ID
Object_Name
Present_Value
Default
name
Writeable
EEPROM
Parameter Unit
Writeable
Cmd.able
Timeout
Option
AV:0
Reserved for VFD profile
AV:1
Input
Reference 1 x
x
Note 1
%
x
x
x
AV:2
Input
Reference 2
Note 1
%
x
x
x
AV:3
Output
Speed
x
x
Note 2
%
AV:4
PID
Feedback
Note 3
%
AV:5
Motor
Current
x
x
1614
Amps
AV:6
Power
x
x
1610
kW
AV:7
Reserved for VFD profile
AV:8
AV:9
AV:10
AV:11
AV:12
AV:13
AV:14
AV:15
Motor
Thermal
1618
%
AV:16
Reserved for VFD profile
AV:17
AV:18
AV:19
AV:20
AV:21
Operating
Hours
1500
Hours
AV:22
Running
Hours
1501
Hours
AV:23
kWh Counter
1502
kWh
AV:24
Motor
Voltage
1612
V
AV:25
Frequency
1613
Hz
AV:26
Torque
1622
%
AV:27
DC Link
Voltage
1630
V
AV:28
Heatsink
Temp.
1634
Deg
AV:29
Inverter
Thermal
1635
%
AV:30
Setpoint 1
2021
%
x
AV:31
Bus
Feedback 1
894
%
x
AV:32
Reserved for P, I, D
AV:33
AV:34
AV:35
Setpoint 2
2022
%
x
AV:36
Bus
Feedback 2
895
%
x
BACnet Objects
VLT
®
HVAC Drive Native BACnet Operating Instructions
14
MG.14.C1.02 - VLT
®
is a registered Danfoss trademark
5