background image

TP970 Series 

CONVERTASTAT

®

 Kits 

REPLACEMENT DATA 

GENERAL 

This document provides procedures for replacing 
existing Johnson, Powers, and Robertshaw thermostats 
with the TP970 Series CONVERTASTAT Kit. The 
appropriate kit, selected from Table 1, replaces newer 
(small size) models of Johnson, Powers, or Robertshaw 
vertical or horizontal pneumatic thermostats used in two­
pipe applications and mounted on hollow wall (drywall) 
construction with air connections made directly to the 
thermostat using 5/32 in. plastic tubing, without the use 
of a wall fitting. 

APPLICATION 

Each CONVERTASTAT Kit includes a universal wall 
plate adapter, cover, and a TP970 Series Thermostat to 
replace various manufacturer’s thermostats. The 
thermostat cover is universal, allowing horizontal or 
vertical mounting and provides windows with or without 
setpoint and thermostat displays. All components 
needed to create a cover to meet building requirements 
are included. 

INSTALLATION 

When the old mounting plate is removed, retain the 
screws to use for mounting the adapter plate. Cut the 
existing tubes as close as possible to the thermostat. Do 
not remove the antikink springs from cut tubes. Do not 
allow tubes to slip inside the wall after removing the old 
thermostat. 

Remove Johnson Thermostat 

1.   Loosen top and bottom screws to remove cover. 
2.   Remove thermostat mounting screws from top and 

bottom and remove thermostat from mounting 
plate. 

3.   Cut tubes near air head and temporarily plug main 

line to conserve air. 

4.   Remove mounting plate and retain screws. 

70 

40  50  60  70  80  90 

C2313 

Fig. 1. Johnson Thermostat. 

Remove Robertshaw Thermostat 

1.   Turn cover screw on bottom clockwise to remove 

cover. 

2.   Remove mounting screws and remove thermostat 

from mounting plate. (Do not remove mounting 
plate.) 

3.   Cut tubes near fitting and temporarily plug main 

line to conserve air. 

® U.S. Registered Trademark 
Copyright © 2000 Honeywell Inc. •  All Rights Reserved 

85- 0210EF- 1 

Summary of Contents for CONVERTASTAT TP970A2145

Page 1: ...mponents needed to create a cover to meet building requirements are included INSTALLATION When the old mounting plate is removed retain the screws to use for mounting the adapter plate Cut the existing tubes as close as possible to the thermostat Do not remove the antikink springs from cut tubes Do not allow tubes to slip inside the wall after removing the old thermostat Remove Johnson Thermostat ...

Page 2: ...3 3011 T27 301 T27 3011 2214 121c 2214 131c 2216 126 2216 136 2216 526d TP971A2183 Same as TP971A2102 except plastic cover is beige T4506 6203c T4506 6204c 2214 521d TP972A2192 Single temp two pipe proportioning 60 to 90 F 16 to 32 C range RA Summer 13 psi 90 kPa or 9 psi 62 kPa unit vent DA Winter 18 psi 124 kPa changeover field adjustable T4756 205 T4756 206 T4756 217 T4756 6205 T4756 6206 T4756...

Page 3: ...s and separate see Fig 5 e Align and attach backplate and adapter plate to mounting screw holes using screws retained from stripping adapter plate threads f Proceed to Step 7 NOTE When adapting to a Johnson thermostat if wall holes are out of alignment with adapter plate holes use any available hole for an additional wall anchor HOLES 10 CODED PER MANUFACTURER J JOHNSON P POWERS R ROBERTSHAW TUBIN...

Page 4: ...at 4 F 2 2 K and should not require any change under normal operating conditions If a change is necessary use following procedures to reset throttling range to values specified on job drawings NOTE Changing throttling range requires recalibration 1 Remove cover and install 0 to 30 psi 0 to 210 kPa gage with gage adapter in gage tap Fig 8 2 Slide throttling range adjustment to desired position on t...

Page 5: ...reads approximately 10F 5 5C degrees above space temperature and set night setpoint dial below space temperature The gage should indicate main air pressure Push day auto lever to day left position it should stay there and BLP should go to 0 psi 0 kPa TP972 Turn setpoint adjustment until setpoint indicator reads approximately 10F 5 5C degrees above space temperature BLP should go to 0 psi 0 kPa 4 S...

Page 6: ...Pa 4 Turn calibration screw in opposite direction until gage indicates 8 1 psi 56 7 kPa The thermostat is now calibrated 5 Remove gage and replace cover TP971 1 Remove cover and install a 30 psi 210 kPa gage into gage tap 2 Turn setpoint adjustment until setpoint indicator reads indicated temperature 3 With 13 psi 90 kPa day main air pressure turn day left calibration screw Fig 8 until gage indica...

Page 7: ... notice explique comment retirer le thermostat selon le fabricant et installer le nouveau thermostat de série TP970 Une fois l ancienne plaque de montage retirée conserver les vis qui serviront à l installation de la plaque d adaptation Couper le tuyau existant aussi près que possible du thermostat Ne pas retirer des tuyaux le ressort antitortillement Ne pas laisser les tuyaux glisser à l intérieu...

Page 8: ...e TP971A2102 mais avec couvercle de plastique beige T4506 6203c T4506 6204c 2214 521d TP972A2192 Une seule temp deux canalisations à action proportionnelle gamme de 60 à 90 F 16 à 32 C action inverse en été à 13 psi 90 kPa ou 9 psi 62 kPa ventilo convecteur action directe en hiver inversion à 18 psi 124 kPa réglable sur place T4756 205 T4756 206 T4756 217 T4756 6205 T4756 6206 T4756 6217 TH192 208...

Page 9: ... plaque d adaptation et les fixer aux ouvertures des vis de montage à l aide des vis qui ont servi à aléser les filets de la plaque d adaptation f Passer à l étape 7 REMARQUE Lors du remplacement d un thermostat Johnson si les trous dans le mur ne corre spondent pas aux ouvertures de la plaque d adaptation utiliser n importe quel autre trou pour insérer une cheville additionnelle TROU DE GUIDAGE 2...

Page 10: ...couvercle et installer un manomètre de 0 à 30 psi 0 à 210 kPa dans la prise de manomètre Fig 8 2 Faire glisser le curseur de la bande proportionnelle à la valeur désirée 3 Vérifier mécaniquement la bande proportionnelle en déplaçant le réglage du point de consigne jusqu à ce que la pression de la canalisation princi pale soit de 3 psi 21 kPa Prendre note du point de consigne 4 Déplacer ensuite le ...

Page 11: ...uto à la position jour à gauche il devrait rester en position et la pression de la canalisation secondaire devrait passer à 0 psi 0 kPa TP972 Faire tourner le réglage du point de consigne jusqu à ce que l indicateur marque environ 10 F 5 5 C au dessus de la température ambiante La pression de la canalisation secondaire devrait passer à 0 psi 0 kPa B M S DU COUVERCLE DU FILTRE FILTRE DES ÉTAGES DU ...

Page 12: ...opposé jusqu à ce que le manomètre indique 8 psi 1 psi 56 kPa 7 psi Le thermostat est maintenant étalonné 5 Retirer le manomètre et remettre le couvercle TP971 1 Retirer le couvercle et installer un manomètre de 30 psi 210 kPa dans la prise de manomètre 2 Faire tourner le réglage du point de consigne jusqu à ce que l indicateur du point de consigne marque la température indiquée 3 Avec une pressio...

Reviews: