background image

CH180RFWIFI

WIRELESS TOUCHSCREEN 

PROGRAMMABLE THERMOSTAT

WITH WIFI CONNECTION

INSTRUCTIONS FOR USE

FANTINI COSMI S.p.A.

Via dell’Osio, 6 20090 Caleppio di Settala, Milano - ITALY

Tel. +39 02 956821 | Fax +39 02 95307006 | [email protected]

www.fantinicosmi.it

Summary of Contents for CH180RFWIFI

Page 1: ...HSCREEN PROGRAMMABLE THERMOSTAT WITH WIFI CONNECTION INSTRUCTIONS FOR USE FANTINI COSMI S p A Via dell Osio 6 20090 Caleppio di Settala Milano ITALY Tel 39 02 956821 Fax 39 02 95307006 info fantinicos...

Page 2: ...or each zone It is equipped with a room temperature and humidity sensor also performing the function of a zone heating cooling and humidity control commanding the O60RF and CH175 actuators It can also...

Page 3: ...rst press of any touch button allows you to activate the functions of the buttons themselves and to light up the display Once powered the MASTER CH180RFWIFI must be included in the Intellicomfort syst...

Page 4: ...gradient of reference 4 K h Maximum room temperature 45 C Storage temperature 10 C 60 C WIFI connection 2 4 GHz 802 11 b g n Router communication port 1080 Transmission and reception frequency 868 MHz...

Page 5: ...RAM TEMPERATURE 18 4 7 SETTING MANUAL and JOLLY PROGRAM TEMPERATURE 18 5 DISPLAYING PARAMETERS DISP 19 5 1 SEASON 19 5 2 EXTERNAL PROBE 19 5 3 HOURS OF USE 20 5 4 WIFI STATUS 21 5 6 RSSI 22 5 5 SERIAL...

Page 6: ...nce with the requirements concerning installation of electrical devices ATTENTION Make sure that the power supply is disconnected before performing installation The CH180RFWIFI programmable thermostat...

Page 7: ...CTION CH180RFWIFI Pry the back panel off the body by applying pressure to the specific groove at the bottom Remove the insulating protection by unscrewing the specific waterproof screw Make the electr...

Page 8: ...NECTION ATTENTION Electrical connections must be made by qualified personnel ATTENTION Electrical connection operations must be done with the system s power disconnected Electrical connections must be...

Page 9: ...tion the display goes back to the main screen allows you to CONFIRM and EXIT from the current screen allows you to PROGRAM 3 1 DATE AND TIME SETTING Note ESC always allows you to go back to the previo...

Page 10: ...R mode was previously selected 2s 2 1 12 01 01 01 18 23 0 1 36 DAY MAN MODE DISP PROG ZONE OFF ESC RH USER PROGR DATE AND TIME WINTER PROFILE AUX1 ON LOCK NO DATE AND TIME OK ESC PRESS x1 WINTER ESC W...

Page 11: ...to the next day Pressing COPY allows you to copy the temperature profile being displayed to the following day Pressing and holding OK allows you to go to the next zone Once you have reached DAY H HOLI...

Page 12: ...you lock the CH180RFWIFI keyboard and any CH120RF included in the network through a 3 digit numerical code It works only once then it must be enabled again 2s 2 1 12 01 01 01 18 23 0 1 36 DAY MAN MOD...

Page 13: ...the set password and unlock the keyboard Note with the KEYBOARD LOCK WITH PASSWORD function running the CH120RF keys connected to the MASTER CH180RFWIFI will also be locked A blackout does not reset t...

Page 14: ...has different operating modes called programs MAN MANUAL PROGRAM The device regulates room temperature using a set temperature specified on a case by case basis for an unlimited amount of time until a...

Page 15: ...he user to view some parameters set based on the active operating program 4 2 SELECTING THE OPERATING PROGRAM The programs are selected in cyclical order Note press ZONE and then press MODE to set the...

Page 16: ...peratures set based on the hourly programs on a weekly profile You can set the following temperature levels tC tE tA OFF every half hour The CH180RFWIFI has weekly pre set profiles in both winter and...

Page 17: ...n is displayed Press OK and use the and arrows to set the time with 30 min resolution and the day until which you want to maintain the set temperature 4 5 SETTING ZONE JOLLY PROGRAM Press ZONE to sele...

Page 18: ...If the device is in MAN or in JOLLY you can set a TMAN and TJ temperature value between 2 and 40 C Note the same procedure applies to single zones Note the same procedure applies to single zones WINT...

Page 19: ...ayed if no external probe is present 1 12 01 01 01 18 23 0 1 36 DAY AUTO MODE DISP PROG ZONE OFF ESC RH 2 24 4 TCOMF 20 1 ESC WINTER ESC PRESS ESC PRESS x2 TCOMF TECO WINTER EXT HOURS OF USE WIFI STAT...

Page 20: ...rrent year TMAX maximum room temperature measured from the previous day TMIN minimum room temperature measured from the previous day RESET Press OK on the CURRENT MONTH PREVIOUS MONTH and CURRENT YEAR...

Page 21: ...al If the icon is STEADY ON status is OK FLASHING ON device cannot find the server OFF the device is not connected to the router OFF will appear on the display Example WIFI STATUS 80 Good Signal 1 12...

Page 22: ...um NO DEVICE no device Note this number identifies the single device and is used for WiFi activation via the Intelliclima app 1 12 01 01 01 18 23 0 1 36 DAY AUTO MODE DISP PROG ZONE OFF ESC RH 2 24 4...

Page 23: ...he batteries contact technical support if the problem persists 050 CH175 No radio communication Check the mains power supply contact technical support if the problem persists 5 7 FAULTS Allows you to...

Page 24: ...5s 2s 2 1 12 01 01 01 18 23 0 1 36 DAY MAN MODE DISP PROG ZONE OFF ESC RH ADVAN PROGR LIGHT ON 30S ESC PRESS ESC LIGHT ON 30S INT LIGHT 5 DAY SVNGS YES TA 5 0 RH RELAY OFF ZONE NAMES OFFSET DIFF STD...

Page 25: ...2s 2 1 12 01 01 01 18 23 0 1 36 DAY MAN MODE DISP PROG ZONE OFF ESC RH ADVAN PROGR LIGHT ON 30S ESC LIGHT ON 30S INT LIGHT 5 DAY SVNGS YES TA 5 0 RH RELAY OFF ZONE NAMES OFFSET DIFF STD CELSIUS ENGLI...

Page 26: ...ing and or cooling unit only in zone 1 DEU G activation of a general dehumidification unit RAF G activation of a general cooling unit RIS G activation of a general heating unit R R G activation of a g...

Page 27: ...ing Room Kitchen Bathroom Entrance Hallway Attic Family Room Closet Guest Room Foyer Cellar Garage Laundry Room Boiler Room Day time area Night time area Floor Zone MASTER BEDROOM ESC 1 ZONE 1 ZONE NA...

Page 28: ...e between the OFF and ON status Note the differential value can be set between 0 3 and 5 0 or STD standard default STD OFFSET ESC OK 2s 2 1 12 01 01 01 18 23 0 1 36 DAY MAN MODE DISP PROG ZONE OFF ESC...

Page 29: ...ROG ZONE OFF ESC RH ADVAN PROGR LIGHT ON 30S ESC LIGHT ON 30S INT LIGHT 5 DAY SVNGS YES TA 5 0 RH RELAY OFF ZONE NAMES OFFSET DIFF STD CELSIUS ENGLISH EXT IN COOL OFF NO AUX1 MAN ZONE DEU WIFI A P CH1...

Page 30: ...W minimum safety temperature exceeded alarm This is a safety threshold only active in the SUMMER season and disables the system To activate press OK and set the desired minimum threshold using the or...

Page 31: ...ary to set a RH threshold and the DEW function must be disabled Note with the control active when a zone switches the cooling system off the symbol flashes in the corresponding zone COLL OFF NO ESC 2s...

Page 32: ...ragraph 3 4 Note CH175 in AUX 1 mode can only be associated to the programmable thermostat CH180RFWIFI and must be configured as auxiliary actuator AUX 1 Pressing or allows you to scroll the different...

Page 33: ...layed Note Only the zones with CH180RFWIFI and CH120RF are displayed CH175 in DEU ZONE A or in DEU ZONE B can only be associated with programmable thermostat CH180RFWIFI and must be configured as auxi...

Page 34: ...allows you to connect a smartphone WIFI A P ESC 2s 2 1 12 01 01 01 18 23 0 1 36 DAY MAN MODE DISP PROG ZONE OFF ESC RH ADVAN PROGR LIGHT ON 30S ESC LIGHT ON 30S INT LIGHT 5 DAY SVNGS YES TA 5 0 RH REL...

Page 35: ...PROGR LIGHT ON 30S ESC LIGHT ON 30S INT LIGHT 5 DAY SVNGS YES TA 5 0 RH RELAY OFF ZONE NAMES OFFSET DIFF STD CELSIUS ENGLISH EXT IN COOL OFF NO AUX1 MAN ZONE DEU WIFI A P CH180RW V1 0 RESET NO PRESS x...

Page 36: ...it go to ADVANCED PROGRAMMING and follow the instructions off NORM normal A P access point allows you to connect a smartphone Select A P and press ESC Start up the guided installation procedure on the...

Page 37: ...red name and press Add the programmable thermostat by pressing the key and select CH180RFWIFI Install the app and upon first activation create an account by entering a user name and password At the en...

Page 38: ...BLEMS If the router does not connect to the server 1 Check that the router password is correct repeating the steps in paragraphs 8 1 and 8 2 2 Check that the router supports standard 802 11 b g n 3 Co...

Page 39: ...er August 13th 2005 Participating in the separate collection of products and batteries contributes to the correct disposal of these materials and therefore avoids possible negative consequences for th...

Page 40: ...FANTINI COSMI S p A Via dell Osio 6 20090 Caleppio di Settala Milano ITALY Tel 39 02 956821 Fax 39 02 95307006 info fantinicosmi it www fantinicosmi it EN79898A 06 2019...

Reviews: