Euu
"
Min. no
Max. yes
Default yes
EWU active on/OFF
Enable or disable early wake up.
"
CLH
"
Min. 0 hour
Max. 24 hour
Default 6 hour
Shop close hour
Shop is assumed to be closed when staying in ECO mode longer than shop close hour.
"
ErL
"
Min. 0 min
Max. 240 min
Default 120 min
Early wake up time offset
Time of exiting ECO mode for next day=
Time of first activity to exit ECO mode - the early wake-up time.
"
0
": early wake up function disabled."
"
HoL
"
Min. 0 hour
Max. 999 hour
Default 72 hour
Holiday Length
If controller stays for longer than HoL in ECO and no activity is detected, the controller will go into Holiday Mode. Early Wake Up
is disabled.
ECA
ECO management
"
Eto
"
Min. -25,0 K
Max. 25.0 K
Default 4.0 K
Eco Temperature Offset
This parameter gives a relative temperature in degrees. It is the difference in temperature for ECO mode operation compared to
normal mode.
NOTE: setting a temperature offset may be illegal in some jurisdictions.
"
Hto
"
Min. -25.0 K
Max. 25.0 K
Default 6.0 K
Holiday Temperature Offset
Increase or decrease of temperature with respect to normal mode
during holiday mode.
"
diE
"
Min. 0.0 K
Max. 10.0 K
Default 2.0 K
ECO Differential
Thermostat differential for ECO.
"
FoE
"
Min. 0 s
Max. 960 s
Default 0 s
ECO Fan on cycle
On time for fan during compressor OFF period in ECO mode.
"
FSE
"
Min. 0 s
Max. 960 s
Default 0 s
ECO Fan stop cycle
OFF time for fan during compressor OFF period in ECO mode.
"
ELC
"
Default on
ECO Cabinet light control
"
on
": always ON (Button is default to control light for all these options).
"
oFF
": always OFF.
"
dor
": door sensor only.
"
ELd
"
Min. 0 min
Max. 10 min
Default 5 min
Eco Light Delay
This parameter causes a delay to the switch from normal to ECO mode
when the shop lights are switched ON or OFF. The ambient light sensor
detects the change in light level and causes a switch mode. With this
parameter set to zero, the switch OFF mode occurs immediately.
If not set to zero (max: 10 minutes), then the change will be delayed by
the number of minutes set.
ASi
Assignments settings
"
uSA
"
Min. no
Max. yes
Default no
MODBUS Safety
"
no
": MODBUS auto detection is enable and serial communication is available for configuration KoolProg Software.
"
yES
": MODBUS communication is deactivated.
User Guide | ERC 112 Refrigeration Controller
20 | BC200686422115en-000802
© Danfoss | DCS (vt) | 2019.07