DKRCI.PI.FN1.C3.ML / 520H8211 

© Danfoss | DCS (MWA) | 2015.05

ENGLISH

Refrigerants

Applicable to HCFC, HFC, R717 (Ammonia),

R744 (CO

2

) and all flammable refrigerants.

The strainer is only recommended for use 

in closed circuits. For further information 

please contact your local Danfoss sales 

office.
Pressure and temperature range

–60/+150°C (–76/+302°F)

FIA SS 15-65:

The strainers are designed for a max. 

working pressure of 52 bar (754 psi g)

Installation

Note: 

At delivery the strainer housing 

is not equipped with strainer 

element or accessories

The strainer must be installed with the top 

cover downwards, and the flow must be 

directed towards the top cover as indicated 

by the arrow on the strainer housing (fig. 

1).  The strainer element must be inserted 

after welding.

The strainer housing is designed to 

withstand a high internal pressure. 

However, the piping system should be 

designed to avoid liquid traps and reduce 

the risk of hydraulic pressure caused by 

thermal expansion. It must be ensured 

that the strainer is protected from pressure 

transients like “liquid hammer” in the 

system.       

Recommended flow direction

The strainer must be installed with the flow 

towards the top cover as indicated by the 

arrow on the side of the valve body (fig. 

1). Flow in the opposite direction is not 

acceptable. 

Welding

To prevent damage to the gasket between 

the strainer body and top cover, the top 

cover should be removed before welding 

and protect it from dirt and moisture (fig. 

2).

Only materials and welding methods, 

compatible with the valve housing 

material, must be welded to the valve 

housing. 

 

Clean the strainer housing internally to 

remove welding debris at completion 

of welding and before the valve is 

reassembled. 

Removing the top cover can be omitted 

provided that:

The temperature in the area between the 

valve body and top cover during welding 

does not 150°C/+302°F. 

This temperature depends on the welding 

method as well as on any cooling of the 

strainer body during the welding itself. 

(Cooling can be ensured by, for example, 

wrapping a wet cloth around the strainer 

body.) Make sure that no dirt, welding 

debris etc. get into the strainer during the 

welding procedure.

The strainer housing must be free from 

stresses (external loads) after installation.

Strainers must not be mounted in systems 

where the outlet side of the strainer is 

open to atmosphere. The outlet side of the 

strainer must always be connected to the 

system or properly capped off, for example 

with a welded-on end plate.

Assembly

Remove welding debris and any dirt from 

pipes and strainer body before assembly. 

Check that the strainer element has 

the right size before it is inserted in the 

top cover and check that the gasket is 

undamaged.

Place the strainer element (pos. D) from 

underneath. The element has a slight force 

fit into the housing, no gaskets or O-rings 

are used. 

If magnet inserts have been chosen as 

accessory, fit those on the top cover before 

replacing the cover.

Tightening

Tighten the top cover with a torque 

wrench, to the values indicated in the table 

(fig. 3).

Please note that the table (fig. 3)

containing maximum torque must be

adhered to and never exceeded.

If the drain valve has been chosen as 

accessory, the drain plug should be 

replaced by the drain valve.

Colours and identification

The FIA SS valves are painted with a 

red oxide primer in the factory. Precise 

identification of the valve is made via the 

ID plate on the top cover, as well as by the 

stamping on the valve body. The external 

surface of the valve housing must be 

prevented against corrosion with a suitable 

protective coating after installation and 

assembly.

Be sure to protect the ID plate when 

repainting the valve.

Maintenance

Mounting of accessory: 

Strainer bag (fig. 4)

A 50µ strainer bag (pos. E), especially for 

commissioning of the plant, can replace 

the normal strainer element.

Mount the strainer bag (held in place by 

the strainer holder) and be sure to place 

the strainer bag correctly in the strainer as 

shown in fig. 4.

The flow must go into the strainer bag 

cavity and out or else the bag will not 

function properly.

Dismantling the strainer (fig. 3)

Before servicing the strainer, isolate it from 

the system and remove all refrigerant by 

evacuation to zero pressure. Check for 

refrigerant pressure before unscrewing and 

removal of the top cover.

The strainer element must be removed 

without any use of tools

Cleaning

Clean the strainer element using an 

appropriate solvent by flushing and 

brushing. The use of strong acids cannot be 

recommended. The strainer element must 

be wiped or blown dry before inspection. If 

the element is damaged or the sediments 

cannot be removed, the strainer element 

must be replaced.

Assembly

Remove any dirt from the body before the 

strainer is assembled. 

Replacement of gasket

Change the gasket for the top cover (pos. 

C) and drain plug.

Check that the strainer element is correctly 

placed before remounting the top cover 

and bolts (pos. A).

Tightening (fig. 3)

Tighten the top cover bolts (pos. A) with 

a torque wrench according to the table in 

fig. 3

Use only original Danfoss parts (including  

gaskets) for replacement. Materials of 

new parts are certified for the relevant 

refrigerant. 

In cases of doubt, please contact your local 

Danfoss sales office. 

Содержание FIA SS 15-65

Страница 1: ...ro ni ning n tipo de accesorio Nota Alla consegna l involucro del filtro non dotato dell elemento filtrante o di accessori Uwaga W dostarczanym korpusie filtra nie ma wk adu ani akcesori w Striner bag...

Страница 2: ...and any dirt from pipes and strainer body before assembly Check that the strainer element has the right size before it is inserted in the top cover and check that the gasket is undamaged Place the st...

Страница 3: ...setzt wird ist sicher zu stellen dass es die richtige Gr e hat Auch sicherstellen dass die Dichtung nicht besch digt ist Das Filtersieb Pos D von unten einsetzen Das Filtersieb hat leichte Presspassun...

Страница 4: ...st la bonne taille avant de l ins rer dans le couvercle sup rieur et v rifiez que le joint d tanch it n est pas endommag Placez l l ment filtrant pos D par le dessous L l ment s ajuste au corps en for...

Страница 5: ...r a su montaje Compruebe que la malla de filtro tiene un tama o correcto antes de introducirla en la tapa superior asimismo compruebe que la junta no est da ada Coloque la malla de filtro pos D desde...

Страница 6: ...corrette prima di inserirlo nel coperchio superiore e verificare che la guarnizione non sia danneggiata Posizionare l elemento filtrante pos D dal basso L elemento viene montato applicando una legger...

Страница 7: ...ss DCS MWA 2015 05 DKRCI PI FN1 C3 ML 520H8211 7 HCFC HFC R717 R 744 Co 2 Danfoss 60 150 C 76 302 F FIA SS 15 65 52 bar 754 psi g 1 1 2 150 C 302 F D O 3 3 FIA SS ID ID 4 50 E 4 3 C A 3 3 A Danfoss Da...

Страница 8: ...uszczelka jest nieuszkodzona Za o y wk ad filtra poz D od do u Wk ad wchodzi do obudowy na lekki wcisk nie s stosowane adne uszczelki ani pier cienie O ring Je eli jako wyposa enie dodatkowe wybrano w...

Страница 9: ...Danfoss DCS MWA 2015 05 DKRCI PI FN1 C3 ML 520H8211 9 R717 R744 CO2 Danfoss 60 150 C 76 302 F FIA SS 15 65 52 754 1 1 2 150 C 302 F D 3 3 FIA SS 4 50 E 4 3 C A 3 A 3 Danfoss...

Страница 10: ...10 DKRCI PI FN1 C3 ML 520H8211 Danfoss DCS MWA 2015 05...

Отзывы: