Data Sheet

Radiator thermostats for one-pipe and two-pipe systems

6

VD.51.Q1.

12 © Danfoss 10/2003

DKCD

The P-band value depends on the chosen valve i.e.
RA-FN 15 will work with a P-band of 2K.

RA-FN 20 will work with a P-band of about 1.4K.

The Kv-value can also be calculated on the basis of
the formula

Kv

=

Q

Q(m

3

/h), 

p (bar)

√ ∆

p

0.044

=

0.044 x 3600 = 0.158 m

3

/h

1000

Kv

=

0.158

= 0.71

0.05

Note: 1m

3

/h = 0.278 l/s

Capacities

Use the following sizing charts
to select the correct valve for
the radiator in question.

Heat requirement:

2.05 kW

Temperature drop:

11°C

Differential pressure
across the radiator:

0.05 bar (5 kPa)

Solution:

Water flow through the radiator per hour:

Q =

2.05

= 0.044l/s

4.2 x11

Capacity with P-band between 0.5K and 2K  with RA 2000 sensor

Note:
As with any device which
imposes a pressure drop
system, noise may occur under
certain flow/pressure conditions.
To ensure quiet operation,
maximum pressure drop should
not exceed 40 to 45kPa.

Example

RA-FN
for two-pipe systems

RA-G
for one-pipe systems

Содержание RA 2000

Страница 1: ...hout draining down the system The protective cap supplied with each new valve may be used for manual control during installation only It should not be used as isolation device A manual shut off device...

Страница 2: ...ure is 2 C higher at de sign load condition 2 Remote sensors are supplied with all the capillary tube coiled within the sensor When installing the sensor only the length required should be uncoiled 3...

Страница 3: ...ase request details The required room temperature is set by rotating the sensor handle to match the scale number with the setting register The correlation between scale Setting the temperature numbers...

Страница 4: ...o temperature variations The time constant fig 3 depends on the specific heat and surface of the sen sor At a sudden change of the ambient temperature at time 0 the thermostat will react as shown rela...

Страница 5: ...sible To ensure that the valve capacity of a fully opened valve is not significantly greater than that at 2 degrees C P deviation all RA FN valves have a modified valve characteristic This improved va...

Страница 6: ...Capacities Use the following sizing charts to select the correct valve for the radiator in question Heat requirement 2 05 kW Temperature drop 11 C Differential pressure across the radiator 0 05 bar 5...

Страница 7: ...ard beneath the radiator if free of surface pipes All remote sensors are now supplied with ultra thin capillary Simply pull out the length required 2m max and fix using clips provided Remote temperatu...

Страница 8: ...perature adjuster DN D d2 RA FN 10 10 Rp 3 8 R3 8 60 85 27 52 22 47 96 22 27 RA FN 10 UK 10 Rp 3 8 R3 8 103 26 51 22 22 27 RA FN 15 15 Rp 1 2 R1 2 67 95 30 58 26 47 96 27 30 RA FN 15 UK 15 Rp 1 2 R1 2...

Отзывы: