manualshive.com logo in svg
background image

DKCD

VD.51.Q1.

12 © Danfoss 10/2003

5

Sensor operating principle

The RA2000 thermostatic sensor consisting of a bel-
lows system and saturated vapour charge provides
proportional control, as opposed to On/Off. The sen-
sor is actuated by ambient temperature changes.
The calibrated pressure in the bellows corresponds
to the temperature of the charge. This pressure is
balanced by the force of a regulating spring.
On a rise in ambient temperature, the vapour pres-
sure increases in the bellows, moving the valve
cone towards the “closed” position, until equilibrium
exists between the bellows and spring. On a drop in
ambient temperature, the vapour pressure falls, al-
lowing the bellows to contract and the valve cone to
move towards the “open” position until a state of
equilibrium is re-established.
The vapour charge will always condense at the cold-
est part of the sensor, usually that furthest away
from the valve body. The radiator thermostat will
therefore always respond to changes in room tem-
perature and will not be affected by the water tem-
perature itself. However, when the air around the
sensor is heated by the hot valve body and
pipework, then the sensor can register a higher tem-
perature than that of the rest of the room. For this
reason, Danfoss recommend that the sensor is
mounted horizontally whenever possible.

To ensure that the valve capacity of a fully opened
valve is not significantly greater than that at 2
degrees C P-deviation, all RA-FN valves have a
modified valve characteristic. This improved valve
characteristic maintains hydraulic balance during
start-up.

Proportional band
Proportional temperature controls try to maintain
equilibrium between heat loss and heat input. They
react proportionately to any deviation from a set
temperature level, until heat input is either com-
pletely shut off or is at its maximum. The tempera-
ture levels at which this occurs are presettable, and
the band between the two levels, measured in K
(degrees C) is the proportional band.

Danfoss radiator thermostats can be sized to oper-
ate across a defined proportional band. A range of
0,5 – 2K is recommended. In providing proportional
control, they ensure smaller swings in room tem-
perature than, say, a conventional room thermostat
which gives on/off control and needs to cycle
throughout its switching differential each time it op-
erates.

1.

Thermostatic element

2.

Bellows

3.

Setting dial

4.

Setting spring

5.

Limit pin

6.

Pressure pin

7.

O-ring seal

8.

Valve cone

9.

Valve body

10. Nozzle

Data Sheet

Radiator thermostats for one-pipe and two-pipe systems

Hydraulic balance

Definitions

kv-Coefficiant of flow
The kv-value of a valve shows the quantity of liquid,
in m3/h, that the valve will pass with a pressure
drop of 1 bar across the valve. This value is used in
the following formulae to calculate flow rates for
valve sizing purposes.

Содержание RA 2000

Страница 1: ...hout draining down the system The protective cap supplied with each new valve may be used for manual control during installation only It should not be used as isolation device A manual shut off device...

Страница 2: ...ure is 2 C higher at de sign load condition 2 Remote sensors are supplied with all the capillary tube coiled within the sensor When installing the sensor only the length required should be uncoiled 3...

Страница 3: ...ase request details The required room temperature is set by rotating the sensor handle to match the scale number with the setting register The correlation between scale Setting the temperature numbers...

Страница 4: ...o temperature variations The time constant fig 3 depends on the specific heat and surface of the sen sor At a sudden change of the ambient temperature at time 0 the thermostat will react as shown rela...

Страница 5: ...sible To ensure that the valve capacity of a fully opened valve is not significantly greater than that at 2 degrees C P deviation all RA FN valves have a modified valve characteristic This improved va...

Страница 6: ...Capacities Use the following sizing charts to select the correct valve for the radiator in question Heat requirement 2 05 kW Temperature drop 11 C Differential pressure across the radiator 0 05 bar 5...

Страница 7: ...ard beneath the radiator if free of surface pipes All remote sensors are now supplied with ultra thin capillary Simply pull out the length required 2m max and fix using clips provided Remote temperatu...

Страница 8: ...perature adjuster DN D d2 RA FN 10 10 Rp 3 8 R3 8 60 85 27 52 22 47 96 22 27 RA FN 10 UK 10 Rp 3 8 R3 8 103 26 51 22 22 27 RA FN 15 15 Rp 1 2 R1 2 67 95 30 58 26 47 96 27 30 RA FN 15 UK 15 Rp 1 2 R1 2...

Отзывы: