6 Troubleshooting
6.1 Step-by-step Troubleshooting
Check: LEDs
The option contains two LEDs to indicate the state of the device and the network. During normal operation the MS and at
least one NS LED shows a constant green light.
State
LED
Description
No power
Off
The device is un-powered
Device operational
Green:
Solid green
The device is operational
Standby
Green:
Flashing green
The device needs commissioning
Minor fault
Red:
Flashing red
The device has detected a recoverable fault
Major fault
Red:
Solid red
The device has detected an un-recoverable
fault
Self test
Red:
Flashing red/
green
The Modbus TCP option is in self-test mode
Green:
No IP address
Yellow
Steady yellow
No IP address configured or obtained
Wink
Yellow
Flashing yellow
Flash for 20 s
Table 6.1 MS: Module Status
State
LED
Description
No IP-address (no power)
Off
No link present (or is un-powered)
Connected
Green:
Solid green
Link present; but nor winked and no ACD
Duplicate IP
Red:
Solid red
The IP-address assigned to the device is
already in use
Self test
Red:
Flashing red/
green
The Modbus TCP option is in self-test mode
Green
Device has been winked Yellow
Flashing yellow
Flash for 20 s
Link present at 10 Mbps Yellow
Steady yellow
Link present; but nor winked and no ACD
Table 6.2 NS1+NS2: Network Status (one per port)
Check: Link Status
The status of the Ethernet link cannot be directly identified
with the LEDs.
Use
12-10 Link Status
, to verify presents of the link.
Use
, to verify that the link is steady
present.
The parameter shows the duration of the present link, and
preset to 00:00:00:00 if the link is broken.
Check: Cabling
In rare cases of cabling mis-configuration, the option might
show the presents of a link, but no communication is
running. Exchange the cable in doubt.
Check: IP Address
Verify that the option has a valid IP address (refer to
) in
12-01 IP Address
. If the option has
identified a duplicate IP Address NS LEDs lights steady red.
If the option is set up for BOOTP or DHCP, verify that a
BOOTP or DHCP server is connected in
12-04 DHCP Server
.
If no server is connected, the parameter shows:
000.000.000.000.
6.2 Alarm Word and Warning Word
Alarm word and warning word are shown in the display in
Hex format. If there is more than one warning or alarm, a
sum of all warnings or alarms is shown. Warning word and
alarm word are displayed in
16-90 Alarm Word
to 16-95.
For more information on the individual alarms and
warnings, refer to the product relevant Design Guides.
Troubleshooting
MCA 122 Modbus TCP
MG90P202 - VLT
®
is a protected Danfoss trademark
37
6
6