29
MG.60.N1.22
- VLT is a registered Danfoss trademark
VLT
®
5000 / VLT
®
6000
HVAC / VLT
®
8000 AQUA
Drive
Feedback to
Network
The VLT LonWorks option provides 16 output
variables to the network containing important
drive and motor feedback data. Feedback data
is sent when there is a change in value. The
VLT LonWorks option will only transmit bound
network variables. Since some data changes
continuously, the transmission rate of those
variables is limited.
Min send time
specifies
the minimum time between transmissions of
variables.
The Drive Outputs (1, 2, or 3) will have a
maximum time between transmission set by the
Max send time.
This function acts as a transmit
heartbeat and allows a controller node to
determine the health of the controller/VLT
connection. The
Max send time
function is
disabled when the configuration network
variable nciMaxsendT is not configured or is set
to “0.”
Network Variable Outputs from VLT
Function
SNVT type
Variable Name
Units
Max
Min
Drive status
SNVT_state
nvoDrvStatus
16 Boolean
NA
NA
Drive output 1
SNVT_lev_percent
nvoOutputPcnt
0.005%
163.835
–163.840
Current
1)
SNVT_amp
nvoDrvCurnt
0.1 amps
3276.7
0
Energy
SNVT_elec_kwh
nvoDrvEnrg
1 kWh
65,535
0
Power
1)
SNVT_power_kilo
nvoDrvPwr
0.1 kW
6553.5
0
Statusword
SNVT_state
nvoStatusWord
16 Boolean
NA
NA
Drive output 3
SNVT_freq_hz
nvoOutputHz
0.1 Hz
6553.5
0
Output voltage
SNVT_volt
nvoVoltage
0.1 V
3276.7
–3276.8
Digital input
SNVT_state
nvoDigitlInput
16 Boolean
NA
NA
Alarm
SNVT_state
nvoAlarmWord
16 Boolean
NA
NA
Warning 1
SNVT_state
nvoWarning1
16 Boolean
NA
NA
Warning 2
SNVT_state
nvoWarning2
16 Boolean
NA
NA
DC voltage
SNVT_volt
nvoDCVolt
0.1 V
3276.7
0
Motor therm. Status
SNVT_lev_cont
nvoTempMtr
0.5 %
100
0
Inverter
therm. Status
SNVT_lev_cont
nvoTempInvrtr
0.5 %
100
0
Analog input
SNVT_volt
nvoAnalog1
0.1 V
10
0
Term. 53
Analog input
SNVT_volt
nvoAnalog2
0.1 V
10
0
Term. 54
Analog input
SNVT_amp_mil
nvoAnalog3
0,1 mA
20
0
Term. 60
Running hours
1)
SNVT_time_hour
nvoDrvRunHours
1 Hour
65534
0
Feedback
SNVT_lev_percent
nvoFeedback
0.01%
100.000
0
Frequency
SNVT_freq_hz
nvoOutputHz1
0.1 Hz
6553.5
0
Drive speed
1)
SNVT_lev_percent
nvoDrvSpeed
0.01%
100
0
Output voltage
1)
SNVT_volt
nvoDrvVolt
0.1 V
3276.7
0
VLT 5000 parameters are shown in parenthesis, where applicable.
1)
Part of the LonMark Functional Profile for
Variable Speed Drive 6010 version 1.1