4.2.4 Parameter Group 5-4* Relays
Table 27: Parameter 5-40 Function Relay - 1
Option
Function
Relay 1 [0], relay 2 [1]
(1)
.
VLT® Extended Relay MCB 113: X47/Relay 3 [2], X47/Relay 4 [3], X47/Relay 5 [4], X47/Relay 6 [5].
VLT® Relay Card MCB 105: Relay 7 [6], relay 8 [7], relay 9 [8].
[0]
No operation
Default setting for all digital and relay outputs.
[1]
Control ready
The control card is ready, for example: Feedback from a drive where the control is supplied by an 24
V external supply (VLT® 24 V DC Supply MCB 107) and the main power to drive is not detected.
[2]
Drive ready
The drive is ready to operate. Mains and control supplies are OK.
[3]
Drive rdy/rem ctrl
The drive is ready for operation and is in auto-on mode.
[4]
Enable/no warning
Ready for operation. No start or stop commands have been applied (start/disable). No warnings are
active.
[5]
Running
The motor is running, and shaft torque is present.
[6]
Running/no warn-
ing
Output speed is higher than the speed set in
parameter 1-81 Min Speed for Function at Stop [RPM]
. The
motor runs and there are no warnings.
[7]
Run in range/no
warn
The motor runs at reference speed. No warnings.
[8]
Run on ref/no
warn
The motor runs at reference speed. No warnings.
[9]
Alarm
An alarm activates the output. No warnings.
[10]
Alarm or warning
An alarm or a warning activates the output.
[11]
At torque limit
The torque limit set in
parameter 4-16 Torque Limit Motor Mode
or
parameter 4-17 Torque Limit Genera-
tor Mode
has been exceeded.
[12]
Out of current
range
The motor current is outside the range set in
parameter 4-18 Current Limit
.
[13]
Below current, low
The motor current is lower than set in
parameter 4-50 Warning Current Low
.
[14]
Above current,
high
The motor current is higher than set in
parameter 4-51 Warning Current High
.
[15]
Out of speed
range
Output speed/frequency is outside the frequency range set in
parameter 4-52 Warning Speed Low
and
parameter 4-53 Warning Speed High
.
[16]
Below speed, low
Output speed is lower than the setting in
parameter 4-52 Warning Speed Low
.
[17]
Above speed, high
Output speed is higher than the setting in
parameter 4-53 Warning Speed High
.
[18]
Out of feedb.
range
Feedback is outside the range set in
parameter 4-56 Warning Feedback Low
and
parameter 4-57 Warn-
ing Feedback High
.
[19]
Below feedback,
low
Feedback is below the limit set in
parameter 4-56 Warning Feedback Low
.
[20]
Above feedback,
high
Feedback is above the limit set in
parameter 4-57 Warning Feedback High
.
Parameter Setup
Operating Guide | VLT® Extended Relay Card MCB 113
AQ322553864968en-000101 / 130R0353
38 | Danfoss A/S © 2020.01