Data Sheet

Radiator thermostats for one-pipe and two-pipe systems

2

VD.51.Q1.

12 © Danfoss 10/2003

DKCD

Valve bodies for two-pipe systems type RA-FN

1) Remote sensors are recommended
2) Kvs-maximum indicates the water flow (Q) with valve fully open

Selection and specification

Should water treatment be
used it is essential that dosing
instructions of the manufacturer
are strictly observed. It is
recommended that formulations
containing mineral oil are
avoided.

RA 2910

013G2910

Built-in

5 - 26 °C (1)

RA 2920

013G2920

Built-in, tamper proof

5 - 26 °C (1)

RA 2914

013G2914

Built-in, low temperature range model

5 - 22 °C (1)

RA 2912

013G2912

Remote sensor, 0 - 2 m  capillary tube (2)

5 - 26 °C

RA 2922

013G2922

Remote sensor, 0 - 2 m  capillary tube, tamper proof (2)

5 - 26 °C

RA 2916

013G2916

Remote sensor, 0 - 2 m  capillary tube (2)

5 - 22 °C

RA 5062

013G5062

Remote temperature adjuster, 0 - 2 m  capillary tube (3)

8 - 28 °C

RA 5065

013G5065

Remote temperature adjuster, 0 - 5 m  capillary tube (3)

8 - 28 °C

RA 5068

013G5068

Remote temperature adjuster, 0 - 8 m  capillary tube (3)

8 - 28 °C

Type

   Code no.                  Sensor   (Max. sensor temperature 60°C)

Temp. range

Xp = 2K

RA2000 thermostatic sensors (4) supplied in separate boxes

(1) Temperatures shown are for units with built-in
sensors which are subject to influence from
radiation and flow temperature. Without these
influences, max. temperature is 2 °C higher at de-
sign load condition.

(2) Remote sensors are supplied with all the
capillary tube coiled within the sensor. When
installing the sensor, only the length required
should be uncoiled.

(3) Remote temperature adjusters are supplied with
adapters for RA-valves. Adaptors for older valves
can be  ordered separately:
RAVL-adaptor, code no. 013G5192
RAV-adaptor, code no. 013G5193

(4) Important note: Do not use any RA2000
sensors with RA-FR bi-directional valve bodies.

(1)

These valve bodies are supplied with compression
fittings for copper tube to BS 864. When these
connections are removed, a standard BSP screwed
inlet BS 21 remains.

(2)

Kvs-maximum indicates the water flow (Q) with valve
fully open.

(3)

Remote sensors are recommended.

Working pressure = differential pressures. The
maximum differential pressure specified is the maximum
pressure at which the valves give satisfactory control. As with
any device which imposes a pressure drop in the system,
noise may occur under certain flow/pressure conditions. To
ensure quiet operation, maximum pressure drop should not
exceed 40 to 45 kPa. The differential pressure can be
reduced by the use of Danfoss differential pressure controls.

When using RA2000 remote temperature adjusters  the kv-values stated in the table above must
be reduced by approximately 40% to take into account the different characteristics of these
sensors.

Valve bodies for one-pipe pumped or  gravity systems, type RA-G

kv-value

(m

3

/h at 1 bar pressure drop)

P-band = K

013G3384

013G3386

013G3388

Содержание RA 2000

Страница 1: ...hout draining down the system The protective cap supplied with each new valve may be used for manual control during installation only It should not be used as isolation device A manual shut off device...

Страница 2: ...ure is 2 C higher at de sign load condition 2 Remote sensors are supplied with all the capillary tube coiled within the sensor When installing the sensor only the length required should be uncoiled 3...

Страница 3: ...ase request details The required room temperature is set by rotating the sensor handle to match the scale number with the setting register The correlation between scale Setting the temperature numbers...

Страница 4: ...o temperature variations The time constant fig 3 depends on the specific heat and surface of the sen sor At a sudden change of the ambient temperature at time 0 the thermostat will react as shown rela...

Страница 5: ...sible To ensure that the valve capacity of a fully opened valve is not significantly greater than that at 2 degrees C P deviation all RA FN valves have a modified valve characteristic This improved va...

Страница 6: ...Capacities Use the following sizing charts to select the correct valve for the radiator in question Heat requirement 2 05 kW Temperature drop 11 C Differential pressure across the radiator 0 05 bar 5...

Страница 7: ...ard beneath the radiator if free of surface pipes All remote sensors are now supplied with ultra thin capillary Simply pull out the length required 2m max and fix using clips provided Remote temperatu...

Страница 8: ...perature adjuster DN D d2 RA FN 10 10 Rp 3 8 R3 8 60 85 27 52 22 47 96 22 27 RA FN 10 UK 10 Rp 3 8 R3 8 103 26 51 22 22 27 RA FN 15 15 Rp 1 2 R1 2 67 95 30 58 26 47 96 27 30 RA FN 15 UK 15 Rp 1 2 R1 2...

Отзывы: