6.5. Fault management
Any faults detected by the system are divided into 3 categories based on their significance and impact:
Fault category 0
Following debugging, it then automatically returns to normal operation and the outputs are enabled again in
accordance with the current system state.
In order to detect any sporadic faults, the fault code readout remains enabled until it is reset by pressing Enter.
Fault category 1
Following debugging and resetting by pressing Enter, it then returns to normal operation.
Fault category 2
In order to delete the saved faults once they have been debugged, the module must be disconnected from the
operating voltage for approx. 1 s. If a fault occurs which cannot be debugged by the user, then the module must be
sent back to the manufacturer in order for it to be repaired.
Irrespective of the category, faults may only be reset if the drive is at a standstill.
6.6. Overview of faults
Category Number
Fault cause
0
1
SLS speed exceeded
0
2
SMS speed exceeded
0
3
Protective device open despite interlock in place
1
4…6
Crossover between input channels
1
7
Speed difference between channel 1 and channel 2 greater than 20%
1
8
Standstill at Pr_x and >4x zero speed at Pr_y
1
9
Pr_1 and Pr_2 disabled at standstill
2
10…11
Ramp output shorted or defective
2
12…13
STO_O output shorted or defective
2
14…15
ExC shorted or defective
2
16…17
SSO output shorted or defective
2
18
Outputs cannot be destaged or fed by 24V
2
19
Module temperature > 85°C
1
20
Contactor (auxiliary contact) does not open in the event ExC output is enabled
1
21
DOOR input disabled and 24 V at Door_1 or Door_2 terminals
1
22
SLS input disabled and 24 V at SLS_1 or SLS_2 terminals
1
23
P104 setting "single channel", but 24 V at SS1_1, SLS_1 or DOOR_1
1
24
P201 setting "single channel", but 24 V or pulses at Pr_1
2
25
Enter key permanently pressed
1
26
P106 setting "emergency", but 24 V at FBC terminal
2
27
Operating voltage < +21 V DC or > +28 VDC
1
28
SLS and/or DOOR actively parameterised without Motor Feedback (P201=0
1
29
Wire break in 2-wire initiator (P201=1-2dr)
1
30
No initiator pulses for P201=1-EnA after "start-up delay" (P204) has elapsed
30…43
Reserve
2
44…55
Internal faults
Table 20: Overview of faults