Quick Start Guide | ICM/ICAD Motorized Valves - Installation, Programming, and Troubleshooting

© Danfoss | DCS (MWA) | 2016.07

DKRCI.EI.HT0.B3.22 | 520H4763 | 13

Description

ICAD 

parameter Min Max

Factory 

Setting

Stored Unit

Pass 

word Comments

In ON/OFF Mode 

 

Closing speed

¡14

0

100

50/ 100

-

No

See ¡04.  

If ¡26= 1 - 3 then factory settin qg = 100 

If ¡26= 4 - 9 then factory setting = 50

Manual set point

¡15

0

100

0

No

When ¡01= 2, ¡15 determine the start up value.

Encoder operation

¡16

0

1

1

Yes

NB: Password protected. Password = 7 

0: Encoder disabled. Means ICAD operation as ICAD 600A/ICAD 600A-TS/1200A  without 

encoder 

1: Encoder enabled

Forced closing when

ICM valve Opening 

Degree < 3% 

i17

0

1

0

-

No

Enable/Disable forced closing

0: When ICM valve Opening Degree < 3% it will be forced to close regardless of    

 

requested ICM valve Opening Degree

1: When ICM valve Opening Degree < 3% no forced to closing will take place

ICM configuration

¡26

0

9

0

Yes

NB: Password protected. Password = 11 

0: No valve selected. Alarm A1 will become active. 

1: ICM 20 with ICAD 600A / ICMTS 20 with ICAD 600A-TS

2: ICM 25 with ICAD 600A

3: ICM 32 with ICAD 600A

4: ICM 40 with ICAD 1200A

5: ICM 50 with ICAD 1200A

6: ICM 65 with ICAD 1200A

7: ICM 100 with ICAD 1200A

8: ICM 125 with ICAD 1200A

9: ICM 150 with ICAD 1200A

Parameter list 

(continued)

It is possible to restore the original factory settings to the ICAD by the following procedure:

1.  Remove the power supply.

2.  Activate the up arrow and the down arrow push buttons at the same time.

3.  While pushing the up and down arrows, reconnect the power supply.

4.  Release the up and down arrows.

5.  When the display on the ICAD is alternating between CA and AI, the factory parameters have been restored.

Pre-startup Checklist

•  Valve Assembly 

 -  Bonnet bolts are secure 

 -  Seat has been replaced in body (ICM 20) 

 -  The degree of opening of the valve is 75% or less 

 -  Grease has been applied to o-ring area on valve stem 

 -  Set screws have been uniformly tightened on ICAD Actuator

•  Power has been connected to actuator ( 24 V d.c.)

•  Back up power (UPS) has been connected to actuator (optional)

•  Control Wiring has been connected 

 -  Signal input: digital or analog 

 -  Feedback wiring (optional)

•  Programming (mandatory parameters) 

 -  The mode of operation has been set (

¡

02

 -  The input signal type has been set (

¡

03

 -  The ICM valve size has been set (

¡

26

Battery back-up (optional) parameters have been established (

¡

07, 

¡

08, 

¡

12)

Содержание ICM 20

Страница 1: ...ugh 65 the function module and top cover are one part the ICAD motor actuator the brains of the valve Actuator ICAD 600A ICAD 1200A Old ICAD 600 Old ICAD 900 Old ICAD 1200 Valve Size ICM 20 ICM 40 ICM...

Страница 2: ...T0 B3 22 520H4763 2 Contents Page ICM ICAD overview 1 Identifying ICM sizes 3 1st and 2nd generation ICAD differences 4 Installation 5 Wiring the ICAD actuator 7 Electrical data 7 ICAD Programming 11...

Страница 3: ...cone which forms more of a conical shape Identifying ICM sizes All ICM sizes except ICM 20 have a stainless steel ID tag located around the valve stem on the top cover which the ICAD mounts on When th...

Страница 4: ...whereas the 2nd generation has the cables mounted on connectors located in the aluminum body Note The wire colors are different between the two generations and the following is a table with the differ...

Страница 5: ...e a 13mm socket and to remove the ICM20 B66 ICM 20 B or ICM20 C valve seat use a 12 mm hex key ICM 25 to 65 1 to 2 1 2 valves the integrated bonnet and function module should be removed as shown in th...

Страница 6: ...the bolts and torque to the following specifications 5 Install the ICAD Motor on the ICM valve The ICM valve must not be in its full opened position while the ICAD motor is calibrated with the valve...

Страница 7: ...50 OFF contact impedance 100 k Digital Output 3 pcs NPN transistor output External Supply 5 24 VDC same supply as for ICAD can be used but note that galvanically isolated system will be spoiled Output...

Страница 8: ...input for valve position feedback Passive 4 20 mA PLC input for valve position feedback Black Optional UPS battery back up Active 4 20 mA PLC output to control ICAD Power supply cable Control cable Te...

Страница 9: ...al ICAD ICM Valve Position Feedback ICAD 2nd gen blue 24 V AC L N 1 2 3 orange ICAD 2nd gen 2010 yellow brown white 24 V 15 V 5 V COM AI 5 AI 4 AI 3 AI 2 AI 1 COM COM DI 2 DI 1 COM R120 CAN H CAN L GN...

Страница 10: ...ange White Brown 24 V d c Power Supply Power Supply Black Optional UPS battery back up Wiring diagram showing ICAD digital outputs wired with customer supplied auxiliary relays NOTE The same 24 V d c...

Страница 11: ...gree in unless there is an alarm or the parameter list is being viewed The display will also indicate Mod if being controlled by an analog input signal modulating mode or if being controlled by digita...

Страница 12: ...setting 50 If ICM is opening and 04 33 or ICM is closing and 14 33 Low is displayed If ICM is opening and 33 If 04 66 or ICM is closing and 33 If 14 66 Med is displayed If ICM is opening and 04 67 or...

Страница 13: ...32 with ICAD 600A 4 ICM 40 with ICAD 1200A 5 ICM 50 with ICAD 1200A 6 ICM 65 with ICAD 1200A 7 ICM 100 with ICAD 1200A 8 ICM 125 with ICAD 1200A 9 ICM 150 with ICAD 1200A Parameter list continued It...

Страница 14: ...I1 ON If 02 3 two digits are shown 00 DI1 OFF DI2 OFF 10 DI1 ON DI2 OFF 01 DI1 OFF DI2 ON 11 DI1 ON DI2 ON DO Status for ICM closed 55 0 1 1 DO ON when OD 3 0 DO OFF DO status for ICM opened 56 0 1 1...

Страница 15: ...gs on the module for ICM 25 and larger For size ICM 20 make sure valve seat is installed The valve does not appear to be moving to the correct position Check service value 51 This is the mA input from...

Страница 16: ...e is approximately 50 watts How can I monitor the valve position remotely The control wiring bundle provides for a 4 to 20 mA or 0 to 20 mA signal output with the blue and orange wires The signal can...

Страница 17: ...Quick Start Guide ICM ICAD Motorized Valves Installation Programming and Troubleshooting Danfoss DCS MWA 2016 07 DKRCI EI HT0 B3 22 520H4763 17...

Страница 18: ...Danfoss DCS MWA 2016 07 DKRCI EI HT0 B3 22 520H4763 18 www danfoss us Industrial_Refrigeration...

Отзывы: