Table 5-5 Bearing Fault Types
Bearing Status
Description
Startup Calibration Check Fault
A discrepancy between the Bearing Startup check and the stored calibration values has been detected.
Axial Displacement Fault
Axial Orbit has exceeded the limit longer than the maximum time allowable.
Axial Overcurrent Fault
Axial Current has exceeded the limit longer than the maximum time allowable.
Front Radial Displacement Fault
Front Radial Orbit has exceeded the limit longer than the maximum time allowable.
Front Radial X Overcurrent Fault
Front Radial X Current has exceeded the limit longer than the maximum time allowable.
Front Radial Y Overcurrent Fault
Front Radial Y Current has exceeded the limit longer than the maximum time allowable.
Rear Radial Displacement Fault
Rear Radial Orbit has exceeded the limit longer than the maximum time allowable.
Rear Radial X Overcurrent Fault
Rear Radial X Current has exceeded the limit longer than the maximum time allowable.
Rear Radial Y Overcurrent Fault
Rear Radial Y Current has exceeded the limit longer than the maximum time allowable.
5.2 Troubleshooting with the Service Monitoring Tools Software
The SMT software package can be used to view detailed compressor information for operational status indications
and troubleshooting procedures. Please refer to the Service Monitoring Tools User Manual for the details on how to
use the SMT software.
5.2.1 Compressor Fault Troubleshooting
When troubleshooting a compressor fault, detailed analysis of this data should be made (in conjunction with a
compressor recording file, if possible) to determine the specific fault and determine the root cause of fault
occurrence.
Downloading fault and event logs every time a compressor is visited is useful for documenting compressor
operational history.
Fault and event history can be extracted from the compressor memory in the SMT Logged Event and Fault Viewer
tool. See the latest Service Monitoring Tools User Manual for user instructions.
Active compressor fault and alarm messages can be viewed in the SMT Active Alarm/Fault Viewer tool. See the latest
Service Monitoring Tools User Manual for user instructions.
Compressor Alarm and Fault settings can be found in the Configure Alarms/Faults menu option of the Active
Alarm/Fault Viewer tool.
The
Compressor Data Recording
and Playback tool provides a method of reviewing operational conditions without a
connection to the compressor. It also creates a file to electronically transmit for peer review. See the latest Service
Monitoring Tools User Manual for use instructions.
The following principle is applied when having both a fault and/or an alarm limit as triggers. Refer to Figure 5-1
Fault Trigger Methods on page 255 for explanations regarding faults and alarms and the trigger method
terminology is used:
l
Instant fault triggering (INS)
l
Ascending Fault Triggering (AFT)
l
Descending Fault Triggering (DFT)
l
Range Fault Triggering (RFT)
Page 254 of 294 - M-SV-001-EN Rev. H 1/23/2023
Содержание Turbocor TT Series
Страница 2: ...THIS PAGE INTENTIONALLY LEFT BLANK Page 2 of 294 M SV 001 EN Rev H 1 23 2023...
Страница 14: ...Page 14 of 294 M SV 001 EN Rev H 1 23 2023 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 16: ...Page 16 of 294 M SV 001 EN Rev H 1 23 2023 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 18: ...Figure 1 2 New Type Code Page 18 of 294 M SV 001 EN Rev H 1 23 2023...
Страница 39: ...Figure 2 6 Compressor Energy and Signal Flow Connections M SV 001 EN Rev H 1 23 2023 Page 39 of 294...
Страница 46: ...Page 46 of 294 M SV 001 EN Rev H 1 23 2023 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 250: ...Page 250 of 294 M SV 001 EN Rev H 1 23 2023 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 268: ...Figure 5 3 Bearing Calibration Flow Page 268 of 294 M SV 001 EN Rev H 1 23 2023...
Страница 274: ...Page 274 of 294 M SV 001 EN Rev H 1 23 2023 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 282: ...Figure B 2 Compressor Operation Troubleshooting Flowchart Sheet 2 Page 282 of 294 M SV 001 EN Rev H 1 23 2023...
Страница 283: ...Figure B 3 Compressor Voltage Troubleshooting Flowchart Sheet 1 M SV 001 EN Rev H 1 23 2023 Page 283 of 294...
Страница 284: ...Figure B 4 Compressor Voltage Troubleshooting Flowchart Sheet 2 Page 284 of 294 M SV 001 EN Rev H 1 23 2023...
Страница 285: ...Figure B 5 Compressor Voltage Troubleshooting Flowchart Sheet 3 M SV 001 EN Rev H 1 23 2023 Page 285 of 294...
Страница 286: ...Page 286 of 294 M SV 001 EN Rev H 1 23 2023 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 290: ...Page 290 of 294 M SV 001 EN Rev H 1 23 2023 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 292: ...Page 292 of 294 M SV 001 EN Rev H 1 23 2023 THIS PAGE INTENTIONALLY LEFT BLANK...