5.2.3 12-2* Process Data
12-21 Process Data Config Write
Range:
Function:
[[0 - 9] PCD read 0 - 9] Configuration of readable process
data.
In POWERLINK this parameter is read only. Same applies
for
12-22 Process Data Config Read
,
12-23 Process Data
Config Write Size
and
12-24 Process Data Config Read Size
.
12-22 Process Data Config Read
Range:
Function:
[[0 - 9] PCD read 0 - 9] Configuration of readable process
data.
12-27 Primary Master
Option: Function:
This parameter control allows fast swapping of masters.
If this parameter is set 0.0.0.0, the first masters that
access the frequency converter locks the interface for
other masters.
If the communication is lost, the frequency converter
will hold the connection for 30 s before a second
master can take control.
By setting
[0] IP address of first Master
and setting
[1] IP
address of second Master
, only these two masters can
control the frequency converter and the second master
does not have to wait 30 s to take control.
Only one master may control the frequency converter
at any time, otherwise the frequency converter might
malfunction.
[0]
*
IP address of first Master.
[1]
IP address of second Master.
12-28 Store Data Values
Option:
Function:
This parameter activates a function that stores
all parameter values in the non-volatile
memory (EEPROM) thus retaining parameter
values at power-down.
The parameter returns to “Off”.
[0]
*
Off
The store function is inactive.
[1]
Store All
set-ups
All parameter values are stored in the non-
volatile memory, in all 5 set-ups.
12-29 Store Always
Option: Function:
Activates function that always stores received
parameter data in non-volatile memory (EEPROM).
[0]
*
Off
[1]
On
5.2.4 Modbus TCP
12-40 Status Parameter
Range:
Function:
Read only. Displays the Modbus TCP- specific 16-bit
Status word.
0
*
[0 - 0 ]
Bit
Description
Bit=[0]
Bit=[1]
0
Link Status
port 1
Disconnected Connected
1
Link Status
port 2
Disconnected Connected
2
Link speed
0/10 Mbps
100 Mbps
3
Link Duplex
Half
Full
4
Port 502
communi-
cation
No
Yes
5
UNUSED
-
-
6
Valid IP
address
No
Yes
7
Modbus
timeout (30 s)
No
Yes
8
Duplicate IP
No
Yes
9
Register 7
error
No
Yes
10
FTP server
Disabled
Enabled
11
HTTP server
Disabled
Enabled
12
SMTP service
Disabled
Enabled
13
Cable
diagnosis
Disabled
Enabled
14
Auto
crossover
Disabled
Enabled
15
IGMP
snooping
Disabled
Enabled
Table 5.1 Bit Descriptions
12-41 Slave Message Count
Range:
Function:
Read only.
Displays the number of Modbus messages received
and processed by the slave.
0
*
[0 - 0 ]
12-42 Slave Exception Message Count
Range:
Function:
Read only.
Displays the number of Modbus messages for
which the slave has sent an exception response.
0
*
[0 - 0 ]
Parameters
MCA 122 Modbus TCP
32
MG90P202 - VLT
®
is a protected Danfoss trademark
5
5