4.4 Danfoss FC Control Profile
→
Illustration 4.2
=Frequency Converter
profile
Bit
Bit value=0
Bit value=1
00
Reference value
External selection LSB
01
Reference value
External selection MSB
02
DC brake
Ramp
03
Coasting
No coasting
04
Quick stop
Ramp
05
Hold output frequency
Use ramp
06
Ramp stop
Start
07
No function
Reset
08
No function
Jog
09
Ramp 1
Ramp 2
10
Data invalid
Data valid
11
No function
Relay 01 active
12
No function
Relay 04 active
13
Parameter set-up
Selection LSB
14
Parameter set-up
Selection MSB
15
No function
Reverse
Table 4.7 Control Word Bits
Explanation of control bits
Bits 00/01
Bits 00 and 01 are used to choose between the four
reference values, which are pre-programmed in
3-10 Preset
Reference
according to
Programmed
ref. value
Parameter
Bit 01
Bit 00
1
3-10 [0]
0
0
2
3-10 [1]
0
1
3
3-10 [2]
1
0
4
3-10 [3]
1
1
Table 4.8 Reference Values
NOTICE
In
8-56 Preset Reference Select
select a selection is made to
define how Bit 00/01 gates with the corresponding
function on the digital inputs.
Bit 02, DC brake
Bit 02=‘0’ leads to DC braking and stop. Braking current
and duration are set in
2-01 DC Brake Current
and
2-02 DC
Braking Time
. Bit 02=‘1’ leads to ramping,
3-41 Ramp 1
Ramp Up Time
Bit 03, Coasting
Bit 03=‘0’ causes the frequency converter to immediately
release the motor (the output transistors are "shut off"), so
that it coasts to a standstill.
Bit 03=‘1’ enables the frequency converter to start the
motor if the other starting conditions have been fulfilled.
NOTICE
In
8-50 Coasting Select
a selection is made to define how
Bit 03 gates with the corresponding function on a digital
input.
Bit 04, Quick stop
Bit 04=‘0’ causes a stop, in which the motor speed is
ramped down to stop via
3-81 Quick Stop Ramp Time
.
Bit 05, Hold output frequency
Bit 05=‘0’ causes the present output frequency (in Hz) to
freeze. The frozen output frequency can then be changed
only with the digital inputs (
5-10 Terminal 18 Digital Input
to
5-15 Terminal 33 Digital Input
) programmed to
Speed up
and
Speed down
.
NOTICE
If Freeze output is active, the frequency converter can only
be stopped by the following:
•
Bit 03 Coasting stop
•
Bit 02 DC braking
•
Digital input (
5-10 Terminal 18 Digital Input
to
5-15 Terminal 33 Digital Input
) programmed to
DC
braking
,
Coasting stop
or
Reset and coasting stop
Bit 06, Ramp stop/start
Bit 06=‘0’ causes a stop, in which the motor speed is
ramped down to stop via the selected
ramp down
parameter.
Bit 06=‘1’ permits the frequency converter to start the
motor, if the other starting conditions have been fulfilled.
NOTICE
In
8-53 Start Select
Start select a selection is made to define
how Bit 06 Ramp stop/start gates with the corresponding
function on a digital input.
Bit 07, Reset
Bit 07=‘0’ no reset.
Bit 07=‘1’ resets a trip. Reset is activated on the leading
edge of the signal, that is, when changing from logic ‘0’ to
logic ‘1’.
Bit 08, Jog
Bit 08=‘1’ causes the output frequency to be determined
by
3-19 Jog Speed [RPM]
.
How to Control
MCA 122 Modbus TCP
MG90P202 - VLT
®
is a protected Danfoss trademark
23
4
4
Содержание MCA 122 Modbus TCP
Страница 1: ...MAKING MODERN LIVING POSSIBLE Operating Instructions MCA 122 Modbus TCP ...
Страница 2: ......
Страница 13: ...Illustration 2 7 How to Install MCA 122 Modbus TCP MG90P202 VLT is a protected Danfoss trademark 9 2 2 ...
Страница 46: ...www danfoss com drives MG90P202 130R0446 MG90P202 Rev 2013 05 02 ...