32
MG.60.N1.22
- VLT is a registered Danfoss trademark
VLT
®
5000 / VLT
®
6000
HVAC / VLT
®
8000 AQUA
Bit
Value
0
1
Bit
Value
0
1
00
32768
33 OFF
33 ON
00
32768
01
16384
32 OFF
32 ON
01
16384
02
8192
29 OFF
29 ON
02
8192
03
4096
27 OFF
27 ON
03
4096
04
2048
19 OFF
19 ON
04
2048
05
1024
18 OFF
18 ON
05
1024
06
512
17 OFF
17 ON
06
512
07
256
16 OFF
16 ON
07
256
08
128
no function
08
128
09
64
no function
09
64
10
32
no function
10
32
11
16
no function
11
16
12
8
no function
12
8
Remote
Local
13
4
no function
13
4
Stopped
Running
14
2
no function
14
2
No Warning
Warning
15
1
no function
15
1
no Alarm
Alarm
Bit
Value
0
1
Bit
Value
0
1
00
32768
Alarm
Ctrl. Ready
00
32768
normal
Brake Test fail
01
16384
Alarm
Drive Ready
01
16384
normal
Trip Lock
02
8192
Safety Open
Safety Closed
02
8192
normal
AMA Fault
03
4096
No Alarm
Alarm
03
4096
normal
AMA OK
04
2048
04
2048
normal
Power Up Fault
05
1024
05
1024
normal
ASIC Fault
06
512
06
512
normal
HPFB Timeout
07
256
no Warning
Warning
07
256
normal
RS-485 Timeout
08
128
Not at Ref.
at Ref.
08
128
normal
Short circuit
09
64
Local
Bus Control
09
64
normal
Power Fault
10
32
Fr. Range Warn
Freq. in Range
10
32
normal
Ground Fault
11
16
Stopped
Running
11
16
normal
Over current
12
8
no used
Stall, Autostart
12
8
normal
Torque limit
13
4
normal
Voltage Warn.
13
4
normal
Motor Thermal
14
2
normal
Current lim.
14
2
normal
Motor Overload
15
1
normal
Therm. Warning
15
1
normal
Inverter Overload
Bit
Value
0
1
Bit
Value
0
1
00
32768
normal
Brake Test Fault
00
32768
normal
Ramping
01
16384
normal
Ctrl. Crd. Fault
01
16384
normal
AMT
02
8192
normal
Pwr. Crd. Fault
02
8192
normal
Start Fwd/Rev
03
4096
normal
HPFB Timeout
03
4096
normal
Slow down
04
2048
normal
RS-485 Timeout
04
2048
normal
Catch up
05
1024
normal
Overcurrent
05
1024
normal
FB High
06
512
normal
Torque limit
06
512
normal
FB Low
07
256
normal
Thermistor O.T.
07
256
normal
Current High
08
128
normal
Motor O.T.
08
128
normal
Current Low
09
64
normal
Inverter O.T.
09
64
normal
Freq. High
10
32
normal
U.V. Alarm
10
32
normal
Freg. Low
11
16
normal
O.V. Alarm
11
16
normal
Brake Test OK
12
8
normal
U.V. Warning
12
8
normal
Braking Max.
13
4
normal
O.V. Warning
13
4
normal
Braking
14
2
normal
Input Phase Loss
14
2
normal
Discharge OK
15
1
normal
No motor
15
1
normal
Out Freq. Range
not used
not used
not used
no function
no function
no function
no function
no function
no function
no function
no function
no function
no function
no function
no function
nvoDigitalInput
nvoDrvStatus
nvoStatusWord
nvoWarning1
nvoAlarmWord
nvoWarning2
VLT 5000 Drive
Status Bit
Definitions