Troubleshooting

Overview

The ICAD actuator has a number of very useful service parameters which should always be consulted first.  

In addition, a manual tool should always be available to manually close the valve completely in the event 

the ICAD has failed.  When using the manual tool, turn the tool clockwise to open the valve and counter-

clockwise to close the valve.

NOTE: 

When rotating the valve manually you are changing the position of the valve to a value different 

than what is in the actuator’s memory.  Therefore, a calibration must be performed when ICAD is 

remounted to the valve.  If power is cut from the actuator prior to using the manual tool or after 

the valve has been adjusted, no problem will occur as the valve will automatically recalibrate itself 

once power is restored.  Power can easily be disconnected and reconnected by unscrewing and then 

reconnecting the power cable from the ICAD actuator.

Service parameter (View only)

Alarms

Description

ICAD 

parameter

Min

Max

Unit

Comments

OD %

¡50

0

100

%

ICM valve Opening Degree

AI [mA]

¡51

0

100

mA

Analog input signal

AI [V]

¡52

0

100

V

Analog input signal

AO [mA]

¡53

0

100

mA

Analog output signal

DI Digital input Status

¡54

0

1

-

DI signals. Depending of ¡02 

If ¡02  = 2, one digit is shown. 

0 : DI1 = OFF

1 : DI1 = ON

If ¡02 = 3, two digits are shown.  

00 : DI1 = OFF, DI2 = OFF 

10 : DI1 = ON, DI2 = OFF 

01 : DI1 = OFF, DI2 = ON 

11 : DI1 = ON, DI2 = ON

DO Status for ICM closed

¡55

0

1

-

1: DO = ON when OD < 3 %; 

0: DO = OFF

DO status for ICM opened

¡56

0

1

-

1: DO = ON when OD > 97 %

0: DO = OFF

DO Alarm status

¡57

0

1

-

1: DO = ON when a Alarm is detected

0: DO = OFF

Display mP SW ver. 

¡58

0

100

-

Software version for display microprocessor

Motor mP SW ver. 

¡59

0

100

-

Software version for motor microprocessor 

Description

ICAD alarm text

Definition of event

Comments

No Valve type selected

A1

Alarm ON

At start-up A1 will be displayed until parameter ¡26 is set

Controller fault

A2

Alarm ON

Internal fault inside electronics. 

Carry out:

1) Power OFF and Power ON 

If A2 still active.

2)  Make a Reset to factory setting

If A2 still active. Return ICAD to Danfoss

Analog input error

A3

Alarm ON

Not active if ¡01 = 2, or ¡02 = 2

When ¡03 = 1 and AI A > 22 mA

When ¡03 = 2 and AI A > 22 mA

or AI A < 2 mA

When ¡03 = 3 and AI A > 12 V

When ¡03 = 4 and AI A > 12 V

or AI A < 1 V

Low voltage of fail safe 

Supply

A4

Alarm ON

If 5 V < fail safe supply

<18 V. Enabled by ¡08

Check supply to ICAD

A5

Alarm ON

If supply voltage < 18 V

Calibration extended failed

A6

Alarm ON

Check valve type selected.

Check presence of foreign debris inside ICM valve

Thermal overload

A8

Alarm ON

ICAD stepper motor temperature too high

Valve locked

A9

Alarm ON

Only active if i16 = 1

If the ICM valve is locked for more than 15 seconds (unable to reach its requested 

position) A9 will flashin display.

A9 alarm can only be reset by Power OFF/ON of ICAD

Note: old alarms that may not be active anymore will be saved and listed in paramenter i11

Содержание ICM 20

Страница 1: ...ugh 65 the function module and top cover are one part the ICAD motor actuator the brains of the valve Actuator ICAD 600A ICAD 1200A Old ICAD 600 Old ICAD 900 Old ICAD 1200 Valve Size ICM 20 ICM 40 ICM...

Страница 2: ...T0 B3 22 520H4763 2 Contents Page ICM ICAD overview 1 Identifying ICM sizes 3 1st and 2nd generation ICAD differences 4 Installation 5 Wiring the ICAD actuator 7 Electrical data 7 ICAD Programming 11...

Страница 3: ...cone which forms more of a conical shape Identifying ICM sizes All ICM sizes except ICM 20 have a stainless steel ID tag located around the valve stem on the top cover which the ICAD mounts on When th...

Страница 4: ...whereas the 2nd generation has the cables mounted on connectors located in the aluminum body Note The wire colors are different between the two generations and the following is a table with the differ...

Страница 5: ...e a 13mm socket and to remove the ICM20 B66 ICM 20 B or ICM20 C valve seat use a 12 mm hex key ICM 25 to 65 1 to 2 1 2 valves the integrated bonnet and function module should be removed as shown in th...

Страница 6: ...the bolts and torque to the following specifications 5 Install the ICAD Motor on the ICM valve The ICM valve must not be in its full opened position while the ICAD motor is calibrated with the valve...

Страница 7: ...50 OFF contact impedance 100 k Digital Output 3 pcs NPN transistor output External Supply 5 24 VDC same supply as for ICAD can be used but note that galvanically isolated system will be spoiled Output...

Страница 8: ...input for valve position feedback Passive 4 20 mA PLC input for valve position feedback Black Optional UPS battery back up Active 4 20 mA PLC output to control ICAD Power supply cable Control cable Te...

Страница 9: ...al ICAD ICM Valve Position Feedback ICAD 2nd gen blue 24 V AC L N 1 2 3 orange ICAD 2nd gen 2010 yellow brown white 24 V 15 V 5 V COM AI 5 AI 4 AI 3 AI 2 AI 1 COM COM DI 2 DI 1 COM R120 CAN H CAN L GN...

Страница 10: ...ange White Brown 24 V d c Power Supply Power Supply Black Optional UPS battery back up Wiring diagram showing ICAD digital outputs wired with customer supplied auxiliary relays NOTE The same 24 V d c...

Страница 11: ...gree in unless there is an alarm or the parameter list is being viewed The display will also indicate Mod if being controlled by an analog input signal modulating mode or if being controlled by digita...

Страница 12: ...setting 50 If ICM is opening and 04 33 or ICM is closing and 14 33 Low is displayed If ICM is opening and 33 If 04 66 or ICM is closing and 33 If 14 66 Med is displayed If ICM is opening and 04 67 or...

Страница 13: ...32 with ICAD 600A 4 ICM 40 with ICAD 1200A 5 ICM 50 with ICAD 1200A 6 ICM 65 with ICAD 1200A 7 ICM 100 with ICAD 1200A 8 ICM 125 with ICAD 1200A 9 ICM 150 with ICAD 1200A Parameter list continued It...

Страница 14: ...I1 ON If 02 3 two digits are shown 00 DI1 OFF DI2 OFF 10 DI1 ON DI2 OFF 01 DI1 OFF DI2 ON 11 DI1 ON DI2 ON DO Status for ICM closed 55 0 1 1 DO ON when OD 3 0 DO OFF DO status for ICM opened 56 0 1 1...

Страница 15: ...gs on the module for ICM 25 and larger For size ICM 20 make sure valve seat is installed The valve does not appear to be moving to the correct position Check service value 51 This is the mA input from...

Страница 16: ...e is approximately 50 watts How can I monitor the valve position remotely The control wiring bundle provides for a 4 to 20 mA or 0 to 20 mA signal output with the blue and orange wires The signal can...

Страница 17: ...Quick Start Guide ICM ICAD Motorized Valves Installation Programming and Troubleshooting Danfoss DCS MWA 2016 07 DKRCI EI HT0 B3 22 520H4763 17...

Страница 18: ...Danfoss DCS MWA 2016 07 DKRCI EI HT0 B3 22 520H4763 18 www danfoss us Industrial_Refrigeration...

Отзывы: