manualshive.com logo in svg
background image

2. Product description

2.1 Outline of refrigerant R744

2.2 Optyma™ iCO2 condensing unit

R744 is an environmentally friendly refrigerant with the ozone depleting coefficent at “0” and a smaller global warming 
potential. Refrigerant R410A is comparable with this in terms of the ozone depleting coefficient but has a higher global 
warming potential. R744 has a higher pressure of 64 bar at the same temperature, it is approximately 4 times higher than 
16.5 bar of R410A.

Caution of refrigerant R744
1. Refrigeration cycle operates at higher pressures.

As a result, it becomes necessary to change the airtight test pressure and setting pressures, including the airtight pressure,
withstanding test pressure, operating pressure, etc., for devices that constitute the refrigerating, and measuring instru-
ments and tools. It is necessary to change also the material and wall thickness of refrigerant pipe (Using K64 class standard 
pipe).

Refrigerant leak detector needs to have a higher sensitivity.

2. Only use Condensing unit oils recommended by Danfoss.

Synthetic oil (ester oil) compatible with R744 is used.

Scroll-rotary type compressor

WARNING

Scroll-rotary compressor is prohibited to turn in reverse.

Contrary to conventional reciprocal type compressor which can rotate in both directions, it can rotate in one direction only 
with the scroll-rotary compressor.

Scroll-rotary compressor becomes very hot

It is highly heated during and immediately after stop of operation. Special care must be taken during maintenance 
and service.

Oil is retained at the high pressure side of scroll-rotary compressor.

Care must be taken particularly when charging or discharging oil during maintenance, service, or test run.

Optyma™ iCO2 combines our market leading expertise in condensing unit design with the unique benefits of stepless 
inverter Rotary technology. The result is 20-30% higher energy efficiency in a flexible plug-and-play package.
The condensing unit includes following: 
•  Inverter Compressor ( Rotary) 
•  2 parallel gas cooler (Coated fin and tube Heat exchanger) 
•  Unit controller 
•  2 DC fan Assembly
•  Receiver 
•  The condensing unit assembly is CE, PED certified CAT II
•  This condensing unit controls its capacity by the speed control by means of inverter
•  Compressor is connected to the inverter, and operated at variable speed. The inverter changes the power supply frequency 

supplied to the compressor of which speed changes nearly proportional to this frequency. The capacity is controlled in 
this way.

•  Whether the load is high or low it is judged by detecting the low pressure (LP) of compressor. If the low pressure (LP) is 

high, it is judged that the load is high so that  the output capacity of condensing unit is increased.

•  The speed control by inverter features that it allows to change the capacity more finely than the unit number control of 

compressor. For this reason, it is better to install a plural number of evaporators, as much as possible, so as to control res-
pective liquid solenoid valves individually, for effective operation.

•  Since the inverter is in the advancing phase, if an advancing capacitor is installed, the power factor drops in reverse. Never 

install an advancing capacitor, because it may be broken.

8

AB408540130380en-000102

© Danfoss | Climate Solutions | 2023.02

Application Guidelines

Содержание Optyma OP-UPAC015COP04E

Страница 1: ...Optyma iCO2 condensing units R744 50 Hz Application guidelines www danfoss com...

Страница 2: ......

Страница 3: ...allation work 23 4 3 Delivery and installation of the condensing unit 23 4 4 Caution for piping work 24 4 5 Caution for electric wiring work 27 5 System design recommendations 31 5 1 Airtight Method 3...

Страница 4: ...ly to specified torque If they are not tightened securely it could cause fire or electric shock owing to overheat on the terminal Usespecifiedcablesforwiring andconnectthemsecurely avoidingexternalfor...

Страница 5: ...cation or disposal remove the refrigerant pipe after stopping the compressor If it is operated while the refrigerant pipe is removed and the gate valve is opened it could inhale air or other and raise...

Страница 6: ...pean Market Children should be supervised to ensure that they do not play with the appliance In the Australian and New Zealand market Restriction on use of equipment This appliance can be used by chil...

Страница 7: ...ething on the condensing unit It could cause injury if you fall damage the machine or drop the object Refrain from touching hands on the gas cooler fin directly You could get hurt CAUTION When washing...

Страница 8: ...pressure side of scroll rotary compressor Care must be taken particularly when charging or discharging oil during maintenance service or test run Optyma iCO2 combines our market leading expertise in...

Страница 9: ...ance 62 0 dB A Enclosure painting specification Stucco white PED catagory II Approval CE UKCA Compressor Type Hermetic inverter Type Oil Diamond freeze MA68 Displacement 15 CC Technology Scroll Rotary...

Страница 10: ...Oil pod Accumulator Subcooling coil temperature sensor Middle pressure receiver inlet temperature sensor EEV for middle pressure receiver inlet Gas cooler temperature sensor inlet Gas cooler temperat...

Страница 11: ...s with a wall If the unit installed in succession 10mm spaces is enough 1 All dimensions are in mm 2 Dimensions are not to scale Wall height H4 Wall height H3 Service space Service space Wall height H...

Страница 12: ...ology 2 stage Scroll Rotary Control box pre wired E panel Yes Fin and Tube condenser Yes Fan speed controller Yes Main switch circuit breaker Yes Filter drier Yes Sight glass Yes Crankcase heater Yes...

Страница 13: ...frigerant E Housing Service Pressure Maximum working pressure F Supply voltage Rated Load Ampere Maximum Continuous Current G Serial Number and bar code Danfoss IP24 PSHP PSLP MP PTHP PTLP MP PED Cate...

Страница 14: ...35 outlet 6 35 17 SENSOR LP SSA551D031 0 093 105 85 55 Carton box Middle pressure sensor PSM HSK BC 016 Range 0 to 100bar Connection size 6 0 18 VALVE CHECK SSA385A053 0 185 150 125 25 Vinyl bag Chec...

Страница 15: ...725 160 160 80 Carton box Fan motor UP12D23 GTEW Rated output 16W Rated voltage 230V 1 phase 50 60Hz 53 SENSOR ASSY LCA551A002 0 052 300 175 10 Vinyl bag THO G1 G2 54 SENSOR ASSY LCA551A002A 0 058 30...

Страница 16: ...tapes When using the wiring refer to the External input harness installation manual page 48 Dryer 1 Install in liquid pipe Dryer pipe diameter need to reduce with reducer to connect liquid pipe This...

Страница 17: ...rature exceeds 5 C rated capacity decreases due to the operation of the protection control and rated capacity decreases as the evaporation temperature increases Notes 1 When evaporating temperature ex...

Страница 18: ...SOUND POWER dB A 1 1 OCTAVE FREQUENCY HZ Acoustic Sound Spectrum 50Hz Weighted dB A Condensing unit Model OP UPAC015COP04E Condensing Unit Code 114X6003 Housing Compressor CO2 Electrical code Compres...

Страница 19: ...x 764 x 1691 5 340 590 340 510 850 375 345 381 726 697 Model Item Compressor speed min 1 Fan speed min 1 OP UPAC015COP04E 6240 1000 1 Note Dimensions L1 X1 X2 and L2 Y1 Y2 indicate the position of ins...

Страница 20: ...in a range of 5 deg to 40 deg Use this condensing unit within the following operation ranges Item Unit Specifications Refrigerant R744 Evaporation temperature C 45 5 Low pressure LP bar abs 8 3 30 5 S...

Страница 21: ...ith which the refrigerant flow speed in the heat exchanger piping is within the oil returnable range in the following figure Range of gas flow speed at the evaporator outlet during rated operation Ins...

Страница 22: ...rigerant oil 3 Oil return operation Delivery Hand over and instruction Plan the project Vacuum drying R744 R744 High pressure side Max 140 Bar Medium low pressure side Max 80 Bar indicates the airtigh...

Страница 23: ...levelness of foundation can prevent vibration and noise The foundation must be larger than the shadowed areas in the above figures larger than the front of the fixing legs of condensing unit The foun...

Страница 24: ...well designed and practiced the refrigerant piping work plays a critical influence over the capacity life or failures on the refrigerating unit Design and practice the piping work as instructed below...

Страница 25: ...from the factory Make sure to keep the seal intact till just before connecting pipes in order to keep out dirt or moisture Release to the atmosphere must be made through service ports at the high med...

Страница 26: ...at site 1 Pipe diameter Prepare refrigerant pipes at site Pipe joints are as shown below 2 Suction pipe Normally adjust the pipe size to the end diameter of copper pipe at the joint of condensing unit...

Страница 27: ...not connect the ground wire to a gas pipe lighting rod or telephone grounding wire If improperly grounded an electric shock or malfunction may result Never connect the grounding wire to a gas pipe bec...

