5
vacon • 30
PROFINET IO protocol
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
5.4.4
User specific record data
For easy access to drive parameters and monitoring values, the VACON
®
100 AC drive maps the
PROFINET user specific record indexes 0x0000 - 0x7FFF directly into the application IDs of the drive
based on the IEC61131 standard. Both read and write access is supported.
NOTE!
The response data is in raw format. See application manual for available IDs, amount of
decimals and the unit used for the parameters.
In the examples below, the following index values are used:
•
102 = Maximum frequency (Hz)
•
600 = Motor control mode
Table 25. Example 1: Reading values from the AC drive
AC drive
Read command
Response
Slot
Subslot
Index
Hex
Dec
Actual value
VACON
®
100
1
2
102
00 07 A1 20
500000
50.0000 Hz
600
00 00 00 01
1
1 = OL Speed
137
VACON
®
DW PDI6
10122
VACON
®
32-bit Process Data In
138
VACON
®
DW PDI7
10122
VACON
®
32-bit Process Data In
139
VACON
®
DW PDI8
10122
VACON
®
32-bit Process Data In
Table 24. Application ID access settings
Slot
Subslot
Description
1
2
Access IDs as VACON® 100 actual data type
Table 26. Example 2: Writing values for the AC drive
AC drive
Write command
Actual value
Slot
Subslot
Index
Length
Value (Hex)
VACON
®
100
1
2
102
4
00 06 DD D0
45.0000 Hz
600
4
00 00 00 00
0 = OL Frequency
Table 23. PROFIdrive signal numbers
Signal no.
Signal name
PNU
PNU name