![Danfoss VACON NXS Air-cooled Скачать руководство пользователя страница 161](http://html1.mh-extra.com/html/danfoss/vacon-nxs-air-cooled/vacon-nxs-air-cooled_operating-manual_3596124161.webp)
Enclosure
size
Drive
type
Input
current
I
in
(1)
Low load-
ability: I
L
[A]
(2)
Low load-
ability:
10% over-
load I [A]
High
loadabili-
ty: I
H
[A]
(2)
High
loadabili-
ty: 50%
overload I
[A]
Loadabili-
ty: Max I
S
2
s
Motor
shaft
power
(3)
:
10% over-
load 40°C
[kW]
Motor
shaft
power
(3)
:
50% over-
load 50°C
[kW]
0027
27.0
27.0
29.7
22.0
33.0
44.0
22.0
18.5
0034
34.0
34.0
37.0
27.0
41.0
54.0
30.0
22.0
FR7
0041
41.0
41.0
45.0
34.0
51.0
68.0
37.5
30.0
0052
52.0
52.0
57.0
41.0
62.0
82.0
45.0
37.5
FR8
0062
62.0
62.0
68.0
52.0
78.0
104.0
55.0
45.0
0080
80.0
80.0
88.0
62.0
93.0
124.0
75.0
55.0
0100
100.0
100.0
110.0
80.0
120.0
160.0
90.0
75.0
FR9
0125
125.0
125.0
138.0
100.0
150.0
200.0
110.0
90.0
0144
144.0
144.0
158.0
125.0
188.0
250.0
132.0
110.0
0170
170.0
170.0
187.0
144.0
216.0
288.0
160.0
132.0
0208
208.0
208.0
229.0
170.0
255.0
340.0
200.0
160.0
FR10
(3)
0261
261.0
261.0
287.0
208.0
312.0
416.0
250.0
200.0
0325
325.0
325.0
358.0
261.0
392.0
522.0
315.0
250.0
0385
385.0
385.0
424.0
325.0
488.0
650.0
355.0
315.0
0416
416.0
416.0
358.0
325.0
488.0
650.0
400.0
315.0
FR11
(3)
0460
460.0
460.0
506.0
385.0
578.0
770.0
450.0
355.0
0502
502.0
502.0
552.0
460.0
690.0
920.0
500.0
450.0
0590
590.0
590.0
649.0
502.0
753.0
1004.0
560.0
500.0
1
The currents in given ambient temperatures are achieved only when the switching frequency is the same or smaller than the factory default.
2
3
690 V
AQ275638903263en-000601 / DPD00910 | 161
Danfoss A/S © 2022.12
Specifications
VACON® NXS/NXP Air-cooled
Operating Guide
Содержание VACON NXS Air-cooled
Страница 1: ...Operating Guide VACON NXS NXP Air cooled Wall mounted and Standalone drives danfoss com...
Страница 2: ......