5.1.2 Binary Input- and Output Objects
Object_Name
Present_Value
ID
Default name
Parameter
Bit number
Option
BI:0
Digital input Term 33
1660
0
BI:1
Digital input Term 32
1660
1
BI:2
Digital input Term 29
1660
2
BI:3
Digital input Term 27
1660
3
BI:4
Digital input Term 19
1660
4
BI:5
Digital input Term 18
1660
5
BI:6
Digital input Term 37
1660
6
BI:7
Digital input GPIO Term X30/2
1660
9
MCB 101
BI:8
Digital input GPIO Term X30/3
1660
8
MCB 101
BI:9
Digital input GPIO Term X30/4
1660
7
MCB 101
BI:10..BI:15 are reserved for P1660/x (MCB 115)
Table 5.5 Binary Inputs
ID
Object_Name
Present_Value
Default name
Parameter
Bit number
Writeable
Cmd.able
Timeout
Option
BO:0
Digital Output Term 27
590
0
x
x
x
BO:1
Digital Output Term 29
590
1
x
x
x
BO:2
GPIO Output Term X30/6
590
2
x
x
x
MCB 101
BO:3
GPIO Output Term X30/7
590
3
x
x
x
MCB 101
BO:4
Relay 1
590
4
x
x
x
BO:5
Relay 2
590
5
x
x
x
BO:6
Option B Relay 1 Output
590
6
x
x
x
MCB 105
BO:7
Option B Relay 2 Output
590
7
x
x
x
MCB 105
BO:8
Option B Relay 3 Output
590
8
x
x
x
MCB 105
BO:9..BO:39 are reserved for Output P590/x (MCB 115)
Table 5.6 Binary Outputs
BACnet Objects
VLT
®
HVAC Drive Native BACnet Operating Instructions
MG.14.C1.02 - VLT
®
is a registered Danfoss trademark
17