
Service guide
Disassembling and assembling iSave 21
16
180R9219 | 521B1171 | DKCFN.PI.003.K5.02 / 03.2016
13. Make sure that the guide pin is located in
the location hole.
14.
Change the O-ring in the HP out
connection flange.
16. Fit the coupling into the pump.
Glue the threat on the bolt with “Loctite
270” and tighten the bolt with 10 Nm±1 Nm.
17. Change the two O-rings in the flange.
15. Bolt the flange onto the vane pump.
Tighten the bolt with 30 Nm ±3 Nm.