Range
Function
0.01 s*
[0.01–
600.00 s]
Enter the delay of the relay cutout time. See
.
Selected
event
Relay
output
On delay
P 5-41
Off delay
P 5-42
e3
0b
a1
72
.1
1
If the selected event condition changes before the on- or off delay timer expires, the relay output is unaffec-
ted.
4.3 6-** Analog Outputs
4.3.1 6-7* Analog Output 3 MCB 113
Parameters for configuring the scaling and limits for analog output, terminals X45/1, and X45/2. Analog outputs are current outputs:
0/4–20 mA. Resolution of analog output is 11 bit.
Table 32: Parameter 6-70 Terminal X45/1 Output
Option
Function
Select the function of terminal X45/1 as an analog current output.
[0]
No operation
When no signal on the analog output is present.
[52]
MCO 305 0–20 mA
[53]
MCO 305 4–20 mA
[100]
Output frequency
0–20 mA
0 Hz = 0 mA; 100 Hz = 20 mA
[101]
Reference 0–
20 mA
Parameter 3-00 Reference Range [0] Min.–Max.
0% = 0 mA; 100% = 20 mA.
Parameter 3-00 Reference
Range [1] -Max.–+Max.
-100% = 0 mA; 0% = 10 mA; +100% = 20 mA.
[102]
Feedback
[103]
Motor current 0–
20 mA
The value is taken from
parameter 16-37 Inv. Max. Current
. The inverter maximum current (160% cur-
rent) is equal to 20 mA. Example: Inverter normal current (11 kW) = 24 A. 160% = 38.4 A. Motor nor-
mal current = 22 A, readout 11.46 mA.
20 mA × 22 �
38 . 4 �
= 11 . 46 mA
If the normal motor current is equal to 20 mA, the output setting of
parameter 6-52 Terminal 42 Output
Max Scale
is:
�
VLT, Max
× 100
�
Motor, Norm
= 38 . 4 × 100
22
= 175 %
[104]
Torque rel to lim
0–20 mA
The torque setting is related to the setting in
parameter 4-16 Torque Limit Motor Mode
.
Parameter Setup
Operating Guide | VLT® Extended Relay Card MCB 113
AQ322553864968en-000101 / 130R0353| 43
Danfoss A/S © 2020.01