manualshive.com logo in svg
background image

25

INSTALLATION AND SERVICE

Leak detection

Whenever possible the compressor 
must be kept isolated from the sys-
tem during leak detection by closing 
the suction and discharge valves  Use 
a mixture of nitrogen and the fi nal re-
frigerant (eg. R404A or R507) and use 
a leak detector for the applied refrig-
erant. A spectrometric detection sys-
tem using helium can also be applied. 
Note that leak detection with refriger-
ant may not be allowed in some coun-
tries. Do not use other gasses such as 

oxygen, dry air or acetylene as these 
gasses can form an infl ammable mix-
ture with the compressor oil. Never 
use CFC or HCFC refrigerants for leak 
detection of HFC systems. Leak detect-
ing additives shall not be used as they 
may aff ect the lubricant properties. 
Warranty may be voided if leak detec-
tion additives have been used.
Eventual leaks shall be repaired 
respecting the instructions written 
above.

Vacuum pump-down and 
dehydration procedure

Moisture obstructs proper operation 
of the compressor and the rest of the 
refrigeration system. Air and moisture 
reduce service life, increase condens-
ing pressure and cause excessively 
high discharge temperatures, which 
are capable of destroying the lubri-
cating properties of the oil. Air and 
moisture also increase the risk of acid 
formation, thus giving rise to copper 
plating. All these phenomena can ul-
timately induce mechanical and elec-
trical compressor failure. To eliminate 
these risks, it is recommended to per-
form the following vacuum pull-down 
procedure:

1

. To the extent possible (i.e. if valves 

are present), the compressor must be 
kept isolated from the system.

2

. After leak detection, the system 

must be pulled-down under a vacuum 
of 500 microns (0.67 mbar). A two-
stage vacuum pump shall be used 
with a capacity appropriate for the sys-
tem volume. It is recommended to use 
connection lines with a large diameter 
and to connect these lines to the serv-
ice valves and not to the schrader con-
nection, so as to avoid excessive pres-
sure losses.

3

. Once the vacuum level of 500 mi-

crons is reached, the system must be 
isolated from the vacuum pump. Wait 
30 minutes during which time the sys-
tem pressure should not rise. When 

the pressure rapidly increases, the sys-
tem is not leak tight. Bring the system 
pressure up to atmospheric pressure 
with dry nitrogen or another suitable 
inert gas in order to reform a new leak 
detection. After repairing all leaks the 
vacuum pull-down procedure should 
be restarted from Step 1. When the 
pressure slowly increases, this indi-
cates the presence of moisture. In this 
case Steps 2 and 3 should be repeat-
ed.

4

. Connect the compressor to the sys-

tem by means of opening the valves. 
Repeat Steps 2 and 3.

5

. Break the vacuum with either nitro-

gen or the ultimate refrigerant.

6

. Repeat Steps 2 and 3 on the total 

system.
Upon commissioning, the system 
moisture content may be as high as 
100 ppm. During compressor opera-
tion, the fi lter drier must reduce this 
content to a level of 20 to 50 ppm.

Warning

Do not use a megohmmeter or apply 
power to the compressor while it is 
under vacuum as this may cause mo-
tor winding damage, and never run 
the compressor under vacuum as this 
may cause the compressor motor to 
burnout.
Refer to News bulletin "Vacuum pump 
down and dehydration procedure" for 
more complete information.

Start-up

Before initial start-up or after a 
prolonged shut-down period, energise 
the crankcase heater 12 hours prior 
to start-up. If the crankcase heater 
cannot be energised long enough 
before start-up, the compressor shall 

be heated in another way (for example 
with an electric heater or fl ood light) 
to boil off  refrigerant from the oil. This 
is particulary important when ambient 
temperature is low at commissioning.

Содержание Maneurop NTZ Series

Страница 1: ...MAKING MODERN LIVING POSSIBLE SELECTION APPLICATION GUIDELINES Maneurop reciprocating compressors NTZ R404A R507A...

Страница 2: ......

Страница 3: ...and relays 11 Single phase motor protection and suggested wiring diagram 11 Three phase electrical characteristics 13 Three phase motor protection and suggested wiring diagram 13 REFRIGERANTS AND LUB...

Страница 4: ...TZ range The NTZ series is engineered as a true low temperature compressor opti mised at 35 C with an extended evaporating temperature range from 45 C up to 10 C The compressors can be operated at a r...

Страница 5: ...5 120F0171 NTZ215 120F0031 120F0006 120F0172 NTZ271 120F0032 120F0007 120F0173 NTZ430 120F0024 NTZ542 120F0025 Compressor model Code no Motor voltage code 1 3 4 5 9 Nominal voltage 208 230 1 60 200 23...

Страница 6: ...nominal ratings Operating envelope R404A R507A Motor code 4 operating conditions R404A Evap temp 35 C Cond temp 40 C RGT 20 C SC 0K For full NTZ data details and capacity tables refer to Online Datas...

Страница 7: ...ck 1 68 82 109 118 35 33 68 Suction 147 Discharge 142 159 17 17 123 39 Threaded oil sight glass 141 224 68 HM8 40 23 15 Silent block 7 1 cylinder OUTLINE DRAWINGS Rotolock connections size Pipe sizing...

Страница 8: ...1 8 38 82 74 68 265 Suction rotolock 1 3 4 Discharge rotolock 1 1 4 Oil equalisation 3 8 HM8 40 23 15 Silent block 8 OUTLINE DRAWINGS 2 cylinders Rotolock connections size Pipe sizing Rotolock valve S...

Страница 9: ...ting hole for PTC crankcase heater Suction rotolock 1 3 4 Discharge rotolock 1 1 4 Oil equalisation 3 8 VE version only Rotolock connections size Pipe sizing Rotolock valve Suction Discharge Suction D...

Страница 10: ...ng 54 with cable gland Screw 10 32 UNF x 9 5 Earth M4 12 Knock out 29 mm 29 mm Models NTZ048 NTZ068 NTZ096 NTZ108 NTZ136 except NTZ136 1 Spade connectors 1 4 AMP AWE Earth M4 12 Knock out 21 mm 21 mm...

Страница 11: ...internally protected by a temperature current sensing bimetallic protector which senses the main and start wind ing current as well as motor winding temperature If the motor were to be overloaded and...

Страница 12: ...capacitors B Start capacitor C Common S Start winding auxiliary R Run winding main IOL Motor protector A C Run capacitors B Start capacitor C Common S Start winding auxiliary R Run winding main Capac...

Страница 13: ...t out It might take up to several hours to reset and restart the compressor FU Fuses MS Main switch C1 Compressor contactor TH Thermostat EC External controls COMP Compressor PTC Crankcase heater IOL...

Страница 14: ...th pump down cycle Control device TH Optional short cycle timer 3 min 5 pts 180 s Control relay KA Liquid Solenoid valve LLSV Compressor contactor KM Safety lock out relay KS Pump down control L P swi...

Страница 15: ...ase For most other aspects howev er this small glide may be neglected R507Aisanazeotropicmixturewithout temperature glide R407A and R407B have different thermodynamic properties than R404A and R507A E...

Страница 16: ...t of oil circulating through the system is small it will contribute to good system operation and improved heat transfer efficiency Lubricant getting trapped in the evaporator or suction lines will aff...

Страница 17: ...eparator is recom mended Also refer to the section Oil charge and oil level Filter driers For new installations with NTZ com pressors Danfoss recommends using the Danfoss DML 100 molecular sieve solid...

Страница 18: ...ondensor may be installed indoor When the compressor is located in a low ambient temperature environ ment increased refrigerant migration will occur during shut down periods For such conditions an ext...

Страница 19: ...ute runtime after each start and a 3 minute idle time between each stop and start Only during the pump down cycle may the compressor run for much shorter intervals Vavg Mean voltage of phases 1 2 and...

Страница 20: ...re frigerant charge can condensate in the compressor crankcase A large amount will dissolve in the compressor oil un til the oil is completely saturated with refrigerant When the compressor is started...

Страница 21: ...pti mal size Crankcase heater A crankcase heater protects against the off cycle migration of refrigerant and proves effective if oil temperature is maintained 10 K above the saturat ed LP temperature...

Страница 22: ...next section Sound Compressors in operation are one of the sources of sound and vibration in a refrigeration system Both phenom ena are closely related Vibration The mounting grommets delivered with...

Страница 23: ...s and using tools chargingsystems tubes vacuum pumps etc dedicated for R404A and R507A Compressor handling mounting and connection Component Torque Nm Min Max Rotolock suction valve NTZ048 NTZ068 80 1...

Страница 24: ...rge can escape via the discharge connection and the risk of an oil mist blow out via the suction connection will be minimal Whenever possible the compressor must be the last component to be integrated...

Страница 25: ...capacity appropriate for the sys tem volume It is recommended to use connection lines with a large diameter and to connect these lines to the serv ice valves and not to the schrader con nection so as...

Страница 26: ...noted while the expansion valve setting is correct the suction line insulation between evaporator and compressor should be checked and eventually replaced by a higher qual ity insulation z A too high...

Страница 27: ......

Страница 28: ...reduce costs streamline processes and achieve your business goals Danfoss A S www danfoss com FRCC PC 002 A2 02 Replace FRCC PC 002 A1 02 May 2005 Produced by Danfoss CC DSS 02 2007 The Danfoss produc...

Отзывы: