5 BACnet Objects
5.1.1 Analog Input- and Output Objects
Control the frequency converter from the BACnet network using 'objects'. The various types of 'objects' and their descriptions
are shown in the following tables. In the following tables all available objects are shown. The availability of objects depends on
the mounting of the B and/or C options.
ID
Object_Name
Present_Value
Default name
Parameter
Unit
Option
AI:0
Analog Input 53
1662
%
AI:1
Analog Input 54
1664
%
AI:2
Analog In X30/11
1675
%
MCB 101
AI:3
Analog In X30/12
1676
%
MCB 101
AI:4
Analog In X42/1
1830
V
MCB 109
AI:5
Analog In X42/3
1831
V
MCB 109
AI:6
Analog In X42/5
1832
V
MCB 109
Table 5.1 Analog Inputs Object Map
ID
Object_Name
Present_Value
Default name
Parameter
Unit
Writeable
Cmd.able
Timeout
Option
AO:0
Terminal 42 Output Bus
Control
653
%
x
x
x
AO:1
Pulse out #27 Bus Control
593
%
x
x
x
AO:2
Pulse out #29 Bus Control
595
%
x
x
x
AO:3
Terminal X30/8 Output Bus
Control
663
%
x
x
x
MCB 101
AO:4
Analog Output X42/7
2643
V
x
x
x
MCB 109
AO:5
Analog Output X42/9
2653
V
x
x
x
MCB 109
AO:6
Analog Output X42/11
2663
V
x
x
x
MCB 109
Table 5.2 Analog Outputs
BACnet Objects
VLT
®
HVAC Drive Native BACnet Operating Instructions
MG.14.C1.02 - VLT
®
is a registered Danfoss trademark
13
5
5