SOUND AND VIBRATION MANAGEMENT

Compressor

model

Sound power level*

at 50 hz dB(A)

Sound power level*

at 60 Hz dB(A)

Acoustic

hood

code no.

without hood

with hood

without hood

with hood

NTZ048

72

65

75

68

7755001

NTZ068

70

64

74

68

NTZ096

78

71

82

74

7755002

NTZ108

76

69

80

75

NTZ136

77

71

80

75

NTZ215

84

78

88

81

7755003

NTZ271

84

78

88

81

(*)  Operating conditions: R404A, Evap. temp.: -35°C, Cond. temp.: 40°C, 400 V / 50Hz

Sound produced by a compressor is 
transmitted in every direction by the 
ambient air, the mounting feet, the 
pipework and the refrigerant in the 
pipework. The easiest way to reduce 
the sound transmitted through ambi-
ent air is to fi t an acoustic hood acces-
sory. Because Maneurop® NTZ com-

pressors are 100% suction gas cooled 
and require no external cooling they 
can be insulated or enclosed in a sound 
proofi ng material lined compartment.
Sound transmitted by mounting feet, 
pipework and refrigerant should be 
treated the same way as vibration (see 
next section).

Sound

Compressors in operation are one of 
the sources of sound and vibration in 

a refrigeration system. Both phenom-
ena are closely related.

Vibration

The mounting grommets delivered 
with the compressor should always 
be used. They will largely attenuate 
the compressor vibration transmit-
ted to the base frame. These rubber 
grommets have been selected and 
calculated in accordance with the vi-
bration frequencies that are typical for 
the compressor. For that reason other 
grommet types or brands shall not be 
used.
The base on which the compressor is 
mounted should be suffi

  ciently  rigid 

and of adequate mass to ensure the 
full eff ectiveness of the mounting 

grommets. The compressor should 
never be rigidly mounted to the base 
frame otherwise high vibration trans-
mission would occur and the service 
life reduced. Suction and discharge 
lines must have adequate fl exibility in 
3 planes. Eventually vibration absorb-
ers may be required.
Vibration is also transmitted by the 
refrigerant gas. Maneurop® NTZ com-
pressors have built-in muffl

  ers to re-

duce pulsation. To further reduce vi-
bration an extra discharge line muffl

  er 

can be installed.

Содержание Maneurop NTZ Series

Страница 1: ...MAKING MODERN LIVING POSSIBLE SELECTION APPLICATION GUIDELINES Maneurop reciprocating compressors NTZ R404A R507A...

Страница 2: ......

Страница 3: ...and relays 11 Single phase motor protection and suggested wiring diagram 11 Three phase electrical characteristics 13 Three phase motor protection and suggested wiring diagram 13 REFRIGERANTS AND LUB...

Страница 4: ...TZ range The NTZ series is engineered as a true low temperature compressor opti mised at 35 C with an extended evaporating temperature range from 45 C up to 10 C The compressors can be operated at a r...

Страница 5: ...5 120F0171 NTZ215 120F0031 120F0006 120F0172 NTZ271 120F0032 120F0007 120F0173 NTZ430 120F0024 NTZ542 120F0025 Compressor model Code no Motor voltage code 1 3 4 5 9 Nominal voltage 208 230 1 60 200 23...

Страница 6: ...nominal ratings Operating envelope R404A R507A Motor code 4 operating conditions R404A Evap temp 35 C Cond temp 40 C RGT 20 C SC 0K For full NTZ data details and capacity tables refer to Online Datas...

Страница 7: ...ck 1 68 82 109 118 35 33 68 Suction 147 Discharge 142 159 17 17 123 39 Threaded oil sight glass 141 224 68 HM8 40 23 15 Silent block 7 1 cylinder OUTLINE DRAWINGS Rotolock connections size Pipe sizing...

Страница 8: ...1 8 38 82 74 68 265 Suction rotolock 1 3 4 Discharge rotolock 1 1 4 Oil equalisation 3 8 HM8 40 23 15 Silent block 8 OUTLINE DRAWINGS 2 cylinders Rotolock connections size Pipe sizing Rotolock valve S...

Страница 9: ...ting hole for PTC crankcase heater Suction rotolock 1 3 4 Discharge rotolock 1 1 4 Oil equalisation 3 8 VE version only Rotolock connections size Pipe sizing Rotolock valve Suction Discharge Suction D...

Страница 10: ...ng 54 with cable gland Screw 10 32 UNF x 9 5 Earth M4 12 Knock out 29 mm 29 mm Models NTZ048 NTZ068 NTZ096 NTZ108 NTZ136 except NTZ136 1 Spade connectors 1 4 AMP AWE Earth M4 12 Knock out 21 mm 21 mm...

Страница 11: ...internally protected by a temperature current sensing bimetallic protector which senses the main and start wind ing current as well as motor winding temperature If the motor were to be overloaded and...

Страница 12: ...capacitors B Start capacitor C Common S Start winding auxiliary R Run winding main IOL Motor protector A C Run capacitors B Start capacitor C Common S Start winding auxiliary R Run winding main Capac...

Страница 13: ...t out It might take up to several hours to reset and restart the compressor FU Fuses MS Main switch C1 Compressor contactor TH Thermostat EC External controls COMP Compressor PTC Crankcase heater IOL...

Страница 14: ...th pump down cycle Control device TH Optional short cycle timer 3 min 5 pts 180 s Control relay KA Liquid Solenoid valve LLSV Compressor contactor KM Safety lock out relay KS Pump down control L P swi...

Страница 15: ...ase For most other aspects howev er this small glide may be neglected R507Aisanazeotropicmixturewithout temperature glide R407A and R407B have different thermodynamic properties than R404A and R507A E...

Страница 16: ...t of oil circulating through the system is small it will contribute to good system operation and improved heat transfer efficiency Lubricant getting trapped in the evaporator or suction lines will aff...

Страница 17: ...eparator is recom mended Also refer to the section Oil charge and oil level Filter driers For new installations with NTZ com pressors Danfoss recommends using the Danfoss DML 100 molecular sieve solid...

Страница 18: ...ondensor may be installed indoor When the compressor is located in a low ambient temperature environ ment increased refrigerant migration will occur during shut down periods For such conditions an ext...

Страница 19: ...ute runtime after each start and a 3 minute idle time between each stop and start Only during the pump down cycle may the compressor run for much shorter intervals Vavg Mean voltage of phases 1 2 and...

Страница 20: ...re frigerant charge can condensate in the compressor crankcase A large amount will dissolve in the compressor oil un til the oil is completely saturated with refrigerant When the compressor is started...

Страница 21: ...pti mal size Crankcase heater A crankcase heater protects against the off cycle migration of refrigerant and proves effective if oil temperature is maintained 10 K above the saturat ed LP temperature...

Страница 22: ...next section Sound Compressors in operation are one of the sources of sound and vibration in a refrigeration system Both phenom ena are closely related Vibration The mounting grommets delivered with...

Страница 23: ...s and using tools chargingsystems tubes vacuum pumps etc dedicated for R404A and R507A Compressor handling mounting and connection Component Torque Nm Min Max Rotolock suction valve NTZ048 NTZ068 80 1...

Страница 24: ...rge can escape via the discharge connection and the risk of an oil mist blow out via the suction connection will be minimal Whenever possible the compressor must be the last component to be integrated...

Страница 25: ...capacity appropriate for the sys tem volume It is recommended to use connection lines with a large diameter and to connect these lines to the serv ice valves and not to the schrader con nection so as...

Страница 26: ...noted while the expansion valve setting is correct the suction line insulation between evaporator and compressor should be checked and eventually replaced by a higher qual ity insulation z A too high...

Страница 27: ......

Страница 28: ...reduce costs streamline processes and achieve your business goals Danfoss A S www danfoss com FRCC PC 002 A2 02 Replace FRCC PC 002 A1 02 May 2005 Produced by Danfoss CC DSS 02 2007 The Danfoss produc...

Отзывы: