12 QUICK STOP ACTIVE SWITCH ON DISABLED
→
Event: - Quick stop has been completed or - “Disable-Voltage” command
Action: - Disable drive function
- The power section can be switched off
13 All states MALFUNCTION REACTION ACTIVE
→
Event: - Drive malfunction detected Action: - Trigger malfunction reaction depending on the fault
14 MALFUNCTION REACTION ACTIVE MALFUNCTION
→
Event: - Malfunction reaction concluded
Action: - Disable drive function
- The power section can be switched off
15 MALFUNCTION SWITCH ON DISABLED
→
Event: - “Malfunction-Reset” command
Condition: - Malfunction is no longer present
Action: - Malfunction reset is executed