Electrical data, connections and wiring
MLZ/MLZ116 compressors are available only in code 4.
Motor voltage
The compressor terminal box according to IEC529 is IP54 for all models when correctly sized IP54 rated
cable glands are used.
First numeral, level of protection against contact and foreign objects
5
- Dust protected
Second numeral, level of protection against water
4
- Protection against water splashing
The temperature inside the terminal box may not
exceed 70°C. Consequently, if the compressor
is installed in an enclosure, precautions must
be taken to avoid the temperature around the
compressor and in the terminal box from rising
too much. The installation of ventilation on the
enclosure panels may be necessary. If not, the
electronic protection module may not operate
properly. Any compressor damage related to this
will not be covered by the Danfoss warranty. In
the same manner, cables must be selected in a
way to ensure that terminal box temperature
does not exceed 70°C.
IP rating
Terminal box
temperature
Electrical power is connected to the compressor
terminals by Ø 4.8 mm (3/16”) screws.
The maximum tightening torque is 3 Nm. Use a
1/4’’ ring terminal on the power leads.
Wiring connections
Motor voltage
code 4
Nominal voltage
50 Hz
380-415 - 3ph
Voltage range
50 Hz
340-457 V
The terminal box is provided with 2 triple
knockouts and 1 single knockout for power
supply and 4 double knockouts for the safety
control circuit.
The 3 power supply knockouts accommodate the
following diameters:
• Ø 50.8 mm (UL 1"1/2 conduit) and Ø 43.7
mm (UL 1"1/4 conduit) and Ø 34.5 mm (UL 1"
conduit)
• Ø 40.5 mm (ISO40) and Ø 32.2 mm (ISO32) and
Ø 25.5 mm (ISO25)
• Ø 25.5 mm (ISO25)
The 4 others knockouts are as follows:
• Ø 22.5 mm (PG16) (UL 1/2") and Ø 16.5 mm
(ISO16) (x2)
• 20.7 mm (ISO20 or PG13.5) (x2)
MLM/MLZ116
Black
Blue
Brown
Faston 1/4" tabs
Power supply
Sump heater
Module
power supply
M1-M2
control circuit
The motor protection module comes preinstalled
within the terminal box. Phase sequence
protection connections and thermistor
connections are pre-wired. The module must be
connected to a power supply of the appropriate
voltage. The module terminals are 6.3 mm size
Faston type.
L N S1 S2 M1 M2
L1 L2 L3
Black Blue Brown
Phase sequence input
Internal control contact
Safety
circuit
Thermistor
connection
Module power
L N
M1 M2
Note: please make sure M1/M2 is connected to OEM controller
and L/N is connected to outside power supply, otherwise, there
will be no motor protection.
12
FRCC.PC.035.A5.02
Application Guidelines
Single compressors