The following messages are shown in online mode in the VLT® Motion Control Tool MCT 10:
•
Status of the safety option.
•
Internal and external errors and the corresponding troubleshooting tips.
To configure the LCP to show the safety option-specific information, use the parameters in
parameter group 0-2* LCP Display
.
Parameter 0-20 Display Line 1.1 Small
to
parameter 0-22 Display Line 1.3 Small
have the following options:
•
Parameter 42-82 Safe Control Word
•
Parameter 42-83 Safe Status Word
•
Parameter 42-85 Active Safe Func
Parameter 0-23 Display Line 2 Large
and
parameter 0-24 Display Line 3 Large
have the following options:
•
Parameter 42-82 Safe Control Word
•
Parameter 42-83 Safe Status Word
•
Parameter 42-86 Safe Option Info
9.4.1 LCP Status Messages
This section describes the LCP status messages related to the VLT® Safety Option MCB 152. The set of messages differs depending on
whether or not a safe fieldbus is enabled. Messages, which are shown regardless of the safe fieldbus state, are shown in
.
Messages, which are only shown when the safe fieldbus is disabled, are shown in
Table 23: LCP Messages
LCP Message
Description
Status
0.0 Hz
50.0 %
!1(1)
0 RPM 0.00 A 0.00KW
!Safe Stop [W68]
Auto Remote Coast
e3
0b
e0
90
.1
1
The safety function was activated via a digital input or via PROFIsafe.
Status
Safe Func. Pending
SO RESET required!
!1(1)
0 RPM 0.00 A 0.00KW
!Safe Stop [W68]
Auto Remote SO Req. RESET
e3
0b
e0
91
.1
1
The source that triggered the safety condition has ceased, but the safety option is waiting for the
reset signal to continue normal operation. The LCP shows this message only if the manual restart
behavior is selected for the digital input. The LCP does not show this message when the PROFI-
safe control word activates the safety function, since the PROFIsafe configuration uses automatic
restart behavior.
Status
SO General Reset
SO RESET required!
!1(1)
0 RPM 0.00 A 0.00KW
!Safe Stop [W68]
Auto Remote SO Req. RESET
e3
0b
e0
92
.1
1
The LCP shows this message after resetting the safety option with VLT® Motion Control Tool MCT
10. After the reset, the safety option is set to blank initial state. For more information, see
.
Maintenance, Diagnostics, and
Troubleshooting
Installation Guide | VLT®Safety Option MCB 152
AN327351953089en-000101 / 130R0578| 69