UL regulations in cable installations see 6 1 2 UL Standards on Cabling If it is necessary to connect an external brake resistor see VACON Br...

Страница 67: ...n 29 Cutting the Grommet in IP54 e30bh278 10 Attach the grommet and the cable until the frame of the drive goes into the groove of the grommet With the protection rating IP54 UL Type 12 the connection...

Страница 68: ...ction with the grounding clamp for cable shield expose the shield of motor cables e30bg104 20 2 1 1 Grounding clamp 2 Exposed shield Attach the cable entry plate and then the cable cover For the tight...

Страница 69: ...ecessary to connect an external brake resistor see VACON Brake Resistor Manual See also 8 7 8 2 Setting the Internal Brake Resistor Connection Make sure that the delivery contains all necessary compon...

Страница 70: ...onnection tight with some insulation tape or a cable tie e30bg077 10 Connect the cables See the correct tightening torques in 12 6 Tightening Torques of the Terminals Connect the phase conductors of t...

Страница 71: ...rounding clamp for cable shield expose the shield of motor cables e30bg104 20 2 1 1 Grounding clamp 2 Exposed shield AQ275638903263en 000601 DPD00910 71 Danfoss A S 2022 12 Electrical Installation VAC...

Страница 72: ...formation on how to comply with the UL regulations in cable installations see 6 1 2 UL Standards on Cabling If it is necessary to connect an external brake resistor see VACON Brake Resistor Manual See...

Страница 73: ...traight If this is not possible make the connection tight with some insulation tape or a cable tie e30bg077 10 To make a 360 connection with the grounding clamp for cable shield expose the shield of m...

Страница 74: ...ke the connection e30bh780 10 Connect the control cables 1 2 4 3 e30bh764 20 1 Control unit 2 Cable routing 3 Grounding 4 Cable entry AQ275638903263en 000601 DPD00910 74 Danfoss A S 2022 12 Electrical...

Страница 75: ...th a grounding clamp for grounding conductor 1 2 3 4 3 1 2 5 5 e30bh775 20 1 Motor cables 2 PE Grounding 3 Mains cables 4 360 Grounding 5 Control cables AQ275638903263en 000601 DPD00910 75 Danfoss A S...

Страница 76: ...ssary to connect an external brake resistor see VACON Brake Resistor Manual See also 8 7 8 2 Setting the Internal Brake Resistor Connection Make sure that the delivery contains all necessary component...

Страница 77: ...for cable shield expose the shield of motor cables e30bh781 10 Connect the cables See the correct tightening torques in 12 6 Tightening Torques of the Terminals Connect the mains and motor cables Use...

Страница 78: ...control cables 1 2 4 3 e30bh765 20 1 Control unit 2 Cable routing 3 Grounding 4 Cable entry AQ275638903263en 000601 DPD00910 78 Danfoss A S 2022 12 Electrical Installation VACON NXS NXP Air cooled Op...

Страница 79: ...amp for grounding conductor 1 2 3 5 5 1 3 4 2 3 e30bh776 20 Illustration 33 FR11 Standalone 1 Motor cables 2 PE Grounding 3 Mains cables 4 360 grounding 5 Control cables AQ275638903263en 000601 DPD009...

Страница 80: ...ation 34 FR11 Standalone 0460 0502 690 V 1 Motor cables 2 PE Grounding 3 Mains cables 4 360 grounding 5 Control cables AQ275638903263en 000601 DPD00910 80 Danfoss A S 2022 12 Electrical Installation V...

Страница 81: ...Type Code W A R N I N G SHOCK HAZARD FROM THE COMPONENTS The components of the drive are live when the drive is connected to mains Do not make changes in the AC drive when it is connected to mains N...

Страница 82: ...move the EMC screw s FR4 e30bg094 10 Illustration 35 FR4 FR5 e30bg095 10 Illustration 36 FR5 AQ275638903263en 000601 DPD00910 82 Danfoss A S 2022 12 Electrical Installation VACON NXS NXP Air cooled Op...

