3.5.4. Custom Telegram 1
In order to interface with the Interbus option, running Custom Telegram 1, the following parameters must be set on the FC 300:
Parameter
Parameter name
Setting
8-40
Telegram Selection
[200] Custom Telegram 1
3-15
Reference Resource 1
[0] No Function
3-16
Reference Resource 2
[0] No Function
5-01
Terminal 27 mode
[1] Output
5-02
Terminal 29 mode
[1] Output
5-10
Terminal 18 Digital Input
[0] No Operation
5-11
Terminal 19 Digital Input
[0] No Operation
5-12
Terminal 27 Digital Input
[0] No Operation
5-15
Terminal 33 Digital Input
[0] No Operation
5-30
Terminal 27 Digital Output
[45] Bus controlled
[46] Bus controlled, 1 if timeout
[47] Bus controlled, 0 if timeout
5-31
Terminal 29 Digital Output
[45] Bus controlled
[46] Bus controlled, 1 if timeout
[47] Bus controlled, 0 if timeout
5-40 [0]
Function Relays, Relay 1
[45] Bus controlled
[46] Bus controlled, 1 if timeout
[47] Bus controlled, 0 if timeout
5-40 [1]
Function Relays, Relay 2
[45] Bus controlled
[46] Bus controlled, 1 if timeout
[47] Bus controlled, 0 if timeout
8-10
Control Word Profile
[0] FC profile
[1] PROFIdrive profile (= Drivecom)
NB!
If the Interbus option is powered up without connection to a FC300 frequency converter, it will run Standard Telegram 1.
This means that it will not be possible to use any I/O’s.
NB!
For the digital- and relay-outputs the reaction in case of a bus-timeout can be selected.
Bus ctrl. [45]
: The output is controlled via bus. In case of a bus-timeout the output state is kept at the last known state.
Bus ctrl. 1 if timeout [46]
: The output is controlled via bus. In case of a bus-timeout the output state is set to logical 1.
Bus ctrl. 0 if timeout [47]
: The output is controlled via bus. In case of a bus-timeout the output state is set to logical 0.
NB!
Setting par. 8-10 to [1]
PROFIdrive profile
, enables the Drivecom Profile on the Interbus option, i.e. Control word and Status word are
interpreted as Drivecom.
Setting par. 8-10 to [0]
FC Profile
will enable the FC profile on the frequency converter.
See section
How to Control the FC 300
for more information on the different profiles.
NB!
Par. 0-40 [Hand on] key on LCP.
If the Hand button on the FC 300 is activated, control of the frequency converter via the Interbus interface is disabled.