Illustration 2.1 Top and Bottom Cooling Clearance
Enclosure
A1-A5
B1-B4
C1, C3
C2, C4
a/b [mm]
100
200
200
225
Table 2.1 Minimum Airflow Clearance Requirements
2.3.2 Lifting
•
Check the weight of the unit to determine a safe
lifting method
•
Ensure that the lifting device is suitable for the
task
•
If necessary, plan for a hoist, crane, or forklift with
the appropriate rating to move the unit
•
For lifting, use hoist rings on the unit, when
provided
2.3.3 Mounting
•
Mount the unit vertically
•
The frequency converter allows side by side
installation
•
Ensure that the strength of the mounting location
will support the unit weight
•
Mount the unit to a solid flat surface or to the
optional back plate to provide cooling airflow
(see
and
•
Improper mounting can result in over heating
and reduced performance
•
Use the slotted mounting holes on the unit for
wall mounting, when provided
130BA219.10
A
Illustration 2.2 Proper Mounting with Back Plate
Item A is a back plate properly installed for required
airflow to cool the unit.
130BA228.10
A
Illustration 2.3 Proper Mounting with Railings
NOTE
Back plate is needed when mounted on railings.
2.3.4 Tightening Torques
See
10.4 Connection Tightening Torques
for proper
tightening specifications.
Installation
VLT
®
AutomationDrive Operating
Instructions
10
MG33AM02 - VLT
®
is a registered Danfoss trademark
2
2
Содержание FC 300
Страница 1: ...MAKING MODERN LIVING POSSIBLE Operating Instructions VLT AutomationDrive FC 300 0 25 75 kW...
Страница 2: ......
Страница 4: ...Safety VLT AutomationDrive Operating Instructions MG33AM02 VLT is a registered Danfoss trademark...
Страница 99: ...Index VLT AutomationDrive Operating Instructions MG33AM02 VLT is a registered Danfoss trademark 95...
Страница 100: ...www danfoss com drives MG33AM02 130R0300 MG33AM02 Rev 2012 11 02...