Страница 83: ...e is a sticker next to the terminals to remind to remove the jumper X10 1 if the AC drive requires this If there is no sticker move to step 4 e30bg472 10 AQ275638903263en 000601 DPD00910 83 Danfoss A...

Страница 84: ...the label is not yet attached attach it on the drive near the nameplate 6 6 2 Installing the AC Drive in an IT System FR7 Use these instructions to change the EMC protection of the AC drive to level...

Страница 85: ...he EMC screws e30bg098 10 Remove the screw and replace with a plastic screw M4 e30bg099 10 AQ275638903263en 000601 DPD00910 85 Danfoss A S 2022 12 Electrical Installation VACON NXS NXP Air cooled Oper...

Страница 86: ...roduct changed label see 4 4 Using the Prod uct Modified Label If the label is not yet attached attach it on the drive near the nameplate N O T I C E Only an authorized VACON service person can change...

Страница 87: ...livered according to the order The next pages contain information on the terminals and general wiring examples The type code shows the I O boards that are installed at the factory For more information...

Страница 88: ...ives N O T I C E The control unit I O ground is not isolated from the chassis ground protective earth In the installation consider the potential differences between the grounding points We recommend u...

Страница 89: ...n mode voltage to GND Selection V mA with jumper block X1 0 10 V Ri 200 k 10V 10V Joystick ctrl sel with jumper 0 20 mA Ri 250 15 max 250 mA all boards total 150 mA from single board Can also be used...

Страница 90: ...voltage and the ground for the digital inputs and the common inputs CMA CMB can be internal or external A B e30bg015 10 DIN1 24V GND DIN2 DIN3 CMA 24V GND DIN1 DIN2 DIN3 CMA Illustration 42 Positive N...

Страница 91: ...inputs Changing the AI AO signal contents requires also a change in the related board parameter in menu M7 On the A1 basic board there are 4 jumper blocks X1 X2 X3 and X6 Each jumper block contains 8...

Страница 92: ...D AI1 mode Voltage input 0 10V differential AI2 mode Voltage input 0 10V differential A B C D AI1 mode Voltage input 0 10V AI2 mode Voltage input 10 10V A B C D Jumper block X3 CMA and CMB grounding...

Страница 93: ...A 125 VDC 0 4 A Minimum switching load 5 V 10 mA 21 OPTA3 22 23 25 26 28 RO1 1 RO1 2 RO1 3 RO2 1 RO2 2 TI1 29 TI1 Relay output 1 Relay output 2 Thermistor input Illustration 45 Control Terminal Signal...

Страница 94: ...lated from each other at 300 VAC EN 50178 e30bg021 20 10Vref L1 L2 L3 U V W GND AI1 GND Control I O ground Gate drivers Control panel Control unit Power unit Digital input group A Digital input group...

Страница 95: ...ption name of the page C The number of items that are available or the item value 8 2 Using the Monitoring Menu M1 Follow these instructions to monitor the actual values of the parameters and signals...

Страница 96: ...The calculated motor temperature in percentage of the nominal temperature See VACON All in One Application Manual V1 11 Analog input 1 V mA 13 AI1 1 V1 12 Analog input 2 V mA 14 AI2 1 V1 13 DIN 1 2 3...

Страница 97: ...e Parameter Group Menu G READY Keypad G1 G8 e30bg024 10 Input signals To find the parameter group use the Browser buttons Up and Down READY Keypad P1 P18 e30bg025 10 Input signals Use the Browser butt...

Страница 98: ...28 10 Min Frequency 13 95 Hz Set the new value with the Browser buttons Up and Down To accept the change push the enter button or ignore the change with menu button Left If the enter button is pushed...

Страница 99: ...it To accept the change push the enter button To ignore the change push Menu button Left many times until the view goes back to the parameter list If the enter button is pushed the value stops to blin...

Страница 100: ...P4 e30bg033 10 Keypad control To go to the Keypad control menu from the main menu push the Menu button Right 8 4 2 Keypad Control Parameters M3 Index Parameter Min Max Unit Default Cust ID Description...

Страница 101: ...structions to change the frequency reference Procedure In the Keypad control menu M3 find the Keypad reference with Menu buttons Up and Down To go to the edit mode push the Menu button Right The frequ...

Страница 102: ...3 and control mode is other than keypad Procedure Do one of the following options Keep the Start button pushed down for 3 s when the motor is in RUN state Keep the Stop button pushed down for 3 s when...

Страница 103: ...50 Fault Symbols A Fault symbol B Fault type symbol 8 5 2 Examining the Fault Time Data Record This menu shows some important data that was valid at the time of the fault This helps to find the cause...

Страница 104: ...cord The value line of the main page H1 H shows the number of faults in the fault history The location indication tells in which order the faults have shown The newest fault has the indication H5 1 th...

Страница 105: ...ht READY I O term S1 S11 e30bg037 10 System Menu 8 7 2 System Menu Functions Table 13 System Menu Functions Code Function Min Max Unit Default Cust Description S6 1 Language selection English The sele...

Страница 106: ...s S6 5 4 Multimonitoring items Change Enabled Change Disabled S6 6 Keypad settings P6 6 1 Default page P6 6 2 Default page Operating menu P6 6 3 Timeout time 0 65535 s 30 P6 6 4 Contrast 0 31 18 P6 6...

Страница 107: ...8 2 3 Operating days trip counter T6 8 2 4 Operating hours trip counter hh mm ss T6 8 2 5 Clear operating time counter S6 8 3 Software info S6 8 3 1 Software package S6 8 3 2 System software version...

Страница 108: ...the Application Package see VACON NX All in One Application Manual Procedure In the System menu M6 find the Application selection page S6 2 Application with the Browser buttons Push the Menu button R...

Страница 109: ...dure In the Copy parameters S6 3 subpage find the Up to keypad page S6 3 2 Push the Menu button Right To go to the edit mode push the Menu button Right All param starts to blink To accept the selectio...

Страница 110: ...arameter Set 1 If no differences are found 0 shows on the bottom line If there are differences the display shows the number of the differences for example P1 P5 5 different values To compare the value...

Страница 111: ...digit for each one with the Browser buttons To accept the new password push the enter button The password activates after the Timeout time P6 6 3 see 8 7 7 4 Setting the Timeout Time 8 7 6 4 Entering...

Страница 112: ...P6 5 3 To go to the edit mode push the Menu button Right Select the action To activate the start up wizard select Yes with the Browser buttons To deactivate the start up wizard select No with the Bro...

Страница 113: ...u page with the Browser buttons To edit the third level page number push the Menu button Right Change the number of the third level page with the Browser buttons To accept the new default page value p...

Страница 114: ...onnected for some reason The brake resistor is available as optional equipment for all sizes It can be installed internally in enclosure sizes FR4 to FR6 Procedure In the Hardware settings submenu fin...

Страница 115: ...1200 TimeOut 6000 Do not use intervals shorter than the AckTimeOut time in the NC Drive monitoring 8 7 8 6 Changing the HMI Acknowledge Timeout Use these instructions to change the HMI Acknowledge Ti...

Страница 116: ...13 days C6 8 1 3 Power On hour counter Value on display is 7 05 16 The drive has operated for 7 hours 5 minutes and 16 s 8 7 9 3 Trip Counters S6 8 2 The Trip counters page S6 8 2 has information on r...

Страница 117: ...ges Procedure In the System info submenu find the Applications page with the Browser buttons To go to the Applications page push the Menu button Right To select the application use the Browser buttons...

Страница 118: ...structions if it is necessary 8 8 Using the Expander Board Menu 8 8 1 Expander Board Menu The Expander board menu that is the menu for option board information allows to see which option boards are co...

Страница 119: ...ameters use the Browser buttons Up and Down To examine the parameter list push the Menu button Right To scroll through the parameters use the Browser buttons Up and Down To go to the edit mode push th...

Страница 120: ...ains and the motor has stopped Also the load side of the drive can generate voltage A contact with this voltage can lead to death or serious injury Before doing electrical work on the drive Disconnect...

Страница 121: ...cooling air For further information on cooling requirements see 5 2 1 General Cooling Requirements 5 2 2 Cooling of FR4 to FR9 5 2 3 Cooling of Standalone AC drives FR10 to FR11 12 8 VACON NXP Technic...

Страница 122: ...ulation check on the drive side Put all phases together and measure to the ground Connect the motor cables to the drive 9 4 Checks after Commissioning 9 4 1 Testing the AC Drive after Commissioning Be...

Страница 123: ...t up Test Do the start up tests without the load if possible If this is not possible make sure that it is safe to do each test before doing it Make sure that the other workers near know about the test...

Страница 124: ...eration and condition for possible causes of operational faults or defects The continuity check on fuses is performed by trained service personnel EMC consider ation 1 year Inspect the installation wi...

Страница 125: ...ents dust or environments with high temperatures Only trained service per sonnel may perform the inspection and service action Power cables and wiring 1 year Check for loose connections aging insulati...

Страница 126: ...n operational or stocked for over 2 years Connect the DC supply to L1 and L2 or the B B terminals DC to B DC to B of the DC link or directly to the capacitor terminals In the NX AC drives with no B B...

Страница 127: ...5 After the reforming operation is done discharge the capacitors AQ275638903263en 000601 DPD00910 127 Danfoss A S 2022 12 Maintenance VACON NXS NXP Air cooled Operating Guide...

Страница 128: ...annot start the motor after an AR fault an FT fault shows The type FT fault stops the AC drive The fault stays active until it is reset see 11 2 Resetting a Fault The memory of active faults can keep...

Страница 129: ...ON NX AC drives This allows the applica tions with larger parameter sets to be copied to keypad memory For more information on control panel display see 3 8 3 Display If an application with larger par...

Страница 130: ...list of dimension information for different types of NXS NXP AC Drives For Wall mounted AC drives see 12 2 2 1 Dimensions for FR4 FR6 12 2 2 2 Dimensions for FR7 12 2 2 3 Dimensions for FR8 12 2 2 4...

Страница 131: ...6 Drive type W1 W2 H1 H2 H3 D1 0003 2 0012 2 0003 5 0012 5 128 5 04 100 3 94 327 12 87 313 12 32 292 11 5 190 7 48 7 0 27 0017 2 0031 2 0016 5 0031 5 144 5 67 100 3 94 419 16 5 406 15 98 391 15 39 214...

Страница 132: ...0 80 QGLM 13 5 0 53 QGLC 21 0 83 QGLM 20 3 0 80 QGLC 28 1 1 QGLM 16 0 63 QGLC 21 0 83 QGLM 25 3 3 x 1 0 QGLC 28 1 1 0017 2 0025 2 0016 5 0022 5 16 0 63 3 x 25 3 3 x 1 0 16 0 63 3 x 25 3 3 x 1 0 16 0...

Страница 133: ...NXS NXP AC Drive FR7 Drive type W1 W2 H1 H2 H3 D1 0075 2 0114 2 0072 5 0105 5 0041 6 0052 6 237 9 33 190 7 48 630 24 80 614 24 17 591 23 27 257 10 12 9 0 35 e30bh750 10 E1 E2 E3 IP21 IP54 Illustration...

Страница 134: ...ter 1 E3 gland plate hole 0075 2 0114 2 0072 5 0105 5 0041 6 0052 6 36 1 42 3 x 50 3 3 x 1 98 21 0 83 3 x 28 3 3 x 1 11 36 1 42 3 x 50 3 3 x 1 98 1 Same as maximum cable thickness 12 2 2 3 Dimensions...

Страница 135: ...rive FR8 Drive type W1 W2 H1 H2 H3 D1 0140 2 0205 2 0140 5 0205 5 0062 6 0100 6 291 11 47 255 10 04 758 29 88 732 28 81 1008 39 69 344 13 54 9 0 35 E1 E2 E3 e30bh751 10 B B R R Illustration 59 Dimensi...

Страница 136: ...TE Cable clamps have 40 mm internal diameter The clamps are used for 360 degree grounding of the shield Exposing the cable shield decreases outer diameter of the cable so the recommended 3x185 95 mm2...

Страница 137: ...1 2 0300 2 0261 5 0300 5 0125 6 0208 6 1150 45 28 1 1120 44 09 721 28 39 205 8 07 16 0 63 1338 52 68 21 0 83 1 Brake resistor terminal box H6 not included For FR8 and FR9 when brake chopper or an addi...

Страница 138: ...eld decreases outer diameter of the cable so the recommended 3x185 95 mm2 MCCMK motor cables fit in the clamp 12 2 3 Flange mounting 12 2 3 1 Dimensions for Flange Mounting FR4 FR6 W2 H1 H2 W1 D1 D2 H...

Страница 139: ...29 The Dimensions in mm in inch of the Opening and Drive Outline with Flange FR4 FR6 Drive type W1 W2 W3 H1 H2 H3 H4 0004 2 0012 2 0003 5 0012 5 123 4 84 113 4 45 315 12 40 325 12 8 5 0 20 6 5 0 26 00...

Страница 140: ...5 2 0140 5 0205 5 0062 6 0100 6 289 11 38 355 13 98 330 12 99 344 13 54 110 4 33 9 0 35 Table 31 Dimensions in mm in inch of the VACON NXS NXP AC Drive with Flange FR7 FR8 Part 2 Drive type H1 H2 H3 H...

Страница 141: ...4 188 5 7 42 188 5 7 42 34 5 1 36 32 1 26 7 0 28 7 0 28 H5 H4 H4 H3 H1 H2 W1 W2 e30bg007 10 Illustration 67 Dimensions of the Opening and Drive Outline with Flange FR8 Table 33 Dimensions in mm in in...

Страница 142: ...type W1 W2 W3 W4 W5 D1 D2 D3 0261 2 0300 2 0261 5 0300 5 0125 6 0208 6 530 20 87 510 20 08 485 19 09 200 7 87 5 5 0 22 362 14 25 340 13 39 109 4 29 21 0 83 Table 35 Dimensions in mm in inch of the VAC...

Страница 143: ...FR11 Standalone W2 W3 W1 H3 D1 H4 H2 H1 e30bg009 10 Illustration 69 Dimensions of the VACON NXS NXP AC Drive FR10 and FR11 Standalone AQ275638903263en 000601 DPD00910 143 Danfoss A S 2022 12 Specifica...

Страница 144: ...R11 Standalone Drive type W1 W2 W3 H1 H2 H3 H4 H5 D1 0385 5 0520 5 0261 6 0416 6 595 23 43 291 11 46 131 5 16 2018 79 45 1900 74 8 1435 56 5 512 20 16 2139 84 21 602 23 70 0590 5 0730 5 0460 6 0590 6...

Страница 145: ...6 4 x 21 4 x 0 83 4 x 28 4 x 1 10 4 x 48 4 x 1 89 4 x 60 4 x 2 36 9 x 11 9 x 0 43 1 Same as maximum cable thickness NOTE Cable clamps have 40 mm internal diameter The clamps are used for 360 degree g...

Страница 146: ...FR6 to FR9 12 3 6 Cable and Fuse Sizes for 380 500 V FR10 to FR11 Standalone 12 3 8 Cable and Fuse Sizes for 525 690 V FR10 to FR11 For AC Drives in North America see 12 3 3 Cable and Fuse Sizes for...

Страница 147: ...correction factor 0 7 12 3 3 Cable and Fuse Sizes for 208 240 V and 380 500 V FR4 to FR9 North America Table 40 Cable and Fuse Sizes for VACON NXS NXP North America Enclosure size Drive type Fuse Cla...

Страница 148: ...168 5 250 3 3 0 AWG 1 0 AWG 3 0 AWG 350 kcmil Cu Al 10 AWG 3 0 AWG 0205 2 0205 5 250 3 300 kcmil 2 0 AWG 3 0 AWG 350 kcmil Cu Al 10 AWG 3 0 AWG FR9 0261 2 0261 5 350 3 350 kcmil 3 0 AWG 2 3 250 kcmil...

Страница 149: ...Rating 600 V FR6 to FR9 North America Table 42 Cable and Fuse Sizes for VACON NXS NXP North America UL Rating 525 600 V Enclosure size Drive type Fuse Class Fast Acting T J A Mains Motor and brake re...

Страница 150: ...omply with the UL standards 12 3 6 Cable and Fuse Sizes for 380 500 V FR10 to FR11 Standalone NOTE In FR10 and FR11 Standalone drives the drive cabinet includes ultra fast aR fuses for short circuit p...

Страница 151: ...3 350 kcmil Al 1 0 AWG Cu Even Even Odd 1 Uses a correction factor 0 7 2 Use cables with a 90 C 194 F heat resistance to comply with the UL standards 12 3 8 Cable and Fuse Sizes for 525 690 V FR10 to...

Страница 152: ...10 0261 6 350 3 pcs Cu 3 350 kcmil 3 0 AWG Al 2 3 3 0 AWG Al 2 AWG Cu Even Odd Even Odd 0325 6 400 3 pcs Cu 2 3 3 0 AWG 1 0 AWG Al 2 3 300 kcmil Al 1 AWG Cu Even Odd Even Odd 0385 6 500 3 pcs Cu 2 3 2...

Страница 153: ...28 240 240 FR9 28 295 28 295 28 295 28 295 Table 48 Cable Stripping Lengths in Enclosure size A1 B1 C1 D1 A2 B2 C2 D2 FR4 0 59 1 38 0 39 0 79 0 28 1 97 0 28 1 38 FR5 0 79 1 57 0 39 1 18 0 79 2 36 0 79...

Страница 154: ...Torques of the Terminals Table 49 Tightening Torques of the Mains and Motor Terminals Enclosure size Drive type Tightening torque Nm Tightening torque in lb FR4 0004 2 0012 2 0003 5 0012 5 0 5 0 6 4...

Страница 155: ...s is to make sure that the output current is not more than IL during the duty cycle e30bg038 10 IL IL 110 1 min 9 min I t IL 110 Illustration 74 Low Overload The high overload means that if 150 of the...

Страница 156: ...5 19 3 12 5 18 8 25 0 4 0 3 0 0025 25 25 27 5 17 5 26 3 35 0 5 5 4 0 0031 31 31 34 1 25 0 37 5 50 0 7 5 5 5 FR6 0048 48 48 52 8 31 0 46 5 62 0 11 0 7 5 0061 61 61 0 67 1 48 0 72 0 96 0 15 0 11 0 FR7 0...

Страница 157: ...5 19 3 12 5 18 8 25 0 5 4 0025 25 25 27 5 17 5 26 3 35 0 7 5 5 0031 31 31 34 1 25 0 37 5 50 0 10 7 5 FR6 0048 48 48 52 8 31 0 46 5 62 0 15 10 0061 61 61 0 67 1 48 0 72 0 96 0 20 15 FR7 0075 75 75 0 8...

Страница 158: ...0012 12 12 13 2 9 13 5 18 5 5 4 FR5 0016 16 16 17 6 12 18 24 7 5 5 5 0022 23 23 25 3 16 24 32 11 7 5 0031 31 31 34 23 35 44 15 11 FR6 0038 38 38 42 31 47 62 18 5 15 0045 46 46 49 5 38 57 76 22 18 5 0...

Страница 159: ...Hz 3 Enclosure size Drive type Input current Iin 1 Low load ability IL A 2 Low load ability 10 over load I A High loadabili ty IH A 2 High loadabili ty 50 overload I A Loadabili ty Max IS 2 s Motor sh...

Страница 160: ...temperatures are achieved only when the switching frequency is the same or smaller than the factory default 2 See 12 7 1 Overload Capability 3 480 V 12 7 6 Power Ratings for Mains Voltage 525 690 V UL...

Страница 161: ...0 90 0 0144 144 0 144 0 158 0 125 0 188 0 250 0 132 0 110 0 0170 170 0 170 0 187 0 144 0 216 0 288 0 160 0 132 0 0208 208 0 208 0 229 0 170 0 255 0 340 0 200 0 160 0 FR10 3 0261 261 0 261 0 287 0 208...

Страница 162: ...2 18 0 27 0 36 0 20 15 0027 27 0 27 0 29 7 22 0 33 0 44 0 25 20 0034 34 0 34 0 37 0 27 0 41 0 54 0 30 25 FR7 0041 41 0 41 0 45 0 34 0 51 0 68 0 40 30 0052 52 0 52 0 57 0 41 0 62 0 82 0 50 40 FR8 0062...

Страница 163: ...nection to mains Once per minute or less Starting delay 2 s FR4 to FR8 5 s FR9 Network imbalance Maximum 3 of the nominal voltage Mains Mains types TN TT and IT short circuit current the maximum short...

Страница 164: ...IL current 10 C 14 F no frost 40 C 104 F IH current 10 C 14 F no frost 50 C 122 F FR10 FR11 Standalone IP21 UL Type 1 IH IL 10 C 14 F no frost 40 C 104 F except 525 690 V 0461 and 0590 10 C 14 F no fr...

Страница 165: ...Vibration IEC EN 60068 2 6 IEC EN 61800 5 1 5 150 Hz Displacement amplitude 1 mm peak at 5 15 8 Hz FR4 FR9 Maximum acceleration amplitude 1 G at 15 8 150 Hz FR4 FR9 Displacement amplitude 0 25 mm pea...

Страница 166: ...ponds to a controlled stop in accordance with stop category 1 EN60204 1 ATEX thermistor input 94 9 EC CE 0537 Ex 11 2 GD Approvals CE cULus RCM KC EAC UA See the nameplate of the drive for more approv...

Страница 167: ...protection of 24 V and 10 V reference voltages Yes Drive enclosure ma terials Paint color codes for the enclosure Dark grey NCS 7010 R90B Pantone 7546C Blue NCS S3020 B 1 For the motor thermal memory...

Страница 168: ...2 2 0012 30 3 0 FR5 0017 30 4 0 0025 30 5 5 0031 20 7 5 FR6 0048 10 11 0 0061 10 15 0 FR7 0075 3 3 22 0 0088 3 3 22 0 0114 3 3 30 0 FR8 0140 1 4 37 0 0170 1 4 45 0 0205 1 4 55 0 FR9 0261 1 4 75 0 030...

Страница 169: ...3 1 5 0004 63 2 2 0005 63 3 0 0007 63 4 0 0009 63 5 5 0012 63 7 5 FR5 0016 63 11 0 0022 63 11 3 0031 42 17 0 FR6 0038 19 22 0 0045 19 30 0 0061 14 37 0 FR7 0072 6 5 45 0 0087 6 5 55 0 0105 6 5 75 0 FR...

Страница 170: ...525 690 V Table 59 Brake Chopper Ratings for VACON NXS NXP AC Drives Mains Voltage 525 690 V 50 60 Hz 3 Enclosure size Drive type The minimum brake resistance Brake power 1166 V DC kW 1 FR6 0004 100 3...

Страница 171: ...nal motor speed to zero or a 1 s full power braking every minute Table 60 Internal Brake Resistors FR4 FR6 Enclosure size Resistance Energy 2 s full torque braking kJ Average power 1 pulse min W FR4 3...

Страница 172: ...crease a short circuit in the motor cables the motor is not the correct type Troubleshooting Check the load Check the motor Check the cables and connections Make an identification run 12 10 4 Fault 1...

Страница 173: ...hat the sum of the motor phase current is not zero Insulation malfunction in the cables or in the motor It is possible to set different responses in the application for this fault See parameter group...

Страница 174: ...ain ask instructions from the local distributor 12 10 13 Fault 8 System fault Subcode S5 Disturbance in VaconBus Cause operation malfunction defective component Troubleshooting Reset the fault and sta...

Страница 175: ...ult Subcode S11 Power unit comm Measurement Cause operation malfunction defective component Troubleshooting Reset the fault and start the drive again If the fault shows again ask instructions from the...

Страница 176: ...se OPTAF board EEPROM error checksum not answering and so on Troubleshooting Change the OPTAF board 12 10 25 Fault 8 System fault Subcode S34 OPTAF Voltage problem Cause OPTAF supply voltage hardware...

Страница 177: ...not detected on thermistor Cause Single hardware problem detected in the thermistor input Troubleshooting Change the OPTAF board 12 10 34 Fault 8 System fault Subcode S43 OPTAF Test pulse high is not...

Страница 178: ...CON NXS control board Cause OPTAF is only compatible with VACON NXP Troubleshooting Remove the OPTAF board 12 10 41 Fault 8 System fault Subcode S50 OPTAF Filter discharge resistor fault Cause Problem...

Страница 179: ...ns from the local distributor 12 10 46 Fault 10 Input line supervision Subcode S1 Phase supervision diode supply Cause The input line phase is missing It is possible to set different responses in the...

Страница 180: ...overtemperature Subcode S1 Overtemperature warning in unit board or phases Cause Overheating detected in AC drive Heat sink temperature is over 90 C 194 F Overtemperature alarm is issued when the heat...

Страница 181: ...otor stalled Cause The motor stalled It is possible to set different responses in the application for this fault See parameter group Protections Troubleshooting Check the motor and the load Insufficie...

Страница 182: ...ror Cause Parameter save fault Operation malfunction defective component Troubleshooting If the fault occurs again ask instructions from the local distributor 12 10 64 Fault 22 Parameter fault Subcode...

Страница 183: ...set Cause Parameter save fault Troubleshooting Recommission the application Check parameters 12 10 70 Fault 24 Counter fault Cause Values that showed on the counters are incorrect Troubleshooting Hav...

Страница 184: ...t of option board has detected increase of the motor temperature It is possible to set different responses in the application for this fault See parameter group Protections Troubleshooting Do a check...

Страница 185: ...ontrol board Cause A new option board has replaced the old one in the same slot The parameters are available in the drive Troubleshooting Reset the fault The device is ready for use The drive starts t...

Страница 186: ...leshooting Ask instructions from the local distributor 12 10 92 Fault 40 Device unknown Subcode S6 Old power unit Asic and new software mis match Cause An unknown or mismatching device was connected t...

Страница 187: ...overtemperature protection has detected too high a short term overload current Troubleshooting Check the load Check the motor frame size Make an identification run Check brake resistor resistance 12 1...

Страница 188: ...e resistance leakage earth fault BCU Cause Brake resistor overtemperature protection has detected too heavy braking Troubleshooting Reset unit Set the deceleration time longer Dimensioning of the brak...

Страница 189: ...erchanging the encoder chan nels can be used to change the indicated rotation direction 12 10 108 Fault 43 Encoder fault Subcode S5 Encoder board missing Cause The encoder board is missing Troubleshoo...

Страница 190: ...unting of the encoder and make sure that the encoder is not slipping Check the encoder parameters for example encoder ppr 12 10 115 Fault 43 Encoder fault Subcode S12 Dual speed supervision fault Caus...

Страница 191: ...zero has occurred in application program Troubleshooting If the fault shows again while the AC drive is in run state ask instructions from the local distributor For an application programmer do a che...

Страница 192: ...entification Cause Identification run has failed This fault is type A fault Alarm Troubleshooting Run command was removed before completion of identification run The motor is not connected to the AC d...

Страница 193: ...main power switch of the drive 12 10 135 Fault 65 Measured Temperature Cause Shows temperature measurement fault for option board OPTBH or OPTB8 Temperature exceeded set limit Sensor disconnected Shor...

Страница 194: ...R9 142 Dimensions FR10 FR11 144 Dimensions FR7 133 Dimensions FR8 135 Dimensions FR9 137 Dimensions FR4 FR6 131 Display indications 26 Display backlight 114 Display contrast 113 Disposal 10 Down from...

Страница 195: ...odified label 31 Q Qualified personnel 10 R Remote commands 16 Resetting fault history 104 RUN test 123 S Safety 12 13 Security menu 110 Service Info file 128 Sine filter parameter 115 Software inform...

Страница 196: ...ures and other printed material Danfoss reserves the right to alter its products without notice This also applies to products already on order provided that such alterations can be made without subseq...

Отзывы: