Nomenclat
ure
1)
Parameter
TLX Series
6k
TLX Series
8k
TLX Series
10k
TLX Series
12.5k
TLX Series
15k
Euro efficiency, V at
dc,r
96.5%
97.0%
97.0%
97.3%
97.4%
Other
Dimensions (H,W,D)
700 x 525 x 250 mm
Mounting
Wall bracket
Weight
35 kg
Acoustic noise level
56 dB(A)
MPP trackers
2
3
Operation temperature
range
-25..60 °C
Nom. temperature range
-25..45 °C
Storage temperature
-25..60 °C
Overload operation
Change of operating point
Active power control
3)
Included
Reactive power control
TLX+ and TLX Pro+
Table 4.1 General Specifications
1) According to FprEN 50524 where relevant.
2) At identical input voltages. At unequal input voltages, V
mppmin
can
be as low as 250 V depending on total input power.
3) Remotely controlled via CLX monitoring and grid management
product or third-party device.
*) At rated grid voltage (V
ac,r
), Cos(phi) = 1.
**) At rated grid voltage (V
ac,r
).
Parameter
TLX Series
Functional Safety
Passive
Active AC discon-
nection
Safety (protective class)
Class I
PELV on the communi-
cation and control card
Class II
Islanding detection - loss
of mains
Three-phase
monitoring ROCOF
Voltage magnitude
Included
Frequency
Included
Insulation resistance
Included
RCMU - Type B
Included
Indirect contact
protection
Yes (class I,
grounded)
Table 4.2 Functional Safety Specifications
Technical Data
L00410309-09_02
19
4
4
www.neoenerji.com