Fieldbus parameterization
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
4.2.1
Name of Station
The Profinet IO "Name of Station" parameter can be set via VACON
®
Live. Other possibility is to set
this name by writing it via Ethernet with the DCP protocol. The name is empty if no name is set, or
if name is set as "temporary" by network device.
4.2.2
Communication timeout
The Communication timeout defines how much time can pass from the last received message from
the Master Device before a fieldbus fault is generated. This value is considered as an additional
timeout which works on top of the timeout mechanism of the PROFINET IO protocol. When a con-
nection loss is noticed, fault activation is started. If communication timeout value is zero, the fault
is activated immediately, otherwise the fault activates after a specified time. If the connection is re-
opened before the specified time has elapsed, no fault is created.
See Chapter 5.5.
4.3
Ethernet common settings
Usually in PROFINET IO network the PLC will set IP settings of the drive automatically when it tries
to connect to it. User only needs to set Profinet IO "Name Of Station" value which will used to identify
the drive in PLC program.
P5.9.5.2.6
Number of process
data
0
8
-
0
2441
The number of additional
process data fields
selected for
communication.
P5.9.5.2.7
Drive control word
0
FFFFFFFF
h
hex
0
2442
The latest control word
(vendor-specific format)
received from the drive
application. (Can be used
for debugging purposes.)
P5.9.5.2.8
Drive status word
0
FFFFFFFF
h
hex
0
2443
The latest status word
(vendor-specific format)
received from the drive
application. (Can be used
for debugging purposes.)
P5.9.5.2.9
Connection time-
outs
0
65535
d
-
0
2444
The number of
connection timeouts that
have occurred in the
PROFINET IO protocol.
P5.9.5.2.10
Parameter access
0
99999
d
-
0
2445
The number of
parameter accesses
received by the device.
P5.9.5.2.11 Profile control word
0
FFFFFFFF
h
hex
0
2595
STW1 sent by master.
Not updated when
vendor specific control
word is used.
P5.9.5.2.12
Profile status word
0
FFFFFFFF
h
hex
0
2596
ZSW1 sent to master.
Not updated when
vendor specific control
word is used.
Table 6. PROFINET monitoring values
Code
Parameter
Min
Max
Unit
Default
ID
Description