Страница 28: ...e drop at 2 V Electric characteristics for 50Hz Item Unit OP UPAC015COP04E Nominal output kW 6 4 Power supply 3P 380 400 415 V 50 Hz Electric characteristics Power consumption kW 10 54 10 54 10 54 Ope...

Страница 29: ...pillary 20 Sight glass 21 Under dome temperature sensor 22 Injection inlet temperature sensor 23 Discharge pipe temperature sensor 24 Subcooling coil temperature sensor 25 Middle pressure receiver inl...

Страница 30: ...ion and maintenance contract SW6 7 Oil level error Sw6 8 Spare SW7 Data erase write SW8 7 segment display 1s SW9 7 seqment display 10s TB1 2 Terminal block Tho A Outdoor air temp sensor Tho C1 Under d...

Страница 31: ...n the manifold If the pressure drops it leaks at some places Find and repair the leak spots When it leaks check welded section and screwed section using foaming liquid Absolute pressure at measurement...

Страница 32: ...to restore before restarting the equipment If it is operated with the coil removed it could break down the unit Middle pressure side service port Oil service port Low pressure side service port High p...

Страница 33: ...akly acidic it is necessary to dry sufficiently by the vacuum drying Fig 20 Start evacuation from the low pressure side to prevent the reverse phase on the compressor Vacuum sufficiently for 2 to 3 ho...

Страница 34: ...er The vacuum pump is connected to the service port at the low pressure side only at that time In the event that the pipe is long or there is an oil sump in the evaporator the condensing unit oil reta...

Страница 35: ...ntity unit length of Lb1 pipe x Lb1 m Oil quantity unit length of Lb2 pipe x Lb2 m Oil quantity unit length of Lb3 pipe x Lb3 m Oil quantity unit length of Lb4 pipe x Lb4 m Oil quantity unit length of...

Страница 36: ...ent pipe length Piping refrigerating oil quantity cc 16 cc m 5 System design recommendations 3 Additional condensing unit oil quantity Additional condensing unit oil is calculated to be 1 140 cc from...

Страница 37: ...temperatures change widely 4 The oil become colorless and transparent 5 Since the unit inside becomes in the state of vacuum during the replenishment of condensing unit oil pay utmost attention not to...

Страница 38: ...g unit oil with the manual pump When the pressure becomes higher than the balance pressure open the valve at the oil service port and charge the condensing unit oil 4 After charging oil close the valv...

Страница 39: ...on temperature setting 5 C Evaporation temperature setting 5 C 10 2 12 2 2 Refrigerant quantity for connected show case or unit cooler Refrigerant quantity for connected show case or unit cooler Check...

Страница 40: ...System design recommendations 5 6 4 Maximum refrigerant charge quantity Confirm that the refrigerant charge quantity as calculated in the step 5 6 3 is not larger than the maximum refrigerant charge q...

Страница 41: ...gerant charge to stopped compressor Charge liquid refrigerant from the medium pressure service port of vessel unit When the unit is energized turn off the unit s power supply Turn the dip switch SW5 7...

Страница 42: ...n short circuited CNS3 Brown Compulsory oil return control input Valid when short circuited Use connectors fixed with tapes on the outer wall of the control box CNG1 Blue Gas cooler fan snow control i...

Страница 43: ...al board using M3 5 crimp terminal as shown in the sketch below Use an adequate screwdriver to tighten terminal screws If it is tightened too much it could destroy screws For the tightening torque of...

Страница 44: ...tion shipping washers are not used on the compressor Since this product does not use anti vibration shipping washers it is not necessary to remove them before operation 6 Turn on the source power supp...

Страница 45: ...the refrigerant system has been opened the system has to be flushed with dry air or nitrogen to remove moisture and a new filter dryer has to be installed If evacuation of refrigerant has to be done...

Страница 46: ...nical or handling equipment according to weight It is recommended not to open the packaging before the unit is at the final place for installation Handle the unit with care The packaging allows for th...

Страница 47: ...Compressor opened or returned unsealed Rust water or leak detection dye inside the compressor Use of a refrigerant or lubricant not approved by Danfoss Any deviation from recommended instructions pert...

Страница 48: ...eaders in our business and positioned us as distinct variable speed technology specialists Today we operate from engineering and manufacturing facilities spanning across three continents AB40854013038...

Отзывы: