39
MG.60.N1.22
- VLT is a registered Danfoss trademark
VLT
®
5000 / VLT
®
6000
HVAC / VLT
®
8000 AQUA
Parameter
Descriptions
803
803
803
803
803
Bus time out
Bus time out
Bus time out
Bus time out
Bus time out
Selection:
1 - 99 sec
★
1 sec
Function:
Sets the duration for the bus time out function.
If the set time passes without the drive
receiving a LonWorks message addressed to
★
Factory setting
it, the drive will take the action specified in
parameter 804,
Bus Time Out Function.
NOTE
After time out counter is reset it
must be triggered by valid control
word before new time out can be
activated.
VLT 5000 parameters are shown in parenthesis, where applicable.
Parameter
List
In addition to the parameters listed above, the
drive's control terminals issue digital inputs
that control functions similar to those provided
by nviStartStop, nviResetFault, and
nviControlWord. Parameters (502) 503
through 508 determine how the drive
responds to commands for (quick stop,
VLT 5000 only), coasting stop, DC brake,
start, reverse, setup select and preset
reference select. See
Network Drive Control
Input
in this manual and the
VLT Instruction
Manual
for more information.
Conversion
Data
PNU
Parameter Description
Default Value
Range
Index
Type
803
Bus time out
1 sec
1 - 99 sec.
0
3
804
Bus time out function
no function
0
3
805
Bit 10 function
Bit 10 = > CTW ACT
0
6
927
Parameter edit
Enable
0
6
928
Process control
Enable
0
6
970
Edit setup
Active Setup
0
5
971
Store data values
no action
0
5