To set

Press “

” button for 3 seconds till “ ” display, there’s a number of count down in the center of LCD, Use “ ” or 

“ ” to adjust the desired sleep time: the max. = 48 hours; thermostat will return to the working status after 5 

seconds, “ ” is flashing to start counting down. The setpoint should be replaced by the sleep setpoint. 

To quit: 

When thermostat get into Sleep function, “ ” will flash, press “ ” or “ ” to quit.   

"

 Keypad lock: 

press “ ” and “ ” for 10 seconds till to “ ” display to activate, under this function, any keypad is locked. 

Press “ ” and “ ” for 10 seconds till “ ” disappear to quit the function. 

"

 

Set Parameters: 

With thermostat off, press “

” for 10 seconds to enter menu to set the parameters. 

Parameter table

 

Paramete

Description Default 

Range 

Step 

Power on status (0: Off; 1: On; 2: Hold) 

0 - 2 

 

Fan speed (0: Single Speed; 1: Three Speed) 

0 - 1 

 

Fan mode (DA; DB) 

 

 

Sensor selection (0: Internal; 1: Remote) 

0 - 1 

 

Temperature format (0: Celsius; 1: Fahrenheit) 

0 - 1 

0.1 

Temperature calibration 

-20.0 -

 ﹢

20.0 0.1 

7 Minimum 

setpoint 

5

/41

0 - 99.5 

0.5 

8 Maximum 

setpoint 

35

/96

0 - 99.5 

0.5 

Dead band (REPI-4) 

0 - 10 

0.5 

10 

Heating & Auto sleep setpoint 

7

/45

0 - 99.5 

0.5 

11 Cooling 

sleep 

setpoint 

28

/82

0 - 99.5 

0.5 

12 

Comms# (REPI-2N;REPI-4N) 

1 - 32 

13 

Input Signal Mode 
0: Invalid 
1: Changeover(REPI-2) 
2: thermostat will be sleep without input signal 
3: thermostat will be Off without input signal 

0 - 3 

 

14 

Heating reset time 

90 sec. 

10 - 300 sec. 

10 sec. 

15 

Cooling reset time 

90 sec. 

10 - 300 sec. 

10 sec. 

16 

Ports mode (0: Modulation & Floating; 1: On/Off) 

0 - 1 

 

17 

Valve status as turn off (0: Close; 1:Hold; 2: Open ) 

0 - 2 

 

18 

Port1 Modulation direction(0:10V Open; 1:10V Close)

0 - 1 

 

19 

Port1 Modulation minimum signal 

0Bit 

0-128Bit(5V/10mA) 0.04V/Bit(0.08mA/Bit)

20 

Port1 Modulation proportional 

1 - 20 

0.5 

21 

Port2 Modulation direction(0:10V Open;1:10V Close)

0 - 1 

 

22 

Port2 Modulation minimum Signal 

0 Bit 

0-128Bit(5V/10mA) 0.04V/Bit(0.08mA/Bit)

23 

Port2 Modulation proportional 

1 - 20 

0.5 

24 

Port1 Floating minimum time 

1 sec. 

1 - 9 sec. 

1 sec. 

25 

Port1 Floating maximum time 

30 sec. 

10 - 300 sec. 

10 sec. 

26 

Port1 Floating minimum time 

1 sec. 

1-9 sec. 

1 sec. 

27 

Port1 Floating maximum time 

30 sec. 

10 - 300 sec. 

10 sec. 

28 

Disable / Enable bypass PID control 
( 0: Disable; 1: Enable ) 

0 - 1 

 

29 

Override output value when bypass PID control 
Display output value when enable PID control 

 

0 - 255 

 

30 

Override output value when bypass PID control 
Display output value when enable PID control 

 

0 - 255 